4.4.2 30 Minutes Alarm / Pump On Too Long
If the pH control point is active in the chemical feed mode for more than 30 minutes, the main
alarm will turn ON and will shut off both the acid and oxidation pumps.
If the ORP control point is active in the chemical feed mode for more than 30 minutes, the main
alarm will turn ON and will shut off both the acid and oxidation pumps.
4.4.3 Alarm
Silence
If there is an alarm, press the Alarm Silence button on the operator interface panel (See Fig. 2) to
silence the alarm and a red indicator light on the button will be on.
Don’t forget to turn off the
“Alarm Silence” button after the problem is fixed.
4.4.4 Alarm
Reset
Alarm Reset button on the operator interface panel (See Fig. 2) will reset the main alarm to
normal mode, and restore the chemical pumps to normal operation for 30 minutes. If the alarm
condition continues to exist after 30 minutes, the alarm function will start again until the condition
is satisfied or reset.
4.4.5 Power ON Alarm Delay
This feature is activated when the control panel is supplied power (turned ON). A logic mode is
activated at power on so that for the first 30 minutes all alarms are ignored and chemical feed is
allowed to occur by the acid or oxidation pumps.
4.4.6 Water
Fault
If there is a “Water Fault”, the pump and alarm functions are disabled, and a Water Fault light on
the operator interface (See Fig. 2) flashes on / off.