PUREAIRO DSC 55S SPARE PARTS
ALL SENTINEL MODELS-PARTS
Part#
Description
S-100
S-101
S-102
S-107
S-108
S-109
S-110
Remote Control
Remote Control Cable,25'
Fiexible Supply Duct,72"
Main Control Board
Display Board
RH/Temperature Sensor
PUREAIRO DSC 55S-PARTS
Part#
Description
S-500
S-501
S-502
S-503
S-504
S-505.
S-506.
S-508
S-509
S-510
S-513
Fan Motor
Complete Fan Assembly
Fan Capacitor
Compressor
Compressor Capacitor
Coil Assembly
Hot Gas Bypass Coil
RH/Temperature Sensor Cable
Display Cable
CAT 5 Prot Internal Cable
Foot,adjustable
PUREAIRO DSC 55S-FILTERS
Part#
Description
S-517
S-518
S-519
MERV-8 Filter
HEPA Filter
Carbon Filter
TROUBLESHOOTING
SYMPTOM
CAUSE
SOLUTION
Verify that there is power to the
outlet and that the plug is
properly installed in outlet
Power Supply
Machine
Won't Run
Clean the filter mesh according
to instructions listed in manual.
Air Filter is Clogged
Low Air Flow
Clear the blockage from inlet or
outlet.
Machine is Not Level
Loud Noise
Check to ensure that wire is
connected at both ends. If no
issues are visible, the sensor
may be faulty.
E1=Humidity Sensor issues
Trouble
Code E:1
The unit is outside the operating
temperature range. Modify the
room conditions so the
temperature is between
33°-105°
F
and operation will
commence. If room conditions
are within temperature range,
replace defective sensor.
Room Temperature Over 105°
F
or Below 33°
F
(Display LO)
Trouble
Code:
HI or LO
Room Temperature Over 105°
F
(Display HI) or Below 33
°F
(Display LO)
The unit is outside the operating
temperature range. Modify the
room conditions so the
temperature is between 33°-105°
F
and operation will commence.
Air Inlet or Outlet is Blocked.
Move the dehumidifier to flat,
firm ground.
Filter Mesh is Blocked
Clean the filter mesh according
to instructions listed in manual.
PureAiro
DSC 55S
Remote Control Package(cable+remote )
10