www.pulsar.pl 

 

 

 

 

PSDC04122T 

 

 

 

 

 
 

2. Installation. 
 

2.1 Requirements. 
The  stabilized  PSU  is  to  be  mounted  by  a  qualified  installer,  holding  relevant  permits  and  licenses 

(applicable  and  required  for  a  given  country)  for  230V/AC  interference  and  low-voltage  installations.  The  unit 
should  be  mounted  in  confined  spaces,  in  accordance  with  the  2nd  environmental  class,  with  normal  relative 
humidity (RH=90% maximum, without condensation) and temperature from -10°C to +50°C. The PSU shall wor k in 
a vertical position that guarantees sufficient convectional air-flow through ventilating holes of the enclosure. 
 

During normal operation the total current consumption of the receivers cannot exceed 

I=2A 

 
 

As  the  PSU  module  is  designed  for  a  continuous  operation  and  is  not  equipped  with  a  power-switch, 

therefore  an  appropriate  overload  protection  shall  be  guaranteed  in  the  power  supply  circuit.  Moreover,  the  user 
shall  be  informed  about  the  method  of  unplugging  (most  frequently  through  separating  and  assigning  an 
appropriate fuse in the fuse-box). The electrical system shall follow valid standards and regulations. 

 
 
2.2  Installation procedure. 
 

1. Before installation, make sure that the voltage in the 230V power-supply circuit is cut off. 
2. Mount the PSU in a selected location and connect the wires. 
3. Connect the power cables (~230VAC) to L-N terminals of the PSU. Connect the ground wire to the terminal 
marked by the earth symbol. Use a three-core cable (with a yellow and green PE protection wire 

) to make the 

connection. Lead the cables to the appropriate terminals of the connection board through the bushing. 
 
 
 

 

The shock protection circuit shall be performed with a particular care, i.e. the yellow 

and green wire coat of the power cable shall stick to one side of the terminal marked with the 

’ earth symbol in the PSU enclosure. Operation of the power supply without a properly 

made and fully operational shock protection circuit is UNACCEPTABLE! It can result in 
device damage or an electric shock. 

 

 
4. Connect the receivers’ cables to the AUX1…AUX4 connectors on the LB4  strips. 
5. In electrical installations with significant voltage drops in the resistance of the wires that lead to the receivers, the 
voltage value can be corrected with the P1 potentiometer (12,0V÷15,0V DC). 
6. Check the PSU operating status indication 
7. Once the installation and operation control have been completed, the enclosure can be locked. 

 
3. Operating status indication. 

The PSU is equipped with LED indication of operation status. The presence of power at the outputs of the 

PSU is indicated by the illumination of green LEDs on the front panel of the device.  

3.1. LED indication  

 

LED1…LED4 green diodes indicate power at the outputs: 

LB4- AUX1…..AUX4. 

In case of a power loss at the output (fuse activation), an appropriate diode goes out. (L1 for AUX1, L2 for 
AUX2 etc.) 

 
 
 

 

 

 
 
 
 
 

Summary of Contents for PSDC04122T

Page 1: ...PSDC04122T v 1 0 PSDC 12V 2A 4x0 5A TOPIC Switched mode power supply for CCTV EN Edition 2 from 25 02 2013 Supersedes the 1 from 08 01 2013 edition ...

Page 2: ...ation procedure 3 Operating status indication 3 1 LED indication 4 Operation and use 4 1 Overload or short circuit at the PSU output 4 2Maintenance 1 Technical description 1 1 General description The stabilized PSU PSDC04122T is intended for supplying CCTV devices requiring stabilised voltage of 12V DC The output voltage adjustment range is adjusted via a potentiometer within the range of 12 0V 15...

Page 3: ... of the LB4 strip 4 AUX1 AUX4 outputs COM shared terminal Fig 2 The view of the PSU s pcb Table 2 Elements of the PSU see fig 3 Element no Description 1 L N 230 V AC power connectors PE protection connector 2 PSU module 3 VADJ potentiometer output voltage adjustment within the range of 12 0V 15 0V DC 4 LED indication of DC power status main module of the PSU 5 LB4 fuse strip with power outputs and...

Page 4: ... Enclosure Steel plate DC01 0 7mm colour RAL 9003 Closing Cheese head screw at the front Connectors Power supply 230V AC Φ0 63 2 05 AWG 22 12 AUX outputs Φ0 51 2 05 AWG 24 12 LB4 Φ0 51 2 05 AWG 24 12 Notes The enclosure does not adjoin the assembly surface so that cables can be led Convectional cooling Operation safety tab 5 Protection class PN EN 60950 1 2007 I first Protection grade PN EN 60529 ...

Page 5: ...s 230VAC to L N terminals of the PSU Connect the ground wire to the terminal marked by the earth symbol Use a three core cable with a yellow and green PE protection wire to make the connection Lead the cables to the appropriate terminals of the connection board through the bushing The shock protection circuit shall be performed with a particular care i e the yellow and green wire coat of the power...

Page 6: ...een chosen replace the fuse of the same parameters in case of a failure 4 2 Maintenance Any and all maintenance operations may be performed following the disconnection of the PSU from the power supply network The PSU does not require performing any specific maintenance measures However in case of significant dust level clean its interior with compressed air In case of a fuse exchange use the repla...

Page 7: ...ue to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried out at the service centre of the manufacturer exclusively 8 The warranty does not cover the defects of the equipment resulting from reasons beyond the manufacturer s control mechanical damage improper storage and transport use that violates the operation manual or equipment s intended...

Reviews: