34
Connecting the Ethernet Cable to the Internet
Use the following steps to complete the connection of the Data Monitoring Module:
1.. Route.the.Ethernet.(CAT5).cable.from.the.Internet-enabled.router,.at.the.gland.plate.
location.on.the.AC.side.(right.side).of.the.inverter,.using.the.proper.conduit.and.hub.
connectors..
Refer to section
4.3 Conduit Entry
for instructions on how to properly
use gland plates.
2.. Plug.the.Ethernet.cable.into.the.Ethernet.port.on.the.Comm.X.PCB.located.at.the.bot-
tom.of.the.AC.module..Refer.to.the.following.figure.
Figure 4-17 Comm X Ethernet Port Location
When the Internet connection is established, go to www.mypvpower.com to register
the inverter and begin using the monitoring tools. Contact PV Powered if additional
information is needed on how to use this online tool.
Advanced Networking and Troubleshooting
All PV Powered commercial inverters come standard with an Ethernet port that is
intended to be connected to the Internet. The PV Powered commercial inverter operates
as an Internet appliance. The inverter communicates with the PV Powered Data Center
using https (port 443). Communications is one way – the inverter only communicates
externally to the PV Powered Data Center. Typically the inverter will post 1Kb to 2Kb of
data via web service call to the data center every 15 minutes. If there is an inverter fault,
the inverter may post data more frequently for a short period of time.
Below is a list of requirements to establish inverter communications with the PV Powered
Data Center. Connectivity must be established before registration on www.mypvpower.
com is attempted.
•. Connect.the.inverter’s.Ethernet.port.to.a.hub.or.router..Ethernet.cables.must.meet.the.
T-568B.wiring.standard.and.must.be.less.than.300.feet.in.length.
•. Provide.DHCP.server.access.to.the.inverter..The.inverter.requires.DHCP.to.establish.
its.IP.address.
Ethernet Port
Summary of Contents for PVP260kW
Page 1: ...97 600100 24 B02 PVP260kW Inverter INSTALLATION OPERATION MANUAL ...
Page 2: ......
Page 4: ...ii ...
Page 6: ...iv ...
Page 8: ...vi ...
Page 48: ...36 ...
Page 62: ...50 ...
Page 86: ...74 ...
Page 87: ...75 Appendix C Mechanical Drawings Figure C 1 Mechanical Drawings APPENDIX C ...
Page 88: ...76 Figure C 2 Mechanical Drawings ...
Page 94: ...82 ...
Page 96: ...84 ...
Page 104: ...92 Notes ...
Page 105: ......
Page 106: ...PO Box 7348 Bend OR 97708 P 541 312 3832 www pvpowered com ...