INSTALLATION AND OPERATION MANUAL SOLAR MODULES DUO-G5.X – Q CELLS

INSTALLATION AND OPERATION MANUAL SOLAR MODULES DUO-G5.X – Q CELLS

11

Module Selection

For detailed key electrical data, please refer to the product data 
sheet for the respective product. (available at www.q-cells.com). 

 

Ä

For maximum energy yields, mismatches of specified electric 
current (I

MPP

) of more than 5 % should be avoided for all modules 

connected in series.

Safety Factor

During normal operation, a module may generate a greater current 
and / or higher voltage than that determined under standardized test 
conditions. Accordingly, the values of I

SC

 and V

OC

 marked on the 

module should be multiplied by a facot of 1.25 when determining:

• 

the component voltage ratings,

• 

conductor ampacities,

• 

fuse sizes,

• 

size of controls connected to the PV output.

Refer to Section 690-8 of the National Electrical Code for an 
additional multiplying factor of 125 percent (80 percent derating) 
which might be applicable.

 

Ä

Please follow the valid national guidelines for the installation 
of electrical systems (refer to section 690-8 of the NEC for an 
additional multiplying factor of 125 percent [80 percent derating] 
which may be applicable).

Series Connection

Connection of modules in series is only permitted up to the maximum 
system voltage as listed in the applicable data sheet.

 

Ä

Take into account all possible operating situations and all relevant 
technical norms and regulations when designing the system. 
This will ensure that the maximum system voltage, including all 
necessary safety margins, is not exceeded. 

 

Ä

Take the voltage limit of the inverter into account when deter-
mining the maximum number of modules in the string.

Parallel Connection

Modules may be damaged by the occurrence of reverse currents 
(caused by module defects, ground leaks, or defective insulation).

 

Ä

Ensure that the maximum reverse current load capacity indicated 
in the data sheet is met. 

In order to limit reverse currents that may occur, we recommend 
using the following safety options:

1) 

Layout with a limited number of 
parallel connected strings :

Without undertaking further current blocking measures, a maximum 
of two module strings may be operated in parallel on a single 
inverter or MPP tracker.

2) 

Layout with string fuses :

Place fuses for each string of modules at the plus and minus 
ends. Use gPV-fuses according to IEC 60269-6. Observe the 
maximum permitted number of strings as indicated in the specifi-
cations provided by the respective string fuse manufacturer and 
the technical guidelines.

NOTE! 

When installing different product versions, the lowest minimum 
permitted reverse current load capacity applies.  

Inverters

Inverters with or without transformers may be used.

2  PLANNING

2.4 ELECTRICAL LAYOUT

3  INSTALLATION

3.1  SAFETY AND TRANSPORT

 

Ä

Leave modules in their original packaging until 
installation. 

 

Ä

Store the modules securely in cool and dry rooms. 
The packaging is not weatherproof.

 

Ä

Inspect the packaging for damages.

 

Ä

Contact the transport company regarding 
any damage to the packaging and follow their 
instructions.

 

Ä

Follow any instructions on the packaging.

 

Ä

Ensure that all personnel are aware of and adhere 
to accident-prevention and safety regulations.

 

Ä

While working wear clean gloves.

§

GB

§

I

§

D

DANGER! Risk of fatal injury due to electric shock! 

 

Ä

Do not install damaged modules.

 

Ä

Inform your vendor of any damages 
immediately.

WARNING! Fire Risk!

 

Ä

Do not install modules indoors.

 

Ä

Do not install modules on moving objects.

Summary of Contents for Q.PEAK DUO-G5 series

Page 1: ...Valid for North America INSTALLATION AND OPERATION MANUAL DUO G5 X solar module series...

Page 2: ...llowing regulations and standards must be upheld at all times during the installation operation and maintenance of the solar modules Installation and Operation Manual Other applicable documents such a...

Page 3: ...ORIZED MODIFICATION Fig 1 External dimensions in inch mm and components for Q PEAK DUO G5 Q PEAK DUO BLK G5 Q PLUS DUO G5 Q PLUS DUO BFR G5 Q PEAK DUO G5 2 Q PEAK DUO BLK G5 2 Q PLUS DUO G5 2 Q PLUS D...

Page 4: ...ns Operating temperatures from 40 F to 185 F Pull loads and push loads according to chapter 2 3 Test Load in accordance with IEC 61215 and Design Load 1 5 in accor dance with UL 1703 Installation usin...

Page 5: ...3 88 352 5 IP1 CL1 0 9 84 0 250 17 72 21 65 450 550 2400 2400 1600 1600 CL2a with rails CL2b without rails 0 11 81 0 300 CL4 0 11 81 0 300 CL5 short side 0 9 84 0 250 long side 11 81 17 72 300 450 400...

Page 6: ...g the maximum number of modules in the string Parallel Connection Modules may be damaged by the occurrence of reverse currents caused by module defects ground leaks or defective insulation Ensure that...

Page 7: ...e damage may occur Never step on modules Do not subject modules to any mechanical stress Do not allow any objects to fall onto modules 3 INSTALLATION 3 1 SAFETY AND TRANSPORT DANGER Risk of fatal inju...

Page 8: ...result from the separation of a closed circuit These can result in life threatening injuries The danger increases when several modules are connected in series Please be aware of that the entire open c...

Page 9: ...ersonnel see page 3 Ensure correct polarity Use solar cables for the connection at the junction box outlet Use the same inverter compatible plugs Use minimum No 12 AWG copper wires insulated for a min...

Page 10: ...l shock or fire the frame of the module as well as any non current carrying metal parts of the system must be grounded While this section provides some information about grounding the Q CELLS frames a...

Page 11: ...rost 0 6 MAINTENANCE AND CLEANING Free the substructure from any dirt and debris leaves bird nests etc Remove dirt with lukewarm water or alcohol based glass cleaner a broom or a soft cloth Do not use...

Page 12: ...400 Spectrum Center Drive Suite 1400 Irvine CA 92618 USA TEL 1 949 748 59 69 EMAIL inquiry us q cells com WEB www q cells us Subject to change without notice Q CELLS Installation manual solar modules...

Reviews: