January
13,
2020 7047-910J
9
5100 Insert ACC
SIDE
TRIM
SIDE
W
ALL
TOP TRIM
27-1/4
692mm
32-1/4
819mm
HEARTH
EXTENSION
USA 16-3/4
CANADA
24-3/4 (629mm)
40-11/16
1033mm
FIREPLA
CE FR
ONT SURF
ACE
USA 23-1/2
CANADA 25-1/2 (648mm)
HEARTH EXTENSION
43-11/16
1110mm
12in max
MANTEL
No thermal protection required
ember protection only
C
D
A
B
Minimum Opening Dimensions
Inches
Millimeters
A
Height
22-1/4
565
B
Front Width
29-3/8
746
C
Back Width
25-3/4
654
D Depth
17-7/8
454
B. Clearances to Combustibles
United States and Canada (UL and ULC)
In Canada a full length 6 inch (152mm) S635 flue liner required as per ULC S628.
In USA a minimum 5 ft length (1.82m), 6 inch (152mm) diameter flue liner is required as per UL 1482.
NOTE:
Minimum opening dimensions include a 1/4”
(6mm) clearance around unit.
NOTE:
If trim measurement is over 3/4 in (19mm)
in depth use mantle or side clearances to
combustibles.
NOTE:
Clearances may only be reduced by means
approved by the regulatory authority having
jurisdiction
Fire Risk.
•
Comply with all minimum clearances to
combustibles as specified.
•
Failure to comply may cause house fire.
WARNING