3.3 System Working Environments Checking
3.3.1 Cleaning
Before installation and system power on, the dust and iron scurf must be removed to keep a clean
environment.
The system cannot be installed in desert area without an enclosure to prevent from sand.
Danger:
Battery module has active DC power at terminal all the time), must be careful to handle
the modules.
3.3.2 Ventilation
3.3.3 Fire-extinguisher System
It must be equipped with fire-extinguisher system for safety purpose.
The fire system needs to be regularly checked to be in normal condition. Refer to the using and
maintenance requirements please follow local fire equipment guidance.
3.3.4 Grounding System
Before the battery installation must make sure the grounding point of the basement is stable and
reliable. If the battery system is installed in an independent equipment cabin (e.g. container),
must make sure the grounding of the
cabin is stable and reliable.
The resistance of the grounding system must
≤100mΩ
3.4 Handling and placement
Warning:
The battery pile’s power terminals are high voltage DC. It must be installed in a restricted
access area;
Warning:
Force-H1 is a high voltage DC system, operated by qualified and authorized personnel
only.
3.3.5 Clearance
Minimum clearance to heat source is more than 2 meters.
Minimum clearance to battery module(rack)
or any object is more than 0.5meters
.
Force-H1 system working temperature range: 0
℃
~
50
℃
; Optimum temperature: 18
℃
~
28
℃
.
There is no mandatory ventilation requirements for battery module, but please avoid of installation
in confined area. The aeration shall avoid of high salinity, humidity or temperature.
Caution:
Force-H1 system is
in-door
design. please avoid frost or direct sunlight. Out of the working
temperature range will cause the battery system over / low temperature alarm or protection
which further lead to the cycle life reduction. According to the environment, the cooling system
or heating system should be installed if it is necessary.