PumpSpy PS1000 Installation And Operating Instructions Manual Download Page 4

METHOD 2  (Connecting to existing discharge line) - 
See Figure 2

If a separate, dedicated discharge is not desired as in Method 
1, the Backup Pump can be tied into the main pump’s discharge 
pipe by installing a “Y” connector.  Two check valves will be 
required.

    1. This pump has a 1-1/2 in. NPT discharge.  
    2. Cut a 3 ft. section of 1-1/2 in. rigid PVC pipe.  

       Glue 1-1/2 in. pipe to a threaded fitting. 

 

    3. Screw pipe from step 2 into pump discharge. 
    4. Place the pump with the 3 ft. section of PVC pipe on a solid,  
       level surface in the sump pit. Do NOT place the pump on a  
       loose or sandy surface. Small stones or sand may damage  
       the pump resulting in pump failure. 
    5. Attach a check valve (sold separately) to the top of the 
       discharge pipe. A check valve is required for proper 
       operation of system. 
    6. Duplicate the discharge piping arrangement for the  
       primary AC pump if the existing discharge line has to be  

                                                                                                           adjusted to accommodate a second pump.
                                                                                                         7. Glue a 45º elbow to the pipe on the Backup DC Pump.  
                                                                                                            Glue a “Y” adapter to the pipe on the main pump, as  
                                                                                                            shown in illustration for Method 2. 
                                                                                                         8. Glue a short piece of PVC pipe between the 45º  
                                                                                                            elbow and the “Y”.

         THE CHECK VALVES FOR BOTH PUMPS MUST BE INSTALLED BELOW THE “Y” FITTING!

         The remainder of the discharge pipe installation will vary depending on individual circumstances. Using sound plumbing   
         practices, route the discharge pipe to an exterior wall by the shortest distance. 

AFTER PLUMBING IS COMPLETED, FOR BOTH METHODS 1 AND 2

Install float sensors at least 10 in. -12 in. above bottom of sump pit so that the sensors are higher than the normal “on” 

 

level for main pump. 

Make sure power wires and hose clamp ends do not interfere with float switch, pump inlet, or main pump operation. Failure to 
position properly may cause improper operation. Position the float switch so that it will not interfere with any portion of the 

plumbing, wiring, or sump pit. 

BACK-UP PUMP OPERATION:
1. The backup pump will turn on when either the bottom or top float sensor rises.
2. The backup pump will keep running for 10 seconds after the float sensor drops.

3. PumpSpy

 will remotely activate the backup pump during system tests at least 3 times per week.

© PumpSpy Technology, LLC   Questions? 

Call Tech Support: 515.999.6935

WARNING! 

 

PUMPSPY SYSTEM TESTS MAY OCCUR AT ANY TIME.  THE BACKUP PUMP MAY 

CYCLE AT ANY TIME WITHOUT NOTICE. 

Summary of Contents for PS1000

Page 1: ... MAX Flow 12VDC Brushless DC 18 Amps 40 F to 120 F 1 1 2 NPT 3000 GPH System Solid State Pump Controller Power Supply Requirements Electrical Ratings Relative Humidity Storage Temperature Operating Temperature 120VAC 60 Hz 15 AMP 12Amps 120VAC 18 Amps 12VDC 0 to 80 0 to 70 C 0 to 50 C SPECIFICATIONS PumpSpy PS1000 PumpSpy Tech Support 515 999 6935 support PumpSpy com 34000 LEAR INDUSTRIAL PARKWAY ...

Page 2: ...ot been investigated for use in or around swimming pools marine areas recreational water installations decorative fountains or any installation where human contact with the pumped fluid is common WARNING Do not use an extension cord Extension cords could present a safety hazard if not properly sized become damaged or the connection falls into the sump pit Do not attempt to disassemble the PumpSpy ...

Page 3: ...harge 2 Cut a 3 ft section of 1 1 2 in rigid PVC pipe Glue 1 1 2 in pipe to a threaded fitting 3 Screw pipe from step 2 into pump discharge 4 Place the pump with the 3 ft section of PVC pipe on a solid level surface in the sump pit Do NOT place the pump on a loose or sandy surface Small stones or sand may damage the pump resulting in pump failure 5 Attach a check valve sold separately to the top o...

Page 4: ...od 2 8 Glue a short piece of PVC pipe between the 45º elbow and the Y THE CHECKVALVES FOR BOTH PUMPS MUST BE INSTALLED BELOWTHE Y FITTING The remainder of the discharge pipe installation will vary depending on individual circumstances Using sound plumbing practices route the discharge pipe to an exterior wall by the shortest distance AFTER PLUMBING IS COMPLETED FOR BOTH METHODS 1 AND 2 Install flo...

Page 5: ...battery case and place 12Volt battery inside 8 Connect the PumpSpy controller to the battery Red to Black to Replace and lock lid on case 9 Plug the PumpSpy controller into an AC outlet Consult your local codes for GFCI requirements 10 The PumpSpy system will initialize and boot up After booting the POWER and SYSTEM lights should be GREEN The DATA light should be BLINKING RED TESTTHE SYSTEM INTHIS...

Page 6: ...ite click the Login Activate button The website will walk you through the registration process step by step A valid credit card is required to activate the PumpSpy Remote Monitoring Service Your card will not be charged until the 30 day trial period expires There is no long term commitment and you can cancel the service at any time For terms and conditions visit www pumpspy com ACTIVATE THE PUMPSP...

Page 7: ...ds normal value Voltage Low Displayed when battery voltage drops below 11 4 volts 50 discharged Voltage Critical Displayed when battery voltage drops below 10 4 volts 90 discharged Primary Hi Amps Displayed when primary pump current exceeds baseline amp reading by 50 System Error Displayed when alarm for an alert is muted Sig Strgth xx Display of signal strength as read from cellular module press ...

Page 8: ...service cost of shipping will be paid one way This warranty does not cover products purchased from a party that is not an authorized retailer dealer or distributor of PumpSpy products OTHER IMPORTANT TERMS This warranty is not transferable and may not be assigned This warranty shall be governed and construed under the laws of the state of Ohio The warranty period will not be extended by any replac...

Reviews: