www.pulsar.pl PSDCB09129C
7
4. Operation and use.
4.1 Overload or short circuit of the PSU output (SCP on)
The
AUX1 ÷ AUX9
PSU outputs are protected against a short circuit by glass fuse.
In case of fuse damage, the replacement of the same parameters is required.
In case of overload, the output voltage is automatically shut off, and so is the LED indicator.
The restoration of the voltage takes place immediately after the failure (overload) is over.
4.2 Battery-assisted operation.
In case of a main power outage, the device is immediately switched into a battery-assisted operation.
The PSU is equipped with the discharged battery disconnection system.
During the battery-assisted operation, reducing voltage below 9,5 V at the battery terminals
will cause battery disconnection.
4.3 Maintenance.
Any and all maintenance operations may be performed following the disconnection of the PSU from the
power supply network. The PSU does not require performing any specific maintenance measures, however,
in case of significant dust rate, its interior is recommended to be cleaned with compressed air. In case of fuse
replacement, use a replacement of the same parameters.
WEEE MARK
According to the EU WEE Directive – It is required not to dispose of electric or electronic waste as unsorted
municipal waste and to collect such WEEE separately.
CAUTION!
The power supply module unit is adapted for a sealed lead-acid battery (SLA). After the operation period it must not be
disposed of but recycled according to the applicable law.