background image

SAFETY LISTING

The Quadra-Fire 4300 is safety  listed by OMNI-Test Laboratories, Inc., Beaverton, Oregon, to UL 1482 and
ULC S627.  It is also approved for mobile home installations with outside combustion air in the U.S. (see pages
15 and 16 for further details).  For residential installations in Canada without an outside combustion air kit, a
source of fresh air into the room must be provided.

INSTALLATION MATERIALS NEEDED FOR YOUR SAFETY

CHIMNEY CONNECTOR (also known as flue pipe or stove pipe):  The chimney connector joins the stove to
the chimney (see page 8).  It should be 6” (152mm) minimum diameter 24 MSG black or blued steel, or an
approved air-insulated double wall venting pipe.

THIMBLE:  A manufactured or site-constructed device installed in combustible walls through which the
chimney connector passes to the chimney (see page 11-13).  It is intended to keep the walls from igniting.

CHIMNEY SYSTEMS:
A.  APPROVED MASONRY (see specifications on pages 8-13) with at least 5/8” (16mm) fire clay lining

joined with refractory cement or other listed system suitable for use with wood stoves.

B.  PREFABRICATED 6" (152mm) listed high temperature (UL 103HT or ULC 629M) chimney.  Components

required by manufacturers for installation such as the chimney support base, firestop (as appropriate), attic
insulation shield, insulated tee, etc., are necessary to assure a safe chimney installation.  Use only
components manufactured for the chimney.  Chimney installation should meet NFPA 211 standards.

FIRE SAFETY:  To provide reasonable fire safety, the following should be given serious consideration:
1.

Install at least one smoke detector on each floor of your home to ensure your safety.  They should be
located away from the heating appliance and close to the sleeping areas.  Follow the smoke detector
manufacturer’s placement and installation instructions, and be sure to maintain regularly.

2.

A conveniently located Class A fire extinguisher to contend with small fires resulting from burning embers.

3.

A practiced evacuation plan, consisting of at least two escape routes.

4.

A plan to deal with a chimney fire as follows:
In the event of a chimney fire:
A. Notify fire department
B. Prepare occupants for immediate evacuation.
C. Close all openings into the stove.
D. While awaiting fire department, watch for ignition of adjacent combustibles from overheated stove pipe,

hot embers or sparks from the chimney.

VENTING SYSTEM

The venting system consists of a chimney connector and a chimney.  These get extremely hot during use.
Temperatures inside the chimney may exceed 2000

°

F (1100

°

C) in the event of a creosote fire.  To protect

against the possibility of a house fire, the chimney connector and chimney must be properly installed and
maintained.  An approved thimble must be used when a connection is made through a combustible wall to a
chimney.  A chimney support package must be used when a connection is made through the ceiling to a
prefabricated chimney.  These accessories are absolutely necessary to provide safe clearances to combustible
wall and ceiling material.  Follow venting manufacturer’s clearances when installing venting system.

This stove may be connected to a lined masonry chimney or a listed high temperature prefabricated approved
metal chimney.  Do not connect it to a chimney serving another appliance.  To do so will affect the safe
operation of both appliances.

Page 7

Summary of Contents for 4300 Series

Page 1: ...unit to a chimney flue already serving another appliance 10 Comply with all minimum clearances to combustibles as shown in this manual for this appliance 11 Build fire on brick firebox floor Do not us...

Page 2: ...stallation 17 Ash removal system installation 18 Ash removal system operating and cleaning 19 Operating instructions 20 Burning process 20 Primary and secondary air systems 20 Blower operating instruc...

Page 3: ...4300 SAFETY LABEL found on back of stove Page 3 Model Quadra Fire 4300 Serial No...

Page 4: ...28 3 8 721m m DIMENSIONS Page 4 FIGURE 1b FIGURE 1a LEG MODEL PEDESTAL MODEL...

Page 5: ...DIMENSIONS 10 245mm 2 13 16 71mm 7 33 STEP TOP LEG MODEL 10 254m m 2 13 16 71m m STEP TOP PEDESTAL MODEL Page 5 FIGURE 2b FIGURE 2b...

Page 6: ...m 24 MSG black or blued steel connector pipe with a listed factory built type HT chimney suitable for use with solid fuels or a masonry chimney Note 2 6 152mm diameter double wall insulated connector...

Page 7: ...at least one smoke detector on each floor of your home to ensure your safety They should be located away from the heating appliance and close to the sleeping areas Follow the smoke detector manufactu...

Page 8: ...p of the stove after one hour of operation at each burn setting NOTE These are guidelines only and may vary somewhat for individual installations Your Quadra Fire stove was designed for and tested on...

Page 9: ...the spaces where the chimney passes through floors and or ceiling Figure 5 The chimney must have a fire clay flue liner or equivalent with a minimum thickness of 5 8 16mm and must be installed with r...

Page 10: ...hest point where it passes through the roof and at least 2 610mm higher than the highest part of the roof or structure that is within 10 3048mm of the chimney measured horizontally Figure 7 Remember t...

Page 11: ...imbles must be strictly followed to assure the safety of the system Be sure to maintain the designated clearances to combustible materials A BRICK CHIMNEY THIMBLE ASSEMBLY Construction of the brick th...

Page 12: ...mm long section of prefabricated listed solid pack chimney to use as a thimble Purchase a wall spacer trim collar and wall band that are manufactured to fit the chimney section you purchase The safety...

Page 13: ...eyond the edge of the chimney flue lining Apply high temperature furnace cement to the end of the chimney section and install it over the connector through the wall band and through the wall spacer Ti...

Page 14: ...hrough the ceiling and the roof Figure 12 The other method is to install an exterior chimney that runs up the outside of the residence Figure 13 The components illustrated may not look exactly like th...

Page 15: ...ved grounding device 6 Refer to clearance to combustibles section page 6 for listing to combustibles 7 Seal all wall floor inlets to prevent air or moisture penetration Check periodically to insure th...

Page 16: ...w ash lip with two 20 mounting screws 2 Mount rear air intake cover plate with two mounting screws 3 Install each side cover with two 8 32 screws 4 Floor installation Cut a 3 76mm minimum hole in the...

Page 17: ...ver piece onto mounting brackets using inner two mounting holes 4 Slip washers onto bolts then bolt legs onto mounting brackets 5 Screw leg assembly onto adapter on bottom of stove using eight 20 scre...

Page 18: ...and tighten securely 7 Carefully stand stove up and place in desired location 8 Slip wooden decorative strips onto pedestal edges 9 Open door of stove and check to insure firebricks and kaowool blanke...

Page 19: ...h down through the ash removal system grate into the drawer below If there are large pieces in the ashes you can remove the grate before cleaning the ash into the drawer Be sure to replace the grate b...

Page 20: ...it is very important that the flames be maintained and not allowed to go out This will insure the cleanest possible fire If you are adjusting your stove for a low burn rate you should close down the a...

Page 21: ...a minimum of 15 minutes 2 Regulate burn rate heat output by using the secondary control center under ashcatcher The primary control on the right is mainly for initial start up reloading or high burns...

Page 22: ...ch other to allow adequate air flow between them 7 When ready to reload the stove add more logs Large logs burn slowly holding a fire longer Small logs burn fast and hot giving quick heat 8 Adjust the...

Page 23: ...g a white non removable film on inside of glass Overfiring voids warranty NOTE Replace with ceramic glass only CARE AND CLEANING OF PLATED SURFACES Clean 24 karat gold plated surfaces with warm soapy...

Page 24: ...rame pieces over the fiberglass tape on the edges of the glass Be sure glass is centered in the opening i e same space top and bottom left and right sides 6 Reinstall screws and glass tabs tight enoug...

Page 25: ...wn free from middle baffle support and into the firebox 4 Kaowool blanket can now be removed out the front of the stove or dropped out through the opening to the rear of the stove 5 Reinstall kaowool...

Page 26: ...r this unit is adjusted at the factory and should not require further adjustment When the speed control is turned clockwise it will click on to high speed Turn the speed control clockwise to decrease...

Page 27: ...ld 821 0292 Standard top shield black 831 1571 Extended top shield black 831 1730 Outside air kit pedestal 831 1740 Outside air kit leg 831 1700 Blower 832 1091 Black door 832 1911 Trim door 832 0031...

Page 28: ...e for any alteration to the unit which causes sooting that results in damage to the interior or exterior of the building in which this appliance is installed This warranty is void if the stove has bee...

Reviews: