Atmospheric Oil Mist Detection System
TM4 / AUGUST 2018
EMAIL [email protected] WEBSITE www.oilmist.com 4 East Barnet Road, London, England, EN4 8RW TEL +44 (0)20 7328 3121
Sheet-15
SETTING ALARM LEVELS
For setting alarm levels see Sheet-31 of this manual for this procedure. Begin by setting
all the Sensors at 0.05mg/L. There will always be areas where there is oil mist; for
instance in the purifier room. The alarm level must be set to a higher level than needed
so that the system does not go into alarm when there is no problem.
TEST PROCEDURE
As these Sensors are sensitive to smoke, steam or oil mist, artificial smoke can be
used to test the Sensors. This is the most effective way of proving the Sensors are
working.