Pulsar PSBS 5012D Manual Download Page 2

www.pulsar.pl                                                       

PSBS5012D                                                                

BLUE POWER

     

 

PSU features: 

 

 

uninterruptible power supply DC 13,8V/5A  

 

battery housing: 40Ah/12V 

 

supply voltage AC 230V  

 

high efficiency 76% 

 

low voltage ripple 

 

battery charging and maintenance control 

 

deep discharge battery protection (UVP)  

 

battery charging current 0,5A/1A/2A/3A, jumper 
selectable  

 

START button to start the battery  

 

battery output protection against short-circuit and 
reverse connection  

 

LED indication  

 

EPS technical output of 230V power failure  
– OC type 

 

PSU technical output indicating PSU failure 

– OC type 

 

LoB technical output indicating low battery voltage 

 

– OC type  

 

Optional installation of the MPSBS relay module  
changing technical outputs of the OC type to relay 
type  

 

adjustable times of 230V AC failure indication 

 

Protection type: 

 

SCP short-circuit protection 

 

Overheat protection OHP 

 

surge protection  

 

Tamper protection: enclosure opening and 

detachment from the wall 

 

overload protection OLP 

 

warranty - 5 years from the production date 

 
TABLE OF CONTENTS: 
1. Technical description. 

1.1 General description 
1.2 Block diagram 
1.3 Description of components and connectors 
1.4 Technical parameters 

2. Installation. 

2.1 Requirements 
2.2 Installation procedure 

3. Power supply operation indication. 

3.1 Optical indication of operation 
3.2 Technical outputs 
3.3 Relay technical outputs 

4. Service and operation 

4.1 Overload or short-circuit the power supply output (SCP activation) 
4.2  Running the PSU from the battery. 
4.3  Deep discharge battery protection UVP. 
4.4  Maintenance 
 

 

 
1. Technical description. 
 

1.1 General description. 

A  buffer  PSU  is  designed  for  uninterrupted  supply  of  devices  requiring  stabilized  voltage  of 

12V  DC  (+/-

15%).

 The PSU supplies voltage of 

U=13,8V DC 

and total current capacity of

 

1. Output current 5A + 0,5A battery charging 

 

 

 

2. Output current 4,5A + 1A battery charging 

 

 

 

3. Output current 3,5A + 2A battery charging 

 

 

 

4. Output current 2,5A + 3A battery charging 

 

Total c battery is max. 5,5A 

 

In  case  of  mains  power  loss,  the  unit  will  instantly  switch  to  battery  operation.  The  PSU  is  enclosed  in  a 

metal  casing  (color  RAL  9003)  with  battery  housing  for  40Ah/12V  batteries.  The  enclosure  is  fitted  with  a  micro 
switch indicating door opening (front cover) and the detachment from the wall. 

 
 
 
 
 
 
 

Summary of Contents for PSBS 5012D

Page 1: ...PSBS 5012D v 1 1 PSBS 13 8V 5A 40Ah OC Buffer switch mode power supply unit with technical outputs EN Edition 7 from 03 11 2016 Supercedes edition 6 from 01 06 2016...

Page 2: ...iption 1 1 General description 1 2 Block diagram 1 3 Description of components and connectors 1 4 Technical parameters 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Power supply operati...

Page 3: ...MPSBS 40Ah 5 Buffer power supply PSBS 13 8V 12V 5A MPSBS 40Ah PSBS 5012D RN500 13 8V 12V MPSBS 40Ah 6 Buffer power supply PSBS 13 8V 2x12V 2x2 5A 40Ah PSBS 5012D 2xRN250 13 8V 12V 40Ah 7 Buffer power...

Page 4: ...n the battery circuit F6 3A 250V Terminals AC AC power input EPS technical output of AC power failure indication hi Z state AC power failure 0V state AC power O K PSU technical output of PSU failure i...

Page 5: ...use Table 5 Operation parameters Table 6 Table 3 Electrical parameters PSU type A EPS External Power Source Mains supply 230V AC 50Hz 15 10 Current consumption 0 57A 230V AC PSU s power 76W Efficiency...

Page 6: ...f green permanently illuminated failure off Technical outputs EPS output indicating AC power failure PSU output indicating no DC power PSU failure LoB output indicating low battery voltage OC type 50m...

Page 7: ...lass with normal relative humidity RH 90 maximum no condensation and temperature range from 10 C up to 40 C The power supply should operate in a vertical position in order to provide free and convecti...

Page 8: ...t taking into account the battery parameters 7 Use the PBAT jumper to set to turn on off deep discharge battery protection U 10V 5 Deep discharge battery protection is ON when the PBAT jumper is OFF 8...

Page 9: ...hort circuit at the output Output overload DC DC voltage converter failure Under voltage protection activation LoB output indicating low battery voltage The output indicates low battery voltage Under...

Page 10: ...ltage at the battery terminals drops below 10V 0 5V during battery assisted operation the batteries will be disconnected The battery protection is on when the PBAT jumper is off Caution It is not reco...