www.pulsar.pl                                                     PSCU08348SEP                                                                     

 

 

 

       

Safety of use (Table 5)

 

Protection class PN-EN 60950-1:2007 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Insulation electrical strength: 
- between input (network) circuit and the output circuits of the PSU (I/P-O/P) 
- between input circuit and PE protection circuit  (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
  500 V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500V/DC  

 
Operation parameters (Table 6) 

Environmental class 

II 

Operating temperature 

-

10ºC...+40ºC 

Storing temperature 

-

20ºC...+60ºC 

Relative humidity 

20%...90%, no condensation 

Vibrations during operation 

unacceptable 

Surges during operation 

unacceptable 

Direct insolation 

unacceptable 

Vibrations and surges during transport 

According to the PN-83/T-42106 standard 

 

2. Installation. 
 

2.1 Requirements. 

            

The power supply unit should be mounted by a qualified installer, holding relevant permits and licenses 

(applicable and  required  for  a  given  country)  for  230V/AC  and  low-voltage  installations. The  unit  should  be 
mounted  in  confined  spaces,  in  accordance  with  the  2nd environmental  class,  with  normal  relative  humidity 
(RH=90% maximum, no condensation) and temperature range from -

10°C up to +40°C. The  power  supply  should  

operate  in  a  vertical position in order to provide free and  convectional  air  flow  through ventilating holes of the 
enclosure.  

The  power  supply  load  balance  should  be  done  before  installation.  During  normal  operation,  the  total 

current of the receivers should be below I=8x1A@30V DC.   

The  power  supply  is  designed  for  a  continuous  operation  and  is  not  equipped  with  a  power-switch. 

Therefore, an appropriate overload protection in the power supply circuit should be provided. Moreover, the user should 
be informed how to disconnect the power supply unit from the mains supply (usually by assigning an appropriate fuse in 
the fuse box). The electrical system shall be made in accordance with applicable standards and regulations.  
 
 

2.2 Installation procedure. 

 

1. Before installation, make sure that the voltage in the 230V power-supply circuit is cut off. 

2. Mount the PSU in a selected location and lead the connection cables.  
3. Connect the power cables (230V AC) to the L-N terminals of the PSU. Connect the ground wire to the terminal 
marked with the PE symbol (power supply module connector). Use a three-core cable (with a yellow and green PE 
protection wire) to make the connection. The power cables should be connected to the appropriate terminals on the 
connection board through the bushing.  

 

The shock protection circuit shall be done with a particular care: the yellow and green wire coat 
of    the    power    cable    should  be  connected  to    the    terminal    marked    with    the  PE    symbol. 
Operation of the PSU without the properly made and fully operational shock protection circuit is 
UNACCEPTABLE! It can cause damage to the equipment or an electric shock.

 

 

 

 

Summary of Contents for PSCU 08348SEP

Page 1: ...PSCU 08348SEP v 1 0 PSCU 34VDC 8A 8x1A SEP Power supply for 8 HD cameras 8A for transmission lines EN Edition 1 from 31 05 2017 Supersedes the edition...

Page 2: ...lated outputs 8 outputs independently protected by 1A fuses LED optical indication Protections Short circuit protection SCP overload protection OLP transformer overheat protection OHP surge protection...

Page 3: ...neral description The PSCU08348SEP power supply is dedicated to solve the problem of long sections of cables voltage drops The PSU supplies constant voltage in the range 30 35V DC and current efficien...

Page 4: ...e power supply Table 1 Fig 2 Table 1 Components of the LP4 SEP strip see Fig 2 Component no Description AC1 AC4 AC power supply input from the transformer F1 F4 fuses in the AUX1 AUX4 output circuits...

Page 5: ...ent consumption 1 6A 230V AC max PSU s power 240W max Output voltage 30V 35V DC 100 load 0 load Output current 8x1A 30V DC max Short circuit protection SCP 8x T 1A melting fuse failure requires fuse r...

Page 6: ...air flow through ventilating holes of the enclosure The power supply load balance should be done before installation During normal operation the total current of the receivers should be below I 8x1A 3...

Page 7: ...TP5e twisted pair cable 2 pcs 0 4mm2 21AWG 200 m 120 m UTP5e twisted pair cable 3 pcs 0 6mm2 19AWG 300 m 180 m Stranded cable 0 25mm2 23AWG 100 m 75m Stranded cable 0 5mm2 20AWG 250 m 150m Stranded ca...

Page 8: ...required not to dispose of electric or electronic waste as unsorted municipal waste and to collect such WEEE separately Pulsar Siedlec 150 32 744 apczyca Poland Phone 48 14 610 19 40 Fax 48 14 610 19...

Reviews: