MULTIPLEX™
Oil Mist Detection System
Manual
ATMOSPHERIC SENSOR
AM8/JANUARY 2015
Page 1: ...MULTIPLEX Oil Mist Detection System Manual ATMOSPHERIC SENSOR AM8 JANUARY 2015...
Page 2: ......
Page 3: ...Systems have been providing a fast response without false alarms to protect lives and prevent fires since the early eighties Our Engine Oil Mist Detection Systems provide engine condition data to cont...
Page 4: ...mospheric Sensors are used Part2 13 Multi way Junction Box PCB with 12V PSU Q07 Part2 14 Connector Q01H1 Details for QMI MULTIPLEX CMU Junction Box Part2 15 Cable Details for Atmospheric Sensors 6 Pol...
Page 5: ...re a Channel Part3 8 Response to Alarm Part3 9 PART 4 FAULT FINDING Drawing Layout of Transistors and Fuses Part4 2 Fault Directory Part4 3 PART 5 MAINTENANCE Maintenance Procedures Part5 2 Lens Clean...
Page 6: ......
Page 7: ...ric Oil Mist Detection System MULTIPLEX AM8 JANUARY 2015 EMAIL qmi oilmist com WEBSITE www oilmist com 4 East Barnet Road London England EN4 8RW TEL 44 0 20 7328 3121 Introduction Part1 1 PART 1 INTRO...
Page 8: ...alarm Normally de energised with 1 set of change over contacts Fault alarm Normally energised with 1 set of change over contacts OPERATING TEMPERATURE 5 70 C MULTIPLEX DIMENSIONS mm WEIGHT kg Central...
Page 9: ...UCTIO NS To display a function place Magnet Pen FLAT over specified circle Function Circle Channel level reading Pre set alarm level mgm litre Self test programme Detector alarm test Isolate detector...
Page 10: ...MULTIPLEX Atmospheric Oil Mist Detection System AM8 JANUARY 2015 EMAIL qmi oilmist com WEBSITE www oilmist com 4 East Barnet Road London England EN4 8RW TEL 44 0 20 7328 3121 Introduction Part1 4...
Page 11: ...head screws retain the display panel Upon removal of the screws the panel can be swung away from the main enclosure PCB Q0106 Part 1 3 The display panel sub assembly carries the main MULTIPLEX PCB ty...
Page 12: ...400mA anti surge fuse for 12V power to the fans The LED will light when all is well FS3 Q0112 is a 400mA anti surge fuse to protect the Data Logger PCB and also has a Green LED3 light which is lit co...
Page 13: ...khead or deckhead allowing the Sensor to be positioned facing the flow of air in the chamber being monitored The sub assembly is fitted to the Articulated Joint by 4 screws which can be removed if and...
Page 14: ...Atmospheric Oil Mist Detection System AM8 JANUARY 2015 EMAIL qmi oilmist com WEBSITE www oilmist com 4 East Barnet Road London England EN4 8RW TEL 44 0 20 7328 3121 Introduction Part1 8 PHOTOGRAPH OF...
Page 15: ...il Mist Detection System MULTIPLEX AM8 JANUARY 2015 EMAIL qmi oilmist com WEBSITE www oilmist com 4 East Barnet Road London England EN4 8RW TEL 44 0 20 7328 3121 Introduction Part1 9 DRAWING OF ATMOSP...
Page 16: ......
Page 17: ...ric Oil Mist Detection System MULTIPLEX AM8 JANUARY 2015 EMAIL qmi oilmist com WEBSITE www oilmist com 4 East Barnet Road London England EN4 8RW TEL 44 0 20 7328 3121 Installation Part2 1 PART 2 INSTA...
Page 18: ...MULTIPLEX Atmospheric Oil Mist Detection System AM8 JANUARY 2015 EMAIL qmi oilmist com WEBSITE www oilmist com 4 East Barnet Road London England EN4 8RW TEL 44 0 20 7328 3121 Installation Part2 2...
Page 19: ...Atmospheric Oil Mist Detection System MULTIPLEX AM8 JANUARY 2015 EMAIL qmi oilmist com WEBSITE www oilmist com 4 East Barnet Road London England EN4 8RW TEL 44 0 20 7328 3121 Installation Part2 3...
Page 20: ...N OF SENSORS Please follow the guidelines outlined below to get the best results We recommend using a smoke test aerosol or smoke generator to judge the way the air flows over the machinery Normally a...
Page 21: ...f Sensors These factors should be considered together and a smoke generator is a good way to observe air movement and test positioning of the Sensors a Size of room or chamber e g hydraulic pack area...
Page 22: ...r of potential sources of oil mist To make it easier to determine the source of oil mist each piece of machinery or potential oil mist source should have a Sensor installed immediately down stream of...
Page 23: ...rticulated Joint BEST PRACTICE Until the ship is in operation to avoid contamination of the lenses after installation cover Sensors with a plastic bag This will prevent paint or other materials dirtyi...
Page 24: ...ual for this procedure Begin by setting all the Sensors at 0 05mg L There will always be areas where there is oil mist for instance in the purifier room The alarm level must be set to a higher level t...
Page 25: ...4 way female shut slowdown output open or relay 3 10 way female alarm output 4 4 way male mains input 5 16 way female data logger output optional MATING CONNECTORS FOR THE ABOVE Connector Part No 1 3...
Page 26: ...and Cross section n x mm2 1 Monitor to Junction Box 19 x 2 x 0 75mm2 2 Monitor to Alarms or Shutdown optional 4 x 2 x 0 5mm2 3 Monitor to Main Alarm 4 x 2 x 0 5mm2 4 Monitor Power 3 x 1 5mm2 rating Mi...
Page 27: ...to right and numbered 1 to 6 The cable specification is 3 twisted pair of 0 5mm2 or 3 twisted pair of 0 75mm2 where distance is over 100 meters This cable can be sourced from Helkama part number is R...
Page 28: ...by QMI ASSEMBLE INSTRUCTIONS 1 Strip back about 125mm of outer sheathing of cable and separate the wires Then tin the ends of wires and the drain wire screen being used 2 Assemble socket on to wire in...
Page 29: ...4 Sensors are used supply common 25 26 are used when more than 3 or 4 Sensors are used supply 27 is used when only 3 or 4 Sensors are used supply 27 28 is used when more than 4 Sensors are used fan fa...
Page 30: ...MULTIPLEX Atmospheric Oil Mist Detection System AM8 JANUARY 2015 EMAIL qmi oilmist com WEBSITE www oilmist com 4 East Barnet Road London England EN4 8RW TEL 44 0 20 7328 3121 Installation Part2 14...
Page 31: ...Atmospheric Oil Mist Detection System MULTIPLEX AM8 JANUARY 2015 EMAIL qmi oilmist com WEBSITE www oilmist com 4 East Barnet Road London England EN4 8RW TEL 44 0 20 7328 3121 Installation Part2 15...
Page 32: ...MULTIPLEX Atmospheric Oil Mist Detection System AM8 JANUARY 2015 EMAIL qmi oilmist com WEBSITE www oilmist com 4 East Barnet Road London England EN4 8RW TEL 44 0 20 7328 3121 Installation Part2 16...
Page 33: ......
Page 34: ...MULTIPLEX Atmospheric Oil Mist Detection System AM8 JANUARY 2015 EMAIL qmi oilmist com WEBSITE www oilmist com 4 East Barnet Road London England EN4 8RW TEL 44 0 20 7328 3121 Installation Part2 18...
Page 35: ...Atmospheric Oil Mist Detection System MULTIPLEX AM8 JANUARY 2015 EMAIL qmi oilmist com WEBSITE www oilmist com 4 East Barnet Road London England EN4 8RW TEL 44 0 20 7328 3121 Installation Part2 19...
Page 36: ...MULTIPLEX Atmospheric Oil Mist Detection System AM8 JANUARY 2015 EMAIL qmi oilmist com WEBSITE www oilmist com 4 East Barnet Road London England EN4 8RW TEL 44 0 20 7328 3121 Installation Part2 20...
Page 37: ...Installation Part2 21 110 240V POWER SUPPLY WIRING 1 The 110 240VAC power supplies the Control Monitor Unit CMU 2 Below shows the wiring for 110 240 VAC Power Supply 3 The cable used should be of mini...
Page 38: ...MULTIPLEX Atmospheric Oil Mist Detection System AM8 JANUARY 2015 EMAIL qmi oilmist com WEBSITE www oilmist com 4 East Barnet Road London England EN4 8RW TEL 44 0 20 7328 3121 Installation Part2 22...
Page 39: ...Atmospheric Oil Mist Detection System MULTIPLEX AM8 JANUARY 2015 EMAIL qmi oilmist com WEBSITE www oilmist com 4 East Barnet Road London England EN4 8RW TEL 44 0 20 7328 3121 Installation Part2 23...
Page 40: ......
Page 41: ...m types i Main Alarm Relay 10 ii Early Warning Alarm Relay 7 iii Functional Shutdown Alarm iv Fault Alarm Relay 8 4 The cable used should be a minimum 6 cores and can range from a minimum thickness of...
Page 42: ...re transmitted from the Central Monitor Unit CMU via a 4 way Harting Plug 2 The Shutdown operates via Open or Closed Contacts Relay 3 Below shows the wiring for Plant Shutdown Relay 9 4 The cable used...
Page 43: ...OWER EXPLOSION LIMIT LEL 50mg L FULL ALARM LEVEL GREEN FLASHING YELLOW EARLY WARNING RELAY PRESET SENSITIVITY LEVEL SHUT SLOW DOWN RELAY MAXIMUM ALLOWABLE DENSITY BEFORE ALARM 1 30mg L FLASHING RED W...
Page 44: ...rresponding to the displayed mist percentage for each Sensor This is a digitally calculated reading taking into account temperature non linearities of the Sensors and oil deposit build ups within the...
Page 45: ...Atmospheric Oil Mist Detection System MULTIPLEX AM8 JANUARY 2015 EMAIL qmi oilmist com WEBSITE www oilmist com 4 East Barnet Road London England EN4 8RW TEL 44 0 20 7328 3121 Installation Part2 29...
Page 46: ......
Page 47: ...t Detection System MULTIPLEX AM8 JANUARY 2015 EMAIL qmi oilmist com WEBSITE www oilmist com 4 East Barnet Road London England EN4 8RW TEL 44 0 20 7328 3121 Running Procedure Part3 1 PART 3 STARTING UP...
Page 48: ...signals are fed to the micro processor which is located in the CMU The signals are scanned at 500 millisecond intervals and the data is presented as a digital display reading from 0 to 100 of alarm le...
Page 49: ...will activate for 2 5 seconds as the Monitor will check first that the fault is in the system and not a problem with the environment Even when this fault alarm relay is activated the instrument goes...
Page 50: ...tings will illuminate 3 Place the magnetic pen Q0109 flat against the circle marked Check Alarm Settings 4 Place the magnetic pen flat against the Raise Alarm Level circle marked with or the Lower Ala...
Page 51: ...relays with the exception of the functional relay will operate for 10 seconds If the system has an audio alarm system it is recommended that the personnel should be warned of the impending test The t...
Page 52: ...r the CHANNEL number The channel identification digital display will be shown digitally as a milligrams per litre value in mg L of oil mist density Should the alarm level need to be adjusted then foll...
Page 53: ...f off off 02 off on off off 03 on on off off 04 off off on off 05 on off on off 06 off on on off 07 on on on off 08 off off off on 09 on off off on 10 off on off on 11 on on off on 12 off off on on Sw...
Page 54: ...3 2 There are a total of 10 Binary switches 6 To program the switches for a number of Sensors switch to the positions shown in the above table TO ISOLATE OR RESTORE A CHANNEL If a Sensor becomes fault...
Page 55: ...d alongside the digital read out level The functional shutdown relay alarm RL9 will operate if wired into the system At this level RL10 the main alarm will be activated Further action should be taken...
Page 56: ...s uses relay RL8 See table below for the fault conditions as presented on the Monitor faceplate For more information see the Fault Directory in Part 4 Channel Reading Response 1 12 F1 Check and repair...
Page 57: ...ic Oil Mist Detection System MULTIPLEX AM8 JANUARY 2015 EMAIL qmi oilmist com WEBSITE www oilmist com 4 East Barnet Road London England EN4 8RW TEL 44 0 20 7328 3121 Fault Finding Part4 1 PART 4 FAULT...
Page 58: ...MULTIPLEX Atmospheric Oil Mist Detection System AM8 JANUARY 2015 EMAIL qmi oilmist com WEBSITE www oilmist com 4 East Barnet Road London England EN4 8RW TEL 44 0 20 7328 3121 Fault Finding Part4 2...
Page 59: ...nsor F1 denotes cable fault Check for split or damaged cable or incorrect earthing see wiring instructions F1 and all Channel Lights Flash 1 Check Fuse FS1 on the Power Supply Board 2 See Part 4 2 If...
Page 60: ...Junction Box PCB 3 Leaving the mains power disconnected to the Junction Box reset the Monitor 4 If F4 has now gone the cable from the Monitor to the Junction Box is okay 5 Remove the links from termin...
Page 61: ...own Replace FS1 with 1 25A anti surge fuse If fuse keeps blowing then check wiring and Sensor for faults See Part 4 2 TR1 Faulty Replace TR1 with spare in Maintenance kit Q0111 take care not to short...
Page 62: ......
Page 63: ...eric Oil Mist Detection System MULTIPLEX AM8 JANUARY 2015 EMAIL qmi oilmist com WEBSITE www oilmist com 4 East Barnet Road London England EN4 8RW TEL 44 0 20 7328 3121 Maintenance Part5 1 PART 5 MAINT...
Page 64: ...T function The warning indication on the digital display will persist until the fault is corrected or the channel isolated SENSOR CLEANLINESS A large percentage of returns under Warranty are in fact d...
Page 65: ...or 3 Holding the Sensor undo the 4 screws fixing the Sensor body to the Articulated Joint Use the Allen Key tool from the Maintenance Kit 4 Replace with a spare Sensor if available Proceed to item 8 5...
Page 66: ...Maintenance Part5 4 IMPORTANT NOTES 1 The Sensor electronics are factory calibrated and cannot be serviced on site In the event of a fault the Sensor must be sent back to QMI unless it is a faulty fan...
Page 67: ...cuit board will invalidate the guarantee and may stop the sensor working 1 Turn the potentiometer screw fully anti clockwise 15 turns 2 Connect air sensor to Monitor The LED on the front of the air se...
Page 68: ...d Joint Q1010 Cleaning Fluid Clean All 200ml For cleaning Q10 Sensor lenses Q0103 Monitor Security Keys For changing settings on MULTIPLEX Monitor Q01H Pack of 2 Q0109 Magnetic Pen To activate display...
Page 69: ...C SENSORS The only regular operation that can be built into a planned maintenance is to clean the lenses but if the manual test programme is initiate on the Monitor on a say weekly basis The indicatio...
Page 70: ......
Page 71: ...mospheric Oil Mist Detection System MULTIPLEX AM8 JANUARY 2015 EMAIL qmi oilmist com WEBSITE www oilmist com 4 East Barnet Road London England EN4 8RW TEL 44 0 20 7328 3121 Spares Part6 1 PART 6 SPARE...
Page 72: ...Q0106 Switch Mode Power Supply No case for Power Supply Unit for Monitor Q0109 Magnetic Pen To activate displays on Monitor Q0111 TR1 Transistor Power Supply Board of Q01H Monitor Q0112 400mA Anti su...
Page 73: ...us the return address for repaired or serviced equipment 5 The above documents should be faxed and emailed to QMI London Fax 44 0 20 7328 5888 Email qmi oilmist com 6 Despatch returned goods to Attn Q...
Page 74: ...rial Number of Monitor ____ ____ ____ ____ 4 Number of Sensors __________ 5 Serial Number of Sensors A ___ ___ ___ ___ to A ___ ___ ___ ___ 6 Email address ____________________________________________...
Page 75: ......
Page 76: ...Quality Monitoring Instruments Ltd 4 East Barnet Road London EN4 8RW Email qmi oilmist com Tel 44 0 20 7328 3121 Fax 44 0 20 7328 5888 visit our website at www oilmist com v 3 2 6906012015...