www.pulsar.pl 

 

 

 

 

PSDC08128T 

 

 

 

 

 
 

2. Installation. 
 

2.1 Requirements. 

The  stabilized  PSU  is  to  be  mounted  by  a  qualified  installer,  holding  relevant  permits  and  licenses 

(applicable  and  required  for  a  given  country)  for  230V/AC  interference  and  low-voltage  installations.  The  unit 
should  be  mounted  in  confined  spaces,  in  accordance  with  the  2nd  environmental  class,  with  normal  relative 
humidity (RH=90% maximum, without condensation) and temperature from -

10°C to +50°C. The PSU shall work in 

a vertical position that guarantees sufficient convectional air-flow through ventilating holes of the enclosure. 
 

During normal operation the total current consumption of the receivers cannot exceed 

I=8A 

 
 

As  the  PSU  module  is  designed  for  a  continuous  operation  and  is  not  equipped  with  a  power-switch, 

therefore  an  appropriate  overload  protection  shall  be  guaranteed  in  the  power  supply  circuit.  Moreover,  the  user 
shall  be  informed  about  the  method  of  unplugging  (most  frequently  through  separating  and  assigning  an 
appropriate fuse in the fuse-box). The electrical system shall follow valid standards and regulations. 

 
 
2.2  Installation procedure. 

 

1. Before installation, make sure that the voltage in the 230V power-supply circuit is cut off. 

2. Mount the PSU in a selected location and connect the wires. 
3. Connect the power cables (~230VAC) to L-N terminals of the PSU. Connect the ground wire to the terminal 
marked by the earth symbol. Use a three-core cable (with a yellow and green PE protection wire 

) to make the 

connection. Lead the cables to the appropriate terminals of the connection board through the bushing. 

 

The shock protection circuit shall be performed with a particular care, i.e. the yellow 

and green wire coat of the power cable shall stick to one side of the terminal marked with the 

’ earth symbol in the PSU enclosure. Operation of the power supply without a properly 

made and fully operational shock protection circuit is UNACCEPTABLE! It can result in 
device damage or an electric shock. 

 

 
4

. Connect the receivers’ cables to the 

AUX1…AUX8 

connectors

 

on the

 LB8  strips.

 

5. In electrical installations with significant voltage drops in the resistance of the wires that lead to the receivers, the 
voltage value can be corrected with the P1 potentiometer 

(12,0V÷15,0V DC). 

6. Check the PSU operating status indication 
7. Once the installation and operation control have been completed, the enclosure can be locked. 

 

3. Operating status indication. 

The PSU is equipped with LED indication of operation status. The presence of power at the outputs of the 

PSU is indicated by the illumination of green LEDs on the front panel of the device.  

3.1. LED indication  

 

LED1

…LED8

 green diodes indicate power at the outputs: 

LB8- 

AUX1…..AUX8. 

In case of a power loss at the output (fuse activation), an appropriate diode goes out. (L1 for AUX1, L2 for 
AUX2 etc.) 

 
 

4. Operation and use. 
 

4.1 Overload or short circuit at the PSU output. 

The AUX1 ÷ AUX8 PSU outputs of the LB8 strips are protected against a short circuit by glass fuses. If a fuse-

assisted protection has been chosen, replace the fuse (of the same parameters) in case of a failure.  

 

4.2 Activation of the OVP system of the PSU. 

When the OVP system is activated, the output voltage is automatically cut off. Restart is possible after 
disconnecting the PSU from the mains supply 230V for at least 20 seconds. 

 
 

Summary of Contents for PSDC08128T

Page 1: ...PSDC08128T v 1 0 PSDC 12V 8A 8x1A TOPIC Switched mode power supply for CCTV EN Edition 3 from 12 12 2013 Supersedes the 2 from 25 02 2013 ...

Page 2: ...ing status indication 3 1 LED indication 4 Operation and use 4 1 Overload or short circuit at the PSU output 4 2 Activation of the OVP system of the PSU 4 3 Maintenance 1 Technical description 1 1 General description The stabilized PSU PSDC08128T is intended for supplying CCTV devices requiring stabilised voltage of 12V DC The output voltage adjustment range is adjusted via a potentiometer within ...

Page 3: ...ut of the LB8 strip 4 AUX1 AUX8 outputs COM shared terminal Fig 2 The view of the PSU s pcb Table 2 Elements of the PSU see fig 3 Element no Description 1 L N 230 V AC power connectors PE protection connector 2 PSU module 3 VADJ potentiometer output voltage adjustment within the range of 12V 15V DC 4 LED indication of DC power status main module of the PSU 5 LB8 fuse strip with power outputs and L...

Page 4: ...plate DC01 0 7mm colour RAL 9003 Closing Cheese head screw at the front Connectors Power supply 230V AC Φ0 63 2 05 AWG 22 12 AUX outputs Φ0 51 2 05 AWG 24 12 LB8 Φ0 51 2 05 AWG 24 12 Notes The enclosure does not adjoin the assembly surface so that cables can be led Convectional cooling Operation safety tab 5 Protection class PN EN 60950 1 2007 I first Protection grade PN EN 60529 2002 U IP20 Elect...

Page 5: ...nnection board through the bushing The shock protection circuit shall be performed with a particular care i e the yellow and green wire coat of the power cable shall stick to one side of the terminal marked with the earth symbol in the PSU enclosure Operation of the power supply without a properly made and fully operational shock protection circuit is UNACCEPTABLE It can result in device damage or...

Page 6: ...rer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried out at the service centre of the manufacturer exclusively 8 The warranty does not cover the defects of the...

Reviews: