4300 Wood Stove Series (ACC)
A. Hearth Protection Requirements
FLOOR PROTECTION:
Floor protector must be non-com-
bustible material, extending beneath heater and to the front,
sides and rear as indicated. The fl oor must be non-com-
bustible or otherwise adequately protected from radiant heat
given off by the unit and from sparks and falling embers. A
layer of thin brick or ceramic tile over a combustible fl oor is
not suffi cient.
For US installations,
it is necessary to install a fl oor protector
of a minimum of 3/8 inch (9.5mm) thick metal clad millboard
or equivalent a minimum of 16 inches (406mm) in front of
glass and 8 inches (203mm) to both sides of the fuel loading
door. Open the door and measure 8 inches (203mm) from
the side edge of the opening in the face of the appliance.
*
See exception.
In Canada,
similar fl oor protection must be provided 18
inches (457mm) in front and 8 inches (203mm) from the
sides and rear of the stove. *
See exception.
*EXCEPTION:
Non-combustible fl oor protections must
extend beneath the fl ue pipe when installed with horizontal
venting and extend 2 inches (51mm) beyond each side.
See Figure 12.4.
Figure 12.3
4
Installation
Figure 12.1
Figure 12.2
Millennium Model
USA
USA
CANADA
Corner hearth pad dimensions with
single wall and double wall pipe
Summary of Contents for 4300 Series
Page 40: ...Page 40 7037 135L August 3 2015 ...
Page 41: ...August 3 2015 7037 135L Page 41 ...
Page 42: ...Page 42 7037 135L August 3 2015 ...
Page 43: ...August 3 2015 7037 135L Page 43 ...
Page 45: ...August 3 2015 7037 135L Page 45 ...
Page 46: ...Page 46 7037 135L August 3 2015 ...
Page 47: ...August 3 2015 7037 135L Page 47 ...
Page 48: ...Page 48 7037 135L August 3 2015 ...
Page 49: ...August 3 2015 7037 135L Page 49 ...
Page 50: ...Page 50 7037 135L August 3 2015 4300 Wood Stove Series ACC C Warranty Policy ...
Page 51: ...August 3 2015 7037 135L Page 51 4300 Wood Stove Series ACC ...