4. Service and operation. 

 
4.1  Overload or short-circuit of the power supply output (SCP activation). 

            The AUX output of the PSU is protected against short-circuit by

 

PTC polymer fuse. If the power supply load 

current exceeds Imax. (110% ÷ 150% @ 25°C of the PSU power), automatic disconnection of the output voltage, 
indicated  by  switching  off  the  green  LED,  takes  place.  To  restore  the  voltage  at  the  output,  disconnect  the  load 
from the power supply output for approximately 1 minute. 
 

In case of a short-circuit at the AUX, BAT output or reverse battery connection, the F

BAT

 fuse in the battery 

circuit becomes permanently damaged. The voltage restoration at the BAT output requires fuse replacement. 

 

4.2  Running the PSU from the battery. 

 

The power supply is equipped with the button on the PCB allowing to run the PSU from the battery, when 

needed. To do that, press and hold the 

START

 button on the unit board for 1 second. 

 

4.3  Deep discharge battery protection UVP. 

The  power  supply  is  equipped  with  deep  discharge  battery  protection  (UVP).  If  the  voltage  at  the  battery 

terminals drops below 1

0V±0.5V during battery-assisted operation, the batteries will be disconnected. 

The battery 

protection is on when the P

BAT 

jumper is off.

 

 

Caution.  

It is not recommended to disable  UVP since deep  discharge of the batteries reduces their ability to 
store energy, their capacity and lifetime. 

 
 

4.4  Maintenance. 

All  maintenance  procedures  can  be  performed  after  disconnecting  the  power  supply  from  the  power 

network.  The  PSU  does  not  require  any  specific  maintenance;  however,  its  interior  should  be  cleaned  with 
compressed air if used in dusty conditions. In case of fuse replacement, use only compatible replacement parts. 
 

 

 

 

WEEE LABEL 

 

Waste electrical and electronic equipment must not be disposed of with normal household waste. 

According to the European Union WEEE Directive, waste electrical and electronic equipment 

should be disposed of separately from normal household waste. 

 

 

CAUTION!

 

The power supply unit is adapted for cooperation with the sealed lead-acid batteries (SLA). After the operation period they must 

not be thrown but recycled according to the applicable law. 

 

 
 
 
 
 
 
 

 

 

Pulsar sp. j.  

Siedlec 150,  32-744 Łapczyca, Poland 

Tel.  (+48) 14-610-19-40, Fax. (+48) 14-610-19-50 

E-mail: 

[email protected]

[email protected]

 

http:// 

www.pulsar.pl

www.zasilacze.pl

 

Summary of Contents for PSBS 5012D

Page 1: ...PSBS 5012D v 1 1 PSBS 13 8V 5A 40Ah OC Buffer switch mode power supply unit with technical outputs EN Edition 7 from 03 11 2016 Supercedes edition 6 from 01 06 2016...

Page 2: ...iption 1 1 General description 1 2 Block diagram 1 3 Description of components and connectors 1 4 Technical parameters 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Power supply operati...

Page 3: ...MPSBS 40Ah 5 Buffer power supply PSBS 13 8V 12V 5A MPSBS 40Ah PSBS 5012D RN500 13 8V 12V MPSBS 40Ah 6 Buffer power supply PSBS 13 8V 2x12V 2x2 5A 40Ah PSBS 5012D 2xRN250 13 8V 12V 40Ah 7 Buffer power...

Page 4: ...n the battery circuit F6 3A 250V Terminals AC AC power input EPS technical output of AC power failure indication hi Z state AC power failure 0V state AC power O K PSU technical output of PSU failure i...

Page 5: ...use Table 5 Operation parameters Table 6 Table 3 Electrical parameters PSU type A EPS External Power Source Mains supply 230V AC 50Hz 15 10 Current consumption 0 57A 230V AC PSU s power 76W Efficiency...

Page 6: ...f green permanently illuminated failure off Technical outputs EPS output indicating AC power failure PSU output indicating no DC power PSU failure LoB output indicating low battery voltage OC type 50m...

Page 7: ...lass with normal relative humidity RH 90 maximum no condensation and temperature range from 10 C up to 40 C The power supply should operate in a vertical position in order to provide free and convecti...

Page 8: ...t taking into account the battery parameters 7 Use the PBAT jumper to set to turn on off deep discharge battery protection U 10V 5 Deep discharge battery protection is ON when the PBAT jumper is OFF 8...

Page 9: ...hort circuit at the output Output overload DC DC voltage converter failure Under voltage protection activation LoB output indicating low battery voltage The output indicates low battery voltage Under...

Page 10: ...ltage at the battery terminals drops below 10V 0 5V during battery assisted operation the batteries will be disconnected The battery protection is on when the PBAT jumper is off Caution It is not reco...

Reviews: