INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.PEAK DUO L-G8.3 / BFG AND L-G8.3 / BGT – Q CELLS

INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.PEAK DUO L-G8.3 / BFG AND L-G8.3 / BGT– Q CELLS

19

18

DANGER! Risk of fatal injury due to electric shock! 

 

Ä

Be sure to maintain the time intervals as specified 
by the inverter manufacturer between switching off 
the inverter and beginning any further work.

DANGER! Risk of fatal injury due to electric shock! 

 

Ä

Never plug or unplug the cable when under load. 
Modules must not carry any current.

1.

 Switch off the inverter.

OFF

EN

4  ELECTRICAL CONNECTION

4.2 ELECTRICAL INSTALLATION SAFETY

2.

 Switch off the DC circuit breaker.

3.

 Measure shutdown in DC String. 

(no DC current flow).

4.

 Disconnect plugs by the use of appropriate 

and qualified tools of the manufacturer.

5.

 When connecting the modules proceed in reverse 

order.

DANGER! Risk of fatal injury due to electric shock! 

 

Ä

Electrical work may only be performed by qualified 
and skilled personnel (see page 3).

 

Ä

Ensure correct polarity.

 

Ä

Use solar cables for the connection at the junction 
box outlet. 

 

Ä

Only interconnect connectors of the same type 
and manufacturer.

 

Ä

Use minimum No. 12 AWG copper wires insulated 
for a minimum of 90 °C for field connections.

NOTE! Module damage may occur!

 

Ä

Ensure that the cabling is not under mechanical stress 
(Comply with bending radius of ≥ 2.36 in (60 mm)).

 

Ä

Ensure that the cables do not run between module 
and mounting rail or structure (danger of pinch).

 

Ä

Position the wiring on the solar modules that 
additional shading is avoided.

 

Ä

Ensure for a tight connection between the plugs. 
Plugs click together audibly.

click

click

click

click

DANGER! Risk of fatal injury due to electric shock! 

 

Ä

Ensure that all electrical components are in a 
proper, dry, and safe condition.

4  ELECTRICAL CONNECTION

4.3 CONNECTION OF MODULES

 

Ä

Do not connect modules with different orientations 
or angles of inclination in the same string.

SOLAR

Summary of Contents for Q.PEAK DUO L-G8.3 / BFG Q.PEAK DUO L-G8.3 /...

Page 1: ...Valid for North America INSTALLATION AND OPERATION MANUAL Q PEAK DUO L G8 3 BFG and L G8 3 BGT solar modules...

Page 2: ...le operator are responsible for com pliance with all applicable statutory requirements and regulations The following regulations and standards must be upheld at all times during the installation opera...

Page 3: ...plicable documents This installation manual is only valid in combination with the following technical information DOCUMENT TYPE Product data sheet Packaging and transport information MISUSE OR INCORRE...

Page 4: ...th UL 61730 Installation using a mounting structure for solar modules Mounting Structure Requirements Requirements for the mounting structure Conform to the necessary structural requirements Compliant...

Page 5: ...rientation Module Clamp Subconstruction Mounting profile 2 PLANNING 2 3 MOUNTING OPTIONS 2 PLANNING 2 3 MOUNTING OPTIONS TYPE OF INSTALLATION POINT MOUNTING SYSTEM LINEAR MOUNTING SYSTEM INSTALLATION...

Page 6: ...hat the subconstruction does not touch the junction box even under load The clamps or insertion profiles etc do not touch the glass even under load Ensure that the connection cables of the junction bo...

Page 7: ...t when deter mining the maximum number of modules in the string Parallel Connection Modules may be damaged by the occurrence of reverse currents caused by module defects ground leaks or defective insu...

Page 8: ...zontally as shown NOTE Module damage may occur Never step on modules Do not subject modules to any mechanical stress Do not allow any objects to fall onto modules 3 INSTALLATION 3 1 SAFETY AND TRANSPO...

Page 9: ...rcs may result from the separation of a closed circuit These can result in life threatening injuries The danger increases when several modules are connected in series Please be aware of that the entir...

Page 10: ...NGER Risk of fatal injury due to electric shock Electrical work may only be performed by qualified and skilled personnel see page 3 Ensure correct polarity Use solar cables for the connection at the j...

Page 11: ...e U S National Electrical Code addresses these issues in Article 250 Proper grounding is achieved by bonding all exposed non current carrying metal equipment to the appropriately sized equipment groun...

Page 12: ...in plated metal Equipment Grounding Conductor Aluminum Frame Screw Stainless Steel Q CELLS solar modules are known for a long operating life and minimal maintenance effort and expense Dirt and grime a...