Remote Display Alarm Indicator for Oxygen monitor
(Part number 99091)
The Remote Display Alarm Indicator is designed to display remote oxygen
concentration information from PureAire’ oxygen monitors. All PureAire O
2
monitors have a built in 4-20mA output. The remote display alarm easily
connects to the monitor’s input power and mA output connection. An 18
AWG, three conductor, shielded control and instrumentation cable, Belden
8770 or equivalent is recommended for the connection. The maximum
permissible cable length is 250 feet. You can simultaneously connect one
remote display to one Air Check Oxygen monitor and one programmable
logic controller, PLC.