background image

4

DMX signal connection

PX227 must be connected to DMX line in series. This means

that 

DMX IN

 terminals in the device must be provided with the

driving cable, and then from 

DMX OUT

 connector the driving cable

must be provided to other DMX receivers. If PX227 is the last
device in DMX line, 

DMX+

 and 

DMX-

 resistor of 120 Ohm between pins 22 and 

23.

5

Programming

After switching on, the display shows the version of the program. During 

the normal operation of demultiplexer, the display shows only one dot. Press

 

enter

 to go the main menu, the display shows

 ALL

. Press

 prev

 or

 next

 to select

the programming menu

 

(

ALL

Ind

noS

) and press 

enter

 to confirm.

Navigating the menus:

esc

– exits the currently programmed parameter
without saving changes or takes you to a 
higher menu level

prev

– takes to a lower menu lever or reduces the
set values

next

– takes to a higher menu level or increase the set values

enter

– takes to device programming function and confirms the set values

6

120 Ohm

esc

prev

next

enter

Summary of Contents for PX227

Page 1: ...PX227 DMX 0 10V Interface 8ch User manual...

Page 2: ...g of individual parameters 9 8 Response to the loss of DMX signal 10 9 Smoothing function 12 10 Screen blanking 13 11 Mounting 14 12 Menu scheme 15 13 Connection scheme 16 14 Dimensions 17 15 Technica...

Page 3: ...ne independent for each channel DMX address from range 1 512 What is more it is possible to arbitrarily assign multiple channels to a single address 2 Safety conditions PX227 is a device powered by lo...

Page 4: ...otected against contact with water and other liquids 7 All sudden shocks particularly dropping should be avoided 8 The device cannot be turned on in places with humidity exceeding 90 9 The device cann...

Page 5: ...13 GND 14 GND 6 OUT 1 5 OUT 2 4 OUT 3 3 OUT 4 15 OUT 5 16 OUT 6 17 OUT 7 18 OUT 8 7 DC power type 8 DC power type 9 DC power type 10 DC power type 11 DC power type 12 DC power type 19 DMX IN 20 DMX IN...

Page 6: ...the version of the program During the normal operation of demultiplexer the display shows only one dot Press enter to go the main menu the display shows ALL Press prev or next to select the programmi...

Page 7: ...f channel dimming The next step is to confirm selection by pressing enter The address or feature programmed in this way will delete the previous individual settings of the channels 6 1 Setting of DMX...

Page 8: ...els 3 Use next to select Cur this will allow to change the characteristic of channel dimming Lin linear characteristics 0 10V FLu linear characteristics 1 10V S_P switched characteristics on off uSr c...

Page 9: ...n each of the eight output channel with any DMX address It is possible after selecting Adr DMX address can be selected within a range from 1 to 512 It is also possible to set the output characteristic...

Page 10: ...start menu go to the noS and press enter 2 Use the next or prev buttons to select the device behavior for DMX signal loss The following options are available Pr1 Pr2 starting program 1 or 2 on switchi...

Page 11: ...step followed first step select the on option in the End menu In each of the four scenes you can program the values of each of the eight output channels separately in the range from 0 to 255 11 ENTER...

Page 12: ...rt menu go to the Sth settings and press enter 2 Use the next or prev buttons to select the smoothing function and confirm with the enter button The enabled smoothing function can slightly slow down t...

Page 13: ...e screen This is provided by the SCr option By using it the display is switched off approx 60 seconds of inactivity button unused The device still operates without interfering with other parameters Us...

Page 14: ...he device Installation on the mounting rail 1 Set PX227 diagonally to the rail by hooking the two supports on the rear panel of the unit on the upper part of the assembly strip 2 Pull the latch down u...

Page 15: ...TER NEXT ENTER NEXT NEXT ENTER NEXT ENTER NEXT NEXT ENTER ENTER NEXT NEXT ENTER NEXT ENTER NEXT NEXT NEXT NEXT NEXT NEXT NEXT NEXT NEXT ENTER NEXT NEXT NEXT ENTER NEXT NEXT NEXT NEXT NEXT NEXT ENTER N...

Page 16: ...ast DC 1 10V AC 230V Electronic Ballast DC 1 10V AC 230V Electronic Ballast DC 1 10V AC 230V Electronic Ballast DC 1 10V AC 230V to next fluorescent lamp to next fluorescent lamp to next fluorescent l...

Page 17: ...of DMX channels 512 number of output channels 8 voltage on outputs 0 10V 3 output sockets screw terminals current consumption max 250mA outputs load max 30mA channel weight 0 14kg dimensions width 70...

Page 18: ...2018 EN 61000 4 2 2009 EN IEC 61000 6 1 2019 EN 61000 6 3 2007 and meets the essential requirements of the following directives 2011 65 UE DIRECTIVE OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 8...

Reviews: