Altec AIR
P8400W Air-dryer User’s Guide
Page 107 of 110
P017585 – Rev. A
(also sets SNMP Trap Community String) “public”)
SNMP Write Community
Alphanumeric
Status Readings (Read-Only)
Outlet Pressure Reading
Numeric (PSI)
Tank Pressure Reading
Numeric (PSI)
System 1 Humidity Reading
Numeric (%)
System 2 Humidity Reading
Numeric (%)
System 1 Duty Cycle Reading
Numeric (%)
System 1 Duty Cycle Reading
Numeric (%)
Flow Reading
Numeric (SCFD)
Cabinet Temperature Reading
Numeric (DEG F)
Compressor 1 Total Run Time Reading
Numeric (Hours)
Compressor 2 Total Run Time Reading
Numeric (Hours)
Compressor 1 Last Run Time Reading
Numeric (Seconds)
Compressor 2 Last Run Time Reading
Numeric (Seconds)
System 1 Status
ON / SHUTDOWN / STANDBY
System 2 Status
ON / SHUTDOWN / STANDBY
Compressor 1 Status
ON / OFF
Compressor 2 Status
ON / OFF
Alarm Readings (Read-Only)
High Flow Alarm
OK / Alarm
High Outlet Pressure Alarm
OK / Alarm
Low Outlet Pressure Alarm
OK / Alarm
High Humidity System 1 Alarm
OK / Alarm
High Humidity System 2 Alarm
OK / Alarm
High Cabinet Temperature Alarm
OK / Alarm
Compressor 1 Last Run Time Alarm
OK / Alarm
Compressor 2 Last Run Time Alarm
OK / Alarm
Maintenance Required System 1Alarm
OK / Alarm
Maintenance Required System 2 Alarm
OK / Alarm
Total Alarm
OK / Alarm
Configuration Settings (Read-Write)
High Flow Alarm Threshold
Numeric (SCFD)
High Outlet Pressure Alarm Threshold
Numeric (PSI)
Low Outlet Pressure Alarm Threshold
Numeric (PSI)
High Humidity Alarm Threshold
Numeric (%)
High Duty Cycle Alarm Threshold
Numeric (%)
Compressor Last Run Time Alarm Threshold
Numeric (Seconds)
Reset Compressor Total Run Time Reading
Numeric (Hours)
Start Up Delay Time
Numeric (Seconds)
Alarm Delay (1 Minute)
ON / OFF
Alarm Traps Sent to SNMP Server
High Flow
High Outlet Pressure
Low Outlet Pressure
High Humidity
High Duty Cycle
High Cabinet Temperature
Compressor Last Run Time
Maintenance Required