Quadra-Fire 57ST-ACC-AU Installation Instructions Manual Download Page 6

Page  6

7038-201

July 19, 2012

R

5700 Step Top ACC Wood Burner

▪ Flue pipe installed crimp/narrow end down

▪ Outer casings installed crimped/narrow end up. (Critical when exposed above the roof)

▪ Inner casings - direction not critical

▪ Flue pipes  - seal all joints including firebox spigot.

- fix with a minimum of 3 stainless steel rivets

▪ Flue pipe spacers - affix to flue pipe

▪ Flue system termination point - Refer to AS/NZS 2918:2001 4.9.1, see Fig. 9.

▪ Flue pipe shall extend not less than 4.6m above top of the floor protector as per

AS/NZS 2918:2001 4.9.1(a)

▪ Façade or chase systems  -  same rule applies as above.

▪ Roof penetration and flashing method refer to NZ Building Code E2.(From 01/07/05)

Note: These instructions apply to 150mm diameter flue pipe systems as tested to

AS/NZS 2918:2001

1.  Either locate the appliance in position or by measuring at the ceiling mark the flue pipe centre position. 

Check that the outer casing is unobstructed through the attic space or roof area.

2.  Spike the centre with a nail. Transfer this position to the next surface above. Plumb bob/laser.

3.  Cut out the ceiling penetration hole – square or rectangle – short axis equals outer casing diameter 

plus 50mm, long axis as required. See Table 5 . Perform the same at the roof penetration.

4.  Frame out the hole with minimum  75 x 50 timber or as required  for roofing material. Minimum 

requirement at roof penetration see NZ Building Code E2 Acceptable Solution (from 01/07/05).

5.  Install the outer casing so that :-

  (i) lower end is flush with the underside of the ceiling material and

  (ii) with the addition of metal “L” brackets, affix to the outer casing at 90 degrees secure the outer 

casing centrally to the ceiling and roof nogs.  Alternatively substitute the “L” brackets for 25mm thick 

non heat sensitive packers. Secure the outer casing through the packers with horizontal fixings to 

the nogs. Refer to the General Instruction for termination height. The option of outer casing slips to 

be taken into account.

6.  Flash the outer casing to the roof material with the appropriate approved flashing.

7.  If using an outer/inner casing combination, now install the inner casing ensuring it extends a minimum 

200mm above the high side of the roof penetration. If not using a combination see ‘11’ below.

8.  Refer to Firebox Installation, points 1 & 2.

9.  Prepare the ceiling plate and place upside down over the flue spigot.

10. Install the flue pipes by preferred method – either up or down the outer casing. Affix each length 

per the notes in General Instructions (above). Extend the flue pipe  above the outer

casing to suit the casing cover/cowl assembly.

11. If the inner casing has not been installed, install now. Refer to 7 above  for minimum height.

12. Install the cowl assembly, i.e. Top spacer, casing cover and cowl.

13. Position and secure the ceiling plate with the screws and spacers.

14. Wipe the flue pipe to remove finger marks.

15. Refer to Firebox Installation, point 3.

16. If flue offset is required, refer to AS/NZS 2918:2001 4.1

GENERAL INSTRUCTIONS FOR FLUE SYSTEM

Summary of Contents for 57ST-ACC-AU

Page 1: ...stallations with tested flue systems as per AS NZS 2918 2001 Appendix F with a ceiling angle between 0 30 inclusive For installations with a ceiling angle greater than 30 refer to Fig 6 7 and AS NZS 2...

Page 2: ...yment in the warmth and comfort of your hearth appliance Thank you for choosing Quadra Fire 5700 STEP TOP ACC JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC 2012 2013 2014 INSTALLATION DATE MILLENNIU...

Page 3: ...700 STEP TOP ACC Wood Burner Dimensions Pedestal Model Quadra Fire 5700 STEP TOP ACC Wood Burner Dimensions Leg Model 33 mm 245 mm 662 mm 945 mm 89 mm 94 mm 699 mm 94 mm 686 mm 535 mm 280 mm 435 mm 37...

Page 4: ...are tested and comply with the minimum Floor Protector requirements of AS NZS 2918 2001 Note The minimum Floor Protector sizes are specified in the clearance chart see Table 1 2 A Floor Protector can...

Page 5: ...projection from wall 841 E Min overall floor protector depth 1615 F Min floor protector front width 850 CORNER POSITIONING 45 Drawing not to scale Table 2 Fig 4 FIREBOX INSTALLATION 1 If a separate f...

Page 6: ...ceptable Solution from 01 07 05 5 Install the outer casing so that i lower end is flush with the underside of the ceiling material and ii with the addition of metal L brackets affix to the outer casin...

Page 7: ...ombustible material Non combustible material Hebel block or 12mm Promina board or similar under the flashing 25 25 Approved Flashing Roof Line Inner Casing 200mm above roof line Outer Casing Inner Cas...

Page 8: ...g 4 6 downward distance of casing and 3 x flue distance of the ceiling plate ADD Cowl Casing Cover Spider Bracket Approved Flashing A Ceiling Plate Batten A 3 x flue pipe Ceiling flue pipe Fig 7 ADD C...

Page 9: ...g the entral tongue to locate inside the flue outlet only Two tabs are provided and if folded back at 90 degrees the bracket and Flue Mounted Shield will mount lower onto the appliance The Flue Mounte...

Page 10: ...TION IS CONSIDERED THE MAN UFACTURER SHOULD BE CONSULTED IN THE FIRST INSTANCE CAUTIONS CRACKED AND BROKEN COMPONENTS e g GLASS PANELS OR CERAMIC TILES MAY RENDER THE INSTALLATION UNSAFE WARNING ANY M...

Page 11: ...July 19 2012 7038 201 Page 11 R 5700 Step Top ACC Wood Burner Service And Maintenance Log Date of Service Performed By Description of Service...

Page 12: ...TOVE DO NOT DISCARD THIS MANUAL CAUTION Important operating and maintenance instruc tions included Leave this manual with party responsible for use and operation Read understand and follow these instr...

Reviews: