background image

www.pulsar.pl   

 

 

 

PSBEN5012D   

 

 

 

    

BLACK POWER

 

 
 

21 

5.3.5 

Setting the parity of the transmission 

“trP” 

applies to cooperation with PowerSecurity. 

 

All  the  parameters  responsible  for  communication  between  the  PSU  and  the  computer,  namely  the 

address, parity and speed should have the same settings for both the PSU and the PowerSecurity program. 

  
The  PSU  has  preset  transmission  parameters  of  115200  baud  8E1.  However,  if  it  is  connected  to  the 

network with differently defined parameters, make the appropriate changes to its configuration. 
 
 
 
 

simultaneously press the „<,>” rightmost and leftmost buttons 

 
 

the „tSt” parameter will be displayed 

 
 

use the „<” or „>” buttons to display the „trP” parameter 

 
 
 
 

 

 
- press 

„OK” 

 
- the information about the parity of the transmission will be displayed  
on the panel 
 

use the „<” or „>” buttons in order to set the required communication mode, 

- 8N2 
- 8E1

 (factory setting) 

- 8O1

 

 
 
 
 
- confirm by pressing 

„OK” 

 
 
 

in order to return to the main menu, simultaneously press the „<,>” rightmost  

and leftmost buttons 
 
 
 

5.4  Acoustic indication. 

Emergency  situations  are  acoustically  indicated.  The  frequency  and  the  number  of  signals  depend  on  an 

event type (see chapter. 5.2.5). The acoustic indication is off after removing an appropriate jumper (fig. 2, [5]). 

Table 11. Acoustic indication

 

No.

 

Description

 

Event

 

1 signal per 10s, battery-assisted 
operation 

No 230 V supply 

1 signal per 10s, mains operation 

Battery fault, undercharged battery 

2 signals per 10s, battery-assisted 
operation 

Low level of battery charge 

Fast signals, battery-assisted operation 

The PSU will be disconnected due to the battery discharge 

Continuous indication 

PSU failure [see chapter. 5.2.5] 

1 signal 

Breaking the battery test 

2 signals 

Activation of the battery test 

 

Summary of Contents for PSBEN 5012D

Page 1: ...PSBEN 5012D v 1 1 PSBEN 13 8V 5A 40Ah EN Buffer switch mode power supply unit Grade 3 EN Edition 9 from 31 01 2019 Supercedes edition 8 from 31 01 2019 LED Version...

Page 2: ...2 LED Display Dimmer dIS 19 5 3 3 Setting the communication address Adr applies to cooperation with PowerSecurity 19 5 3 4 Setting the transmission speed trS applies to cooperation with PowerSecurity...

Page 3: ...ww pulsar pl PSBEN5012D BLACK POWER 3 8 TECHNICAL PARAMETERS 30 TABLE 13 ELECTRICAL PARAMETERS 30 TABLE 14 MECHANICAL PARAMETERS 31 TABLE 15 SAFETY OF USE 31 9 TECHNICAL INSPECTIONS AND MAINTENANCE 32...

Page 4: ...charge protection battery output protection against short circuit and reverse polarity connection jumper selectable battery charging current 0 6 A 1 5 A 2 2 A 3 A remote battery test additional module...

Page 5: ...ES YES No battery charge YES YES Low output voltage YES YES High output voltage YES YES PSU failure YES YES Surge protection YES YES Short circuit protection YES YES YES YES Overload protection YES YE...

Page 6: ...tandard Output current 0 66 A 3 A battery charge General use if the PSU is not mounted in an installation complaint with the EN 50131 standard the acceptable current efficiency amounts to 1 Output cur...

Page 7: ...ACK POWER 7 3 2 Block diagram The PSU is manufactured based on a high duty system of DC DC converter The microprocessor system is responsible for full diagnostics of the PSU and battery parameters Fig...

Page 8: ...utton disconnection of the PSU during battery assisted operation pin activation of the acoustic indication indication on indication off Caption jumper on jumper off VADJ potentiometer DC voltage adjus...

Page 9: ...nt no Description Insolation transformer PSU board see Tab 1 fig 2 TAMPER micro switch contacts of tamper resistance NC FMAINS fuse in the supply circuit 230 V L N power supply connector 230 V protect...

Page 10: ...the enclosure see fig 3 7 and guarantees indication in case of any attempts of detaching the device from the mounting surface Proper installation is one of the requirements of the EN 50131 6 standard...

Page 11: ...the protection system against complete battery discharge 11 Check the current consumption of the receivers taking into account the battery charging current so as not to exceed the total current effici...

Page 12: ...g 5 Control panel Table 5 The description of the buttons and LEDs of the LED panel Description Additional information moves the pointer on the screen next screen selection selection approval red LED i...

Page 13: ...e voltage indicator displays the measured output voltage at the AUX output If the voltage drops below 13 V during operation with activated battery test or exceeds 14 7 V the PSU will indicate a failur...

Page 14: ...tically displayed if the memory has more failures pressing the OK button will result in displaying subsequent codes the parameter on the display marks the end of the list of failures 5 2 4 Current fai...

Page 15: ...e code will be automatically displayed if the memory has more failures pressing the OK button will result in displaying subsequent codes the parameter on the display marks the end of the list of failu...

Page 16: ...Low battery voltage APS FLT the battery voltage has dropped below 11 5 V during battery assisted operation F11 Low battery volt off APS FLT the battery voltage has dropped below 10 V during battery as...

Page 17: ...bols Symbol Description Additional information Battery test tSt On battery test on OFF battery test off Sections 5 3 1 LED display dimmer On dimmer ON OFF dimmer OFF Sections 5 3 2 Communication addre...

Page 18: ...your choice with the OK button in order to return to the main menu simultaneously press the rightmost and leftmost buttons on the LED panel Deactivating activating the test with the STOP button on the...

Page 19: ...mer on OFF dimmer off confirm by pressing OK in order to return to the main menu simultaneously press the rightmost and leftmost buttons 5 3 3 Setting the communication address Adr applies to cooperat...

Page 20: ...ss parity and speed should have the same settings for both the PSU and the PowerSecurity program The PSU has preset transmission parameters of 115200 baud 8E1 However if it is connected to the network...

Page 21: ...he panel use the or buttons in order to set the required communication mode 8N2 8E1 factory setting 8O1 confirm by pressing OK in order to return to the main menu simultaneously press the rightmost an...

Page 22: ...ndicates the PSU failure Under normal status during correct operation the output is close In case of a failure the PSU will switch the output into the open state Any failures can be triggered by the f...

Page 23: ...ee a correct cooperation between the module and the EXT IN input the VEXT jumper must be on and the connections are to be made accordingly to the diagram below Fig 11 Example of a connection with the...

Page 24: ...ated by the OVP yellow LED on the PCB board and the PSU FLT output 5 9 PSU overload The PSU is fitted with the LED OVL overload on the PCB and indicator on the LED panel informing about output overloa...

Page 25: ...s voltage The protection mode is off when the PBAT jumper is removed Caution Deactivating of the UVP function is not recommended since a deep discharge of the battery limits its capability of storing...

Page 26: ...tery charging time The PSU has a battery circuit charged with direct current The current selection is done with use of the IBAT jumpers The table below shows how long does it take to charge a fully di...

Page 27: ...onsumption used for the calculation of standby time should be taken into account see section 6 4 7 1 ETHERNET network communication Communication in the Ethernet network is possible due to the additio...

Page 28: ...www pulsar pl PSBEN5012D BLACK POWER 28 Fig 13 Ethernet network communication using the RS485 INTRE interface...

Page 29: ...the program into smaller areas depending on the number of monitored power supplies The program is equipped with manager mode which allows the grouping of power supplies for easier analysis and orient...

Page 30: ...circuit protection SCP Electronic current limitation and or FBAT fuse failure in the battery circuit requires fuse replacement Automatic return Overload protection OLP Program equipment Battery circui...

Page 31: ...Terminals Supply 0 63 2 50 AWG 22 10 Outputs 0 51 2 AWG 24 12 BAT battery outputs 6 3F 2 5 30cm Notes The enclosure does not adjoin the assembly surface so that cables can be led Convectional cooling...

Page 32: ...batteries and run the battery test 4 weeks after installation re tighten all screw connections see Fig 2 9 WEEE LABEL According to the European Union WEEE Directive waste electrical and electronic eq...

Reviews: