Pulsar PSBS 5012D Manual Download Page 8

www.pulsar.pl                                                       

PSBS5012D                                                                

BLUE POWER

     

 

AC OK: 

 

on – The PSU supplied with 230V AC voltage 

 

 

off – no 230V AC mains supply  

DC OK: 

 

on – DC voltage at the AUX output  

 

off - no DC voltage at the AUX output 

BAT OK: 

 

on – battery voltage  U

BAT

 > 11,5V 

 

off – battery voltage  U

BAT

 < 11,5V 

 

3.  Connect  the  power  cables  (230V  AC)  to  the  L-N  terminals  of  the  PSU.  Connect  the  ground  wire  to  the 

terminal  marked  with  the  PE  symbol  (power  supply  module  connector).  Use  a  three-core  cable  (with  a 
yellow  and  green  PE  protection  wire)  to make  the  connection.  The  power  cables  should  be  connected  to 
the appropriate terminals on the connection board through the bushing. 

 

The shock protection circuit shall be done with a particular care: the yellow and green 
wire coat of  the  power  cable  should be connected to  the  terminal  marked  with  
the PE  symbol. Operation of the PSU without the properly made and fully operational 

shock protection circuit is UNACCEPTABLE! It can cause damage  to  the equipment  or 
an electric shock

  

 

4.  Connect the receiver cables to the AUX terminals at the power supply board. 
5.  If needed, connect the device cables to the technical outputs: 

- EPS; technical output indicating AC power failure 
- PSU; technical output indicating PSU failure. 

- LoB; technical output indicating low battery voltage 
- Optional installation of the MPSBS relay module changing technical outputs of the OC type to relay type 

(page 9, section. 3.3) 
6.  Use  the  I

BAT

  jumper  to  set  the  maximum  battery  charging  current,  taking  into  account  the  battery 

parameters. 

7.  Use  the  P

BAT

  jumper  to  set  to  turn  on/off  deep  discharge  battery  protection  U<10V  (+/-5%). 

Deep 

discharge battery protection is ON when the P

BAT 

jumper is OFF.

 

8.  Mount the battery in the battery compartment of the enclosure (Fig. 3). Connect the batteries with the PSU 

paying special attention to the correct polarity.  

9.  Switch on the 230V AC supply. The corresponding LEDs on the power supply PCB should be ON: red AC 

and green AUX. The yellow LB LED should light up while charging. 

10.  Check  the  output  voltage  (the  power  supply  voltage  without  load  should  be  13,6

V ÷ 13,9V, 11V ÷ 13,8V 

while battery charging). If the voltage requires adjustment, use the V

ADJ

, potentiometer while monitoring the 

voltage at the AUX output of the power supply. 

11.  Check the current consumption of the receivers, taking into account the battery charging current, so as not 

to exceed the total current efficiency of the PSU (section 1.1). 

12.  Close the cover after installing and checking the operation of the power supply. 

 
 

3. 

Power supply operation indication

 

3.1 Optical indication.  

 

The PSU is fitted with 3 LED lights at the front panel

:

 

 

 

 

 

 
Additionally, the PSU is fitted with 3 LED lights indicating the operating status: AC, LB and AUX at the PCB 

of the PSU: 

 

AC-  red  LED

:  is  permanently  illuminated  during  normal  operation  (AC  power  ON).  No  AC  power  is 

indicated by turning off the LED. 

 

LB- yellow LED

: indicates battery charging. The light intensity depends on the charging current. 

 

AUX

green LED:

 indicates DC power status at the PSU output. During normal operation, it is permanently 

illuminated. In case of short-circuit or output overload the LED is off.

 

 
 
 
 
 
 
 

Summary of Contents for PSBS 5012D

Page 1: ...PSBS 5012D v 1 1 PSBS 13 8V 5A 40Ah OC Buffer switch mode power supply unit with technical outputs EN Edition 7 from 03 11 2016 Supercedes edition 6 from 01 06 2016...

Page 2: ...iption 1 1 General description 1 2 Block diagram 1 3 Description of components and connectors 1 4 Technical parameters 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Power supply operati...

Page 3: ...MPSBS 40Ah 5 Buffer power supply PSBS 13 8V 12V 5A MPSBS 40Ah PSBS 5012D RN500 13 8V 12V MPSBS 40Ah 6 Buffer power supply PSBS 13 8V 2x12V 2x2 5A 40Ah PSBS 5012D 2xRN250 13 8V 12V 40Ah 7 Buffer power...

Page 4: ...n the battery circuit F6 3A 250V Terminals AC AC power input EPS technical output of AC power failure indication hi Z state AC power failure 0V state AC power O K PSU technical output of PSU failure i...

Page 5: ...use Table 5 Operation parameters Table 6 Table 3 Electrical parameters PSU type A EPS External Power Source Mains supply 230V AC 50Hz 15 10 Current consumption 0 57A 230V AC PSU s power 76W Efficiency...

Page 6: ...f green permanently illuminated failure off Technical outputs EPS output indicating AC power failure PSU output indicating no DC power PSU failure LoB output indicating low battery voltage OC type 50m...

Page 7: ...lass with normal relative humidity RH 90 maximum no condensation and temperature range from 10 C up to 40 C The power supply should operate in a vertical position in order to provide free and convecti...

Page 8: ...t taking into account the battery parameters 7 Use the PBAT jumper to set to turn on off deep discharge battery protection U 10V 5 Deep discharge battery protection is ON when the PBAT jumper is OFF 8...

Page 9: ...hort circuit at the output Output overload DC DC voltage converter failure Under voltage protection activation LoB output indicating low battery voltage The output indicates low battery voltage Under...

Page 10: ...ltage at the battery terminals drops below 10V 0 5V during battery assisted operation the batteries will be disconnected The battery protection is on when the PBAT jumper is off Caution It is not reco...

Reviews: