27
PVP260kW Inverter
Installation and Operation Manual
4.4 Setting and Anchoring
The inverter base is designed to allow a properly rated forklift to lift it from the front or
back. Fork slots are also provided on the left and right sides to enable small adjustments.
!
WARNING
Do not attempt to lift the full weight of the inverter from the left or right sides
only. Attempting to lift from just the left or right sides only will result in an
unstable and unsafe condition.
1.. Lift.the.inverter.with.a.forklift.by.positioning.the.forks.under.the.enclosure.and.
through.the.openings.in.the.bottom.of.the.inverter.
2.. Position.the.inverter.to.the.preferred.location.
Alternate methods of lifting and positioning the inverter may be used at the
discretion of the installer. Such methods may include the use of a crane with a
strap rated for the weight of the inverter.
3.. Secure.the.inverter.to.the.concrete.base.by.setting.the.anchoring.hardware.through.
each.of.the.six.holes.in.the.external.mounting.flange.as.shown.in.sheet.two.of.
Appen-
dix C - Mechanical Drawings
.
The flanged inverter base allows the unit to be anchored after positioning.
4.5 Electrical Connections
Proceed with making the electrical connections of the inverter once it has been properly
secured to the concrete slab. Terminal connections for the inverter are located inside the
unit. When facing the inverter:
•. DC.terminals.are.located.on.the.left.side
•. AC.terminals.are.on.the.right.side
The AC and DC busbars accept standard terminal lug-crimped wires mounted to the
busbar fittings with standard 3/8” mounting hardware.
For the optional fused subcombiners, the wire is inserted directly into the fuse holder
assembly. Accepted cables sizes for each subcombiner lug option are shown in Table D-4
in
Appendix D - Limits, Descriptions, Fault Codes and Torque Values
.
The inverter is a NEMA 4 enclosure. Use only rain-tight or wet-location conduit hubs
and install these hubs as shown in the following figure.
Summary of Contents for PVP260kW
Page 1: ...97 600100 24 B02 PVP260kW Inverter INSTALLATION OPERATION MANUAL ...
Page 2: ......
Page 4: ...ii ...
Page 6: ...iv ...
Page 8: ...vi ...
Page 48: ...36 ...
Page 62: ...50 ...
Page 86: ...74 ...
Page 87: ...75 Appendix C Mechanical Drawings Figure C 1 Mechanical Drawings APPENDIX C ...
Page 88: ...76 Figure C 2 Mechanical Drawings ...
Page 94: ...82 ...
Page 96: ...84 ...
Page 104: ...92 Notes ...
Page 105: ......
Page 106: ...PO Box 7348 Bend OR 97708 P 541 312 3832 www pvpowered com ...