Page 4
7038-201D
October 12, 2015
5700 Step Top ACC Wood Burner
DESCRIPTION
Hawkwind Kit
Shall be Fitted
A
Min. Clearance from
fi
rebox to rear wall
200mm
B
Min. clearance from
fi
rebox to side wall
330mm
C
Min. distance from
fi
rebox opening to
fl
oor protector front
450mm
D
Min. distance from
fi
rebox to
fl
oor protector side
76mm
E
Min. distance from
fl
ue centre to side wall
673mm
F
Depth of
fl
oor protector
1210mm
G
Width of
fl
oor protector
850mm
Minimum
fl
oor protector thickness
6mm
Quadra-
fi
re 5700 Step Top ACC does not require a insulating Floor Protector, as they are tested and
comply with the minimum Floor Protector requirements of
AS/NZS 2918:2001.
Note:
▪
The minimum Floor Protector sizes are speci
fi
ed in the clearance chart, see Table 1 & 2.
▪
A Floor Protector can include ceramic tiles with grouted joints
fi
xed directly onto a wooden
fl
oor or
a sheet of toughened glass, panel steel or any other non combustible material laid directly onto a
wooden
fl
oor.
▪
If installed directly onto a concrete slab, the concrete slab can be considered as the
fl
oor
protector,but must maintain the minimum measurement listed.
FLOOR PROTECTOR
PARALLEL POSITIONING
NOTE: HEAT SHIELD REQUIREMENTS FOR HEAT SENSITIVE WALLS
Clearances may be reduced by provision of an appropriately located heat shield refer to
AS/NZS 2198:2001 3.2.3 TABLE 3.1
Table 1
Fig. 3
Drawing not to scale
A
E
B
F
D
C
G