Page 15
5100-I ACT WOOD INSERT
R
438-0380E
April 21, 2010
UL 1777 Insulated Stainless Steel
Liner or Other Approved Lining System
Follow Manufacturer’s Instructions
on Insulation and Support
For Zero or Other Non-Code Clearances,
Follow Approved Liner Manufacturer’s Specific
Insulation Requirements: Different Clearances
May Require Different Specifications
Masonry Chimney Must
Have Structural Integrity
UL 1777 Insulated Stainless Steel
Liner or Other Approved Lining System
Minimum 8 in. (203mm) Masonry
Thickness in Front of Smoke Chamber
Damper Plate Removed or
Fastened in Open Position
Seal with Non-Combustible Material
Minimum Clearance in Accordance
with Insert Listing
Floor Protection in
Accordance with Insert
Listing
Follow Manufacturer’s
Instructions for Maximum
Liner Extension Above
Chimney
Maximum 30
Degrees
Offset in Chimney
Combustible Floor
Masonry Chimney (Cont’d)
Figure 15.1
NOTE:
In Canada, this fireplace insert must be installed
with a continuous chimney liner of a 6 inch (152mm) diam-
eter extending from the fireplace insert to the the top of the
chimney. The chimney liner must conform to the Class
requirements of CAN/ULC-S65, Standard for Lining Sys
-
tems for Existing Masonry or Factory-Built Chimneys and
Vents, or CAN/ULC-S60, Standard for Lining Systems
for New Masonry Chimneys.
The Quadra-Fire 5100-I Insert conforms with the UL 18
and ULC S68 (Canada) in all respects, and is approved to
UL & ULC safety standards for installation and use within a
fireplace with a masonry chimney in accordance with NFPA
11 and CAN/CSA-B65-01.
NOTE:
Installation into fireplaces without a permit will
void the listing.