www.pulsar.pl PSCU08348SEP
5
Tab.2 Components of the PSU (see Fig. 3).
Component
[Fig. 3]
Description
Isolation transformer
LP4/SEP rectifying strip
F
MAIN
–
fuse in the power supply circuit (230V AC)
L-N
power supply connector 230V AC,
protective connector PE
Table 2. Components of the PSU.
Fig.3. The view of the PSU.
1.4 Technical parameters:
- Electrical parameters (Table 3)
- Mechanical parameters (Table 4)
- Safety of use (Table 5)
- Operation parameters (Table 6)
Electrical parameters (Table 3)
Supply voltage
230V AC
Current consumption
1,6A@230V AC max.
PSU’s power
240W max.
Output voltage
30
V÷ 35V DC (100% load ÷ 0% load)
Output current
8x1A@30V DC max.
Short-circuit protection SCP
8x T 1A melting fuse (failure requires fuse replacement)
Overload protection OLP
DC 30V: 8 x T 1A circuit
AC 230V: T 6,3A circuit
Surge protection
varistors
Mechanical parameters (Table 4)
Dimensions
W=290, H=250, D+D
1
=72 +8 [+/- 2 mm]
W
1
=295, H
1
=255 [+/- 2 mm]
Mounting
see Fig. 3
Battery housing
5,2kg / 5,4kg
Net/gross weight
Steel plate, DC01 1,0mm color RAL 9003
Enclosure
Cylindrical screw x 2 (at the front)
Terminals
Mains supply:
Φ0,63-2,50 (AWG 22-10)
Outputs
: Φ0,51-2,05 (AWG 24-12)
Notes
The enclosure does not adjoin the mounting surface so that cables can be led.