Component Checks 

1.

Check Fan Motor and Power Source

If the fan does not run when the switch is on either in the 

High

 or 

Low 

position, check the

 

voltage supplied to the motor.

1.

If the motor does not turn when the proper voltage is supplied to it, check
to see that the shaft turns freely.  Replace the motor if necessary.

2.

If the correct line voltage is not measured, check back through the wiring to
the power source, including the interlock system.

2.

Check the Electronic Cell

Visual Inspection – Carefully examine the electronic cell and look for the following:

- Bent plates
- Broken ionizing wires
- Dirt Accumulating on the cell plates
- Cracked or broken insulators

3.

Check for Short Circuits

Use an ohmmeter to check resistance through the cell.  Resistance should show an open circuit.

4.

Check Transformer and Voltage Doubler (Electronic Units Only)

This check will locate a faulty component or connection in the power supply of your LAF

M

.

 

CAUTION

!!!  EXPOSURE TO LINE VOLTAGE

 

IN THIS PROCEDURE WARRANTS SPE-CIAL CARE.  BE SURE THE POWER IS TURNED OFF BEFORE CONNECTING OR DIS-
CONNECTING ANY COMPONENT.

1.

Inspect power supply (transformer and doubler) for any physical signs of damage.

2.

Turn the power off and connect voltage meter to the primary side of the high voltage

 

transformer.  Energize the system and check

 

the line voltage.

3.

Turn off the power, disconnect the primary side and reconnect to the secondary side

 

of the transformer.  A poor reading here will

 

probably indicate a faulty transformer.

 

Replacement is in order.

4.

Turn off the power again, disconnect the transformer and connect to the output grid

 

cap connector.  Measure voltage (DC) at about

 

6000V open circuit.  A poor

 

measurement here should be traced back to the doubler in case of bad high voltage wire.

 

If the reading is

 

still poor at the doubler, it should be replaced. 

11 

L A - F M   I N S T A L L A T I O N   M A N U A L   &   U S E R   G U I D E 

Pure n Natural Systems, Inc.  |  purennatural.com  |  1-800-237-9199

Summary of Contents for LA-1000-FM

Page 1: ...ount Media Air Cleaner Distributed by Pure n Natural Systems Inc purennatural com 1 800 237 9199 COMMERCIAL AIR CLEANER INSTALLATION MANUAL AND USER GUIDE L A F M I N S T A L L A T I O N M A N U A L U...

Page 2: ...M General Information 8 Application 8 8 Sizing Maintenance 9 9 9 Washing the Electric Cells and Prefilter Replacing the HEPA Media Pad Service 9 Troubleshooting Guide and Chart Diagnostic Checks Power...

Page 3: ...exhausting of polluted air to the outside is the most common solution to the removal of concentrations of polluted air In doing so however you must also bring supplies of fresh air to take the place...

Page 4: ...ust Grille Mounting System Two speed Blower Switch System Light Piggyback Fuse System Power Supply Module Not used with HEPA Units Blower Motors COMPONENTS OF THE LAFM AND HEPA LAFM 4 Hood Assembly Th...

Page 5: ...LAFM Self Contained Flush Mounted Electronic Air Cleaner removes the smoke dust dirt pollen and other pollutants from the air with an electrostatic process which works this way 1 The internal circula...

Page 6: ...the cell 3 After removing the items in the previous step close and lock the hinged intake panel Preparation for Mounting The LAFM and HEPA LAFM are designed to fit into a T bar drop ceiling Remove as...

Page 7: ...cal authority Reassembly of the Unit 1 With the unit now in place loosen the 1 4 turn screws on the intake grille and allow the hinged portion to drop down 2 Replace the prefilter screen electronic ce...

Page 8: ...de air quality How fast is the level of contamination rising What kind of air speed is anticipated ASHRAE Standard 62 81 recommends several different air change formulas depending on the type of estab...

Page 9: ...ir cleaners and their components are susceptible to damage Take care when working with them to avoid equipment damage Replacing the HEPA Media Pad The HEPA Media pad cannot be cleaned and MUST BE REPL...

Page 10: ...ping sound and arcing should occur if the cell is properly energized b If no arcing is heard check for continuity through the collector cell then check for failure of the cell due to broken wires crac...

Page 11: ...ty component or connection in the power supply of your LAFM CAUTION EXPOSURE TO LINE VOLTAGE IN THIS PROCEDURE WARRANTS SPE CIAL CARE BE SURE THE POWER IS TURNED OFF BEFORE CONNECTING OR DIS CONNECTIN...

Page 12: ...nsure that any malfunction in the electronic air cleaner is quickly and properly repaired Refer first to flow chart below for an outline of the procedure and then refer to the Troubleshooting Guide 12...

Page 13: ...E FROM POWER SUPPLY IN LAFM BROWN OR WHITE WIRE FROM POWER SUPPLY IN LAFM GREEN GROUND WIRE FROM POWER SUPPLY IN LAFM NEUTRAL CONDUCTOR WIRE GREEN GROUND WIRE L A F M I N S T A L L A T I O N M A N U A...

Page 14: ...RLOCK MICRO SWITCH 497576 497567 ON OFF SWITCH 497612 497612 MOTOR BLOWER 497602 497609 FUSE 497547 497547 INDICATOR LAMP 497570 497592 POWER SUPPLY 10079 10179 L A F M I N S T A L L A T I O N M A N U...

Page 15: ...Electronic Filter Cell HEPA Media pad with integrated carbon filter 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Other parts in the LAFM assembly can be obtained by calling our Customer Service Department MODEL LAFM P...

Page 16: ...ny part thereof which has not been operated in accordance with the operating instruc tions herein contained where components or other accessories not compatible with the LakeAir Electronic Air Cleaner...

Reviews: