438-0380E

   

 D.  Masonry Chimney

  • Must meet minimum standards of NFPA 11.
  • Must  have  at  least  5/8  inch  (16mm)  fireclay  lining  joined 

with refractory cement.   (Installations into a clay flue without 

a  stainless  steel  liner  may  reduce  draw  which  affects 

performance,  will  cause  the  glass  to  darken  and  produce 

excessive creosote).

  • 

The masonry wall of the chimney, if brick or modular block, 

must be a minimum of  inches (10mm) nominal thickness.

  • 

A chimney of rubble stone must be at least 12 inches (305mm) 

thick.

  • Cross-sectional  area  should  be  no  more  than  3  times  the 

cross-sectional area of the flue collar of the insert.  (8 sq inch 

flue area x  inches = 8 square inches maximum chimney 

area).

  • Should be lined with a 6 inch (15mm) stainless steel flue liner 

to improve performance and reduce creosote build-up.

 

• 

An equivalent liner must be a listed chimney liner system or 

other approved material.

  • No dilution air is allowed to enter the chimney.

   

1. 

Secure the fireplace damper in the open position.  If this 

cannot be accomplished, it will be necessary to remove 
the damper

 

 

    . Seal damper area of chimney around chimney connector 

with a high temperature sealant or seal insert against the 

face of the fireplace.

   

3. Both  methods  must  be  removable  and  replaceable  for 

cleaning and re-installation.

  • When possible, install an airtight clean-out door to the rear of 

the smoke shelf.

Minimum 1/2” (25mm) Air Space,
Maximum 4” (102mm) Air Space

Airtight Clean-
Out Door

Minimum 5/8” (16mm) 
Fireclay Flue Liner

Non-Water Soluble 
Refractory Mortar

4“ (102mm) Masonry 
or Modular Block Wall 
(Nominal)

12” (305mm) if Rubble 
Stone Wall (Nominal)

Footing (depth and size of footing 
accordance with local building code)

Figure 14.1

A.  Venting Systems

Chimney Connector:

It is also known as flue pipe or stove pipe.  It must be 

6  inches  (152mm)  minimum  diameter  stainless  steel 
connector pipe.

Chimney

:

The  chimney  can  be  new  or  existing,  masonry  or 

prefabricated  and  must  meet  the  following  minimum 

requirements as specified below.

WARNING! Risk of Fire!

Follow  venting  manufacturer’s  clearances  and 
instructions when installing venting system.

B.  Inspections

Existing chimneys should be inspected and cleaned by a 

qualified professional prior to installation.  The chimney 

must not have cracks, loose mortar or other signs of dete

-

rioration and blockage.  Hearth & Home recommends a 

NFI or CSIA certified professional or a technician, under 

the direction of a certified professional, conduct a Level II 

inspection per NFPA 11.

Fire Risk
Inspection of Chimney:

• 

Chimney must be in good condition.

•  Meets minimum standard of NFPA 11
•  Factory-built chimney must be 6 inch 

(15mm) UL10 HT.

WARNING

NOTICE:

  Check  with  your  local  building  authorities 

and/or consult the National Fire Protection Association 

(NFPA 11).  

C.  Larger Chimneys

It  is  recommended  that  chimneys  with  larger  diameters 

than  6  inches  (15mm)  be  relined.    An  oversized  flue 

can  affect  draft  and  impair  performance  and  will  allow 
increased build-up of creosote.

4

Chimney Requirements

Summary of Contents for 5100I-GD-B

Page 1: ...RT Advanced Combustion Technology ACT 438 0380E R Installation and service of this appliance should be performed by qualified personnel Hearth Home Technologies recommends NFI certified professionals...

Page 2: ...ntained The insert must be properly grounded to the frame of the mobile home A complete relining of the chimney system with a 6 diameter listed stainless liner is required Must be equipped with a spar...

Page 3: ...7 Appliance Set Up A Installation Outline 21 B Leveling Bolts 21 C Panel Trim Set 21 22 D Securing Liner to Flue Collar 22 E Adj Zero Clearance Trim Support 23 Section 8 Operating Instructions A Over...

Page 4: ...for the installation or mainte nance of this unit and assumes no responsibility for any consequential damage s NOTE This installation must conform with local codes In the absence of local codes you mu...

Page 5: ...o provide reasonable fire safety the following should be given serious consideration 1 Install at least one smoke detector on each floor of your home to ensure your safety They should be located away...

Page 6: ...eward Outside Termination Cap Figure 6 1 Imbalances of HVAC air handling system Upper level air leaks Recessed lighting Attic hatch opening Duct leaks To minimize the affects of negative air pressure...

Page 7: ...ch W C during a low burn measured 6 inches 152mm above the top of the appliance after one hour of operation at each burn setting NOTE These are guidelines only and may vary somewhat F Inspect Applianc...

Page 8: ...VIEW SIDE VIEW FRONT VIEW A B 39 1 8 994mm 26 3 4 679mm 9 1 8 232mm 22 1 4 565mm 21 1 8 537mm 29 5 8 752mm 10 1 2 267mm 34 3 16 919mm C L 25 5 8 651mm 12 7 8 327mm 17 5 8 448mm 39 1 8 994mm 12 0 305mm...

Page 9: ...al D Floor Protection USA Canada E Calculating Alternate Floor Protection Material Thermal Conductivity k value The k value indicates the amount of heat in BTU s that will flow in 1 hour through 1 squ...

Page 10: ...rt kit can be ordered from your dealer Refer to page 23 Material k per inch thick R per inch thick Minimum thickness required Hearth Home HX3 HX4 0 49 2 06 1 2 in USG Micore 300 0 49 2 06 1 2 in USG D...

Page 11: ...e 11 1 5 Attach the cover to the front of the insert to block room air from entering through the front grille Figure 11 2 A Outside Air Installation Remove 2 screws Remove both spring handles Snap dis...

Page 12: ...lower cord attached to right side of grille Remove button plug Grounding screw Back view of left side of grille Bottom of grille Top of grille 1 Disconnect the appliance from power supply 2 Remove the...

Page 13: ...iner 12 1 4 4 1 2 7 3 4 3 1 16 2 1 2 3 3 4 1 1 4 16 3 4 Drill points Center to Center Slide gasket between halves Offset Adapter Chimney Liner Mounting Bracket Slide gasket between halves Drill holes...

Page 14: ...imum 1 2 25mm Air Space Maximum 4 102mm Air Space Airtight Clean Out Door Minimum 5 8 16mm Fireclay Flue Liner Non Water Soluble Refractory Mortar 4 102mm Masonry or Modular Block Wall Nominal 12 305m...

Page 15: ...sert Listing Follow Manufacturer s Instructions for Maximum Liner Extension Above Chimney Maximum 30 Degrees Offset in Chimney Combustible Floor Masonry Chimney Cont d Figure 15 1 NOTE In Canada this...

Page 16: ...himney top The liner must be securely attached to the insert flue collar and the chimney top The air flow of the factory built zero clearance fireplace system must not be altered The flue liner top su...

Page 17: ...n Curtain Doors The following parts may be removed Fire Risk When lining air cooled factory built chimneys Run chimney liner approved to UL 1777 Type HT requirements 2100 degrees F Re install original...

Page 18: ...ay vary somewhat for individual installations This product was designed for and tested on a 6 inch 152mm chimney 14 to 16 feet 4 27 4 87m high in cludes appliance height measured from the base of the...

Page 19: ...roof within 10 feet 305cm Must be located away from trees or other structures These are safety requirements and are not meant to assure proper flue draft NOTE Chimney performance may vary Trees buildi...

Page 20: ...d 3 Appliance must be grounded with 8 solid copper grounding wire or equivalent and terminated at each end with N E C approved grounding device 4 The factory built fireplace must meet UM 84 HUD requir...

Page 21: ...long handle screw driver Back view of top and side panel assembled Panel bracket Cage nut 1 Attaching Panels to the Insert C Panel Trim Set Installation Kit Includes 2 Side panels left right 1 Panel...

Page 22: ...details for removing the manifold tubes baffle and ceramic blanket NOTE Tabs are shipped from factory in a flat position Bend upwards 90 degrees as show in Figure 22 2 2 pre drilled holes on flue coll...

Page 23: ...ce trim has adhered to tape Do a dry run first without removing paper from tape 6 Place cut edge of trim under top lip and into position on scissors Place side pieces on first and then front piece The...

Page 24: ...re Over firing may ignite creosote or will damage the stove and chimney To prevent over firing your stove DO NOT Use flammable liquids Overload with wood Burn trash or large amounts of scrap lumber Pe...

Page 25: ...ere is one method that works well 1 Place several wads of crushed paper on the firebox floor Heating flue with slightly crumpled newspaper before adding kindling keeps smoke to a minimum 2 Place sever...

Page 26: ...to 15 minutes on High to achieve the following burn rates set the controls as listed below MEDIUM HIGH Close the Primary Air Control to 1 0 inch to 2 1 2 inch 25 to 64mm open Start Up Air is closed ME...

Page 27: ...ave fan off until the burn is well established then if you wish turn the fan on at a low rate 5 The fan is equipped with a rheostat speed control The highest fan speed is obtained by turning the rheos...

Page 28: ...ramic Blanket and Baffle Board are NOT in contact with the back of the firebox Ceramic Blanket is NOT in contact with the back of the firebox and NOT even with the Baf fle Board in the front Ceramic B...

Page 29: ...rst operated this appliance may release an odor for the first several hours This is caused by the curing of the paint and the burning off of any oils remaining from manufacturing Metallic noise Noise...

Page 30: ...ng season the entire system be professionally inspected cleaned and repaired if necessary Close the door tightly The creosote or soot should be removed with a brush specifically designed for the type...

Page 31: ...lean as needed Quadra Fire stoves are equipped with ceramic super heat resistant glass which can only be broken by impact or misuse Do not slam stove door or impact the glass When closing door make su...

Page 32: ...burn dry wood to help prevent cap blockage and creosote build up Keeping the door and glass gasket in good shape will maintain good burn times on a low burn setting Check the glass frame for loose sc...

Page 33: ...ttom left and right sides 7 Replace the glass retainers Be careful not to cross thread the screws 8 Tighten each retainer just a few turns until each is secured Check again for centering of glass in d...

Page 34: ...ove smoothly Locknut Door Cross Section Latch Cam Spacing Washers Square Key Door Handle Spring Handle Frequency As needed By Homeowner Qualified service technician Task See the following instructions...

Page 35: ...nstall side bricks Slide top of brick under clips on side of firebox and push the bottom of the brick until it is flush with the side of the unit NOTE Do not operate unit with any firebrick missing It...

Page 36: ...nifold tubes slide the tube to one side until one end is out of its hole Then while lifting that end of the fiber board baffle pull tube up over the air channel and out of hole at the other end It is...

Page 37: ...section Check for adequate vent height refer to chimney assembly section Open window below the appliance towards the wind Wood condition is too wet too large Use dry seasoned wood refer to wood fuel...

Page 38: ...5100 I ACT WOOD INSERT Page 38 April 21 2010 R 438 0380E 11Reference Materials A Exploded Drawings Figure 38 1 7025 026 5 14 09...

Page 39: ...Gold 832 0620 Y Nickel 250 8330 7 Spring Handle 1 4 Gold 832 0630 Y Nickel 250 8340 Cam Latch 430 1141 Door Glass Assembly 7000 011 Y Door Handle Only 430 1131 Gasket Glass Tape 3 4 3 4 x 5 Ft Dealer...

Page 40: ...438 5440 Glass Nickel Trim Frame 438 5560 Bolt Window Frame Qty 4 812 2350 Glass Window Qty 1 pc Lt Rt Interchangeable 832 2000 Y Nut Keps Lock 8 32 Qty 40 226 0060 40 Y Trim Ring Window Gold 430 2721...

Page 41: ...Component Pack Assembly 436 5130 Logo Quadra Fire Gold 200 3180 Trim Set Only Gold Trim 832 2151 Panel Nickel Trim Ots 51 in W x 34 in H SP 51L NL Component Pack Assembly 436 5130 Logo Quadra Fire Nic...

Page 42: ...5100 I ACT WOOD INSERT Page 42 April 21 2010 R 438 0380E C Warranty Policy...

Page 43: ...Page 43 5100 I ACT WOOD INSERT R 438 0380E April 21 2010...

Page 44: ...ual with party responsible for use and operation Read understand and follow these instructions for safe installation and operation DO NOT DISCARD Date purchased installed Serial Number Location on app...

Reviews: