B26P
BAT3 CEL
OT P
BAT3 Cell Over
Temp Protection
When the maximum cell temperature is
above protection level, thus terminating
the system.
Automatically returns to normal when the
maximum cell temperature goes below
the limit value.
WEB Display
HMI Display
Description
Measures
B27P
BAT3 COM P
BAT3 Communication
Protection
Power reset of the system is required. If the
symptom persists after reset, replace the
cable connecting the Battery pack and the
INVERTER. After replacement, repair of BMS
or PCS Control Board is necessary.
B28P
BAT3 ADD P
BAT3 Additional
Protection
Power reset of the system is required.
If the symptom still occurs after reset, repair
of BMS or PCS Control Board is necessary.
B31P
BAT4 CHG
OC P
BAT4 Charge Over
Current Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.
B34P
BAT4 CEL
OV P
BAT4 Cell or Rack
Over Voltage Protection
When the maximum cell or rack voltage is
above protection level, thus terminating the
system.
Automatically returns to normal when the
maximum cell or rack voltage goes below
the limit value.
B35P
BAT4 CEL
UV P
BAT4 Cell or Rack
Under Voltage
Protection
When the minimum cell or rack voltage is
below protection level, thus terminating the
system.
Automatically returns to normal when the
minimum cell or rack voltage goes above
the limit value.
B33P
BAT4 CEL V
HOLD P
BAT4 Cell Voltage
Sensing Data Hold
Protection
Power reset of the system is required. If the
symptom still occurs after reset, repair of BMS
or PCS Control Board is necessary.
B32P
BAT4 DCHG
OC P
BAT4 Discharge
Over Current Protection
The product stops the generating process
because a significant protection event has
occurred. Wait until the event message
disappears. After the event message is
removed, it automatically returns to normal.
If it is not removed until the time limit is
reached, it is converted to a significant event.