Troubleshooting 

 

Too Much Humidity 

 

 

 

1.  Humidity controller out of calibration. 

 

2.  Humidifier oversized. 

 

3.  Check humidifier (GX, SX, ES, EC) for proper operation. 

 

Too Little Humidity 

 

 

1.  Humidity controller out of calibration. 

 

2.  Undersized humidifier. 

 

3.  Check humidifier (GX, SX, ES, EC) for proper operation. 

 

4.  Water seals are not primed. 

 

5.  Water seals are blown due to improper supply piping. 

 

Humidifier Discharges Water 

 

  

1.  Faulty drainage: 

 

 

A)  Return line pressure greater than humidifier pressure. 

 

 

B)  Return line flooded. 

 

 

C)  Vertical lift. 

 

 

 

 

Summary of Contents for Fast-Pac

Page 1: ...have to be increased ES EC Water Seal Height if excessive duct static pressure exists 11 28 cm 8 20 cm 17 43 cm 19 48 cm 58 5 thru 102 Total KW 22 thru 33 3 thru 19 5 39 thru 49 5 151 and above 100 t...

Page 2: ...iameter Duct plates are provided to seal the opening The layout should be based on the Location instructions listed above see Fig 3 2 Cut a hole through the AHU or duct wall for the supply connection...

Page 3: ...rt bracket 1 6 Tube mounting bolts 1 per tube 7 Duct plate condensate 1 ITEM NO DESCRIPTION QUANTITY Header drain connection 3 4 NPT Fig 2 4 1 Header mounting bracket welded onto the header 7 Steam in...

Page 4: ...on tubes with the orifices injecting upwards 4 All condensate drain piping is by others Header Support Bracket Mounting Detail Fig 3 Condensate drain connection dashed line is the alternate location s...

Page 5: ...locity of 300 feet per minute is required to avoid saturation and excessive fog travel Controls Fan Interlock Switch PURE Humidifier Co recommends the use of an air flow proving switch or fan interloc...

Page 6: ...Little Humidity 1 Humidity controller out of calibration 2 Undersized humidifier 3 Check humidifier GX SX ES EC for proper operation 4 Water seals are not primed 5 Water seals are blown due to imprope...

Page 7: ...h reservoir outlet size Do not use supply piping with a smaller inside diameter than the reservoir outlet 6 Failure to follow the piping recommendation on this page may result in blown water seals lea...