QED ADDP Operation Manual Download Page 17

QED Environmental Systems

Page 14

ADDP Manual

The 

and 

3

  HP  compressors  should  have  60  to  80  gallon  tanks.    A 

5

  HP 

compressor  should  have  an  80  gallon  tank  and  the 

7-1/2 

HP  and 

10

  HP 

compressors  should  have  a  120  gallon  tank.    Storage  tanks  and  automatic 

pressure  shut  off  switches  provide  a  buffer  so  the  compressor  motor  can  cool 

between  each  time  the  tank  is  pressurized.

Electrical  wiring  for  the  Compressor

All  electrical  connections  should  be  made  by  a  licensed  electrician  and 

in  accordance  with  the  electrical  code  for  particular  areas.  The  wiring 

should  provide  full  motor  nameplate  voltage  and  current  at  the  motor 

terminals  during  starting.

Wiring  hook-up  must  be  made  so  that  the  compressor  flywheel  turns 

in  the  proper  direction.    There  is  usually  an  arrow  on  the  flywheel  to 

indicate  the  proper  rotation  direction.

Motor  overload  protection

To  prevent  motor  damage,  provide  all  compressor  motors  with  overload 

protection.    Some  motors  are  furnished  with  built-in  thermal  overload 

protection.

To  prevent  motor  damage  due  to  low  voltage  or  undue  load  imposed 

on  the  motor,  larger  motors  should  be  used  in  conjunction  with  starters 

that  include  thermal  overload  units.

To  determine  the  proper  thermal  protection  (thermal  element),  consider 

the  load  to  be  carried,  starting  current,  running  current  and  ambient 

temperature.    Recheck  electric  current  characteristics  against  nameplate 

characteristics  before  connecting  wiring.

NOTE: Fuses are for circuit protection only, and are not to be considered 

motor  protection  devices.    Consult  your  local  power  company  regarding 

proper  fuse  size.

In  compressors  requiring  lubricating  oil,  do  not  use  synthetic  oil.  

Synthetic  oil  adversely  affects  the 

DDP

.    Non-detergent  30  Weight  oil  is 

recommended  for  compressor  lubrication.

An  automatic  drain  should  be  installed  on  the  compressor  holding  tank  to 
periodically  drain  the  water  and  oil  which  collects  in  the  tank

.

Summary of Contents for ADDP

Page 1: ...oad Ann Arbor Michigan 48106 3726 800 624 2026 North America Only 734 995 2547 Tele 734 995 1170 Fax info qedenv com E mail www qedenv com Copyright QED Environmental Systems November 2008 Environment...

Page 2: ...atent Specific Gravity Skimmer SPG 1 239 868 AP is a Registered Trademark of QED Environmental Systems AutoPump is a Registered Trademark of QED Environmental Systems SOS is a Registered Trademark of...

Page 3: ...DDP System with Foot Valve 6 FIGURE 3 ADDP System with Top Loading Cup 7 Chapter 2 Operation 9 Chapter 3 Assembly 10 FIGURE 4 Locking Quick Connect Instructions 11 Chapter 4 Installation 13 Chapter 5...

Page 4: ...id level in a well or tank by sensing the fluid level and removing fluid which rises above the sensor The ADDP system is powered by compressed air and requires no electricity It is capable of flows fr...

Page 5: ...ove ground and pulls fluid from 22 feet or less below ground at sea level Needle valve The DDP has an adjustable needle valve to control its rate of cycling and quick connect fi ings for both power ai...

Page 6: ...his filter has an automatic drain valve which activates when the fluid level rises in the filter bowl See Figure 1 The second air filter for the bubbler sensor system 0 01 micron oil coalescing filter...

Page 7: ...QED Environmental Systems Page 4 ADDP Manual Figure 1 ADDP System...

Page 8: ...e well It supplies air to the DDP when the fluid level rises and shuts the DDP off when the fluid level recedes See Figure 1 System with Foot Valve The pneumatic sensor circuit has an air bubbler conn...

Page 9: ...QED Environmental Systems Page 6 ADDP Manual Figure 2 ADDP System with Foot Valve...

Page 10: ...Revision 6 November 2008 ADDP Manual Page 7 Figure 3 ADDP System with Top Loading Cup Chapter 1 Equipment...

Page 11: ...l quick connect on the top of the pneumatic system The other end of this hose is positioned in the well or tank from which the fluid is being drawn There are two fluid hoses one for intake ribbed and...

Page 12: ...ng safeguards All components are air driven All air hoses have automatic shut off quick connects which prevents injury due to accidental high pressure discharge All quick connects are brass to elimina...

Page 13: ...on the system on a level surface The fluid level should not be more than 22 feet below the DDP STEP 1 LOCKING QUICK CONNECT INSTRUCTIONS Follow the instructions on Figure 4 for properly securing the l...

Page 14: ...Revision 6 November 2008 ADDP Manual Page 11 Figure 4 Locking Quick Connect Instructions Chapter 3 Assembly...

Page 15: ...ct on the top loading cup See Figure 3 STEP 4 DDP to WELL and DISCHARGE POINT Fluid Hoses System with Foot Valve Connect FEMALE quick connect of the fluid intake hose to the MALE DDP quick connect The...

Page 16: ...ilter regulator and then into the pneumatic system where it powers the DDP and controls operation of the system NOTE The information on compressors is for reciprocating piston compressors A centrifuga...

Page 17: ...tion To prevent motor damage provide all compressor motors with overload protection Some motors are furnished with built in thermal overload protection To prevent motor damage due to low voltage or un...

Page 18: ...ssed air If there is too much oil in the compressed air it will reach the control and possibly cause a shut down The compressor should provide between 70 and 200 pounds per square inch psi of air pres...

Page 19: ...he needle valve in the air hose going from the pneumatic circuit to the DDP If the flow rate is low the DDP cycling rate should be fairly low This prevents the DDP from running fast and drawing the fl...

Page 20: ...ter The valves function satisfactorily as long as the air is not very oily Both bowls should be checked for a buildup of emulsified white solid oil and water This build up will clog the valve If the v...

Page 21: ...afely serviced STEP 2 ZINC BOWLS Remove the zinc bowls of the air filters by sliding the black bu on downward and twisting the bowl about 1 10 of a turn The bowl should slide downward from the upper p...

Page 22: ...t and tension must be checked carefully Placement A compressor is a source of sparking so it must be placed out of what is considered a hazardous area by local and national fire and electric codes Mou...

Page 23: ...ceiver and traps Weekly Examine intake filter elements and if dirty remove and clean or replace Check oil level and add if necessary Do not fill over level mark on sight glass Keep compressor clean fo...

Page 24: ...still bubbling Blow into well level sensor hose or fi ing to simulate high fluid level See Figure 2 Close and open needle valve to clear possible blockage Adjust primary regulator so gauge reads betwe...

Page 25: ...ado Street San Leandro California 94577 2640 800 537 1767 North America Only 510 346 0400 Tele 510 346 0414 Fax Ann Arbor Service Center PO Box 3726 6095 Jackson Road Ann Arbor Michigan 48106 3726 800...

Page 26: ...embly 10 automatic drain valve 3 17 D discharge point 8 Double Diaphragm Pump DDP 3 start up 10 16 F float drains 18 maintenance 18 fluid discharge hose black 8 assembly 12 fluid discharge point 12 fl...

Page 27: ...01 Micron oil coalescing filter for bubbler sensor system with auto drain trap 1 Low Pressure regulator 2 Needle valve 1 Air hose socket with 1 4 inch MPT 1 Well level control valve 1 Foot valve or 1...

Reviews: