PureAire Monitoring Systems, Inc.
34
This is the gas concentration at which the CO
2
level must be displaying to activate the
alarm. To change the displayed value, push the joystick to the right to display the CO
2
level alarm setting. The display will indicate a value between 0 ppm and 50,000 ppm.
Pushing the joystick up increases the value and pushing the joystick down decreases the
value.
After entering the alarm setting push the joystick left to enter the setting. The display
will scroll the following:
Push the joystick down to access the next sub menu;
Set Relay 2 Alarm Threshold,
will scroll on the digital display.
This is the gas concentration at which the second CO
2
level must be displaying to
activate the alarm. To change the displayed value, push the joystick to the right to
display the CO
2
level alarm setting. The display will indicate a value between 0 and
50,000 ppm.
Pushing the joystick up increases the value and pushing the joystick down decreases the
value.
After entering the alarm setting push the joystick left to enter the setting. The display
will scroll the following:
Push the joystick left once to return to the
Set Alarm Thresholds menu.
The display
will scroll the following:
5000PPM
..Set Relay 2, CO2, Alarm Threshold…
10,000PPM
..Set Alarm Thresholds..
..Set Relay 1, CO2, Alarm Threshold…
..Set Relay 2, CO2, Alarm Threshold…