background image

www.pulsar.pl   

 

 

 

PSBEN5012D   

 

 

 

    

BLACK POWER

 

 
 

11 

off. 

The battery protection is on when the P

BAT

 jumper is off.

 

7. Switch on the ~230 V supply (red AC diode and green AUX diode should be on). 
8.  Check  the  output  voltage  (the  PSU  voltage  without  load  and  without  battery  should  amount  to  13.

7  V÷13.9 V, 

with a battery or during battery charging process: 11.0 

V÷13.8 V). If the value of the voltage requires adjustment, it 

should be set with use of the V

ADJ

 potentiometer, monitoring the voltage at the AUX output of the PSU. 

9. Connect the batteries in accordance with the markings: +BAT red to 'plus', -

BAT black to 'minus’. The LB diode 

should be on during battery charging process. 
10. Press the STOP button to activate or deactivate a dynamic battery test. Deactivating the test turns out the PSU 
failure  indication  at  the  APS  FLT  output,  but  it  does  not  affect  the  protection  system  against  complete  battery 
discharge. 
11. Check the current consumption of the receivers, taking into account the  battery charging current, so as not to 
exceed the total current efficiency of the PSU. 
12. Once the tests are completed, close the PSU cover. 
 
        

Table 3. Operation parameters. 

Environmental class 

II 

Operating temperature 

-

10ºC...+40ºC 

Storing temperature 

-

20ºC...+60ºC 

Relative humidity 

20%...90%, no condensation 

Sinusoidal vibrations during operation 

EN 50130-5 

Surges during operation 

EN 50130-5 

Direct insolation 

unacceptable 

Vibrations and surges during transport 

PN-83/T-42106 

 
 
         

Table 4. Factory settings of the PSU. 

Indication time of EPS network loss 

5s 

section 5.5 

Battery charging current 

1,5 A 

section 6.5 

Battery presence 

YES (battery present) 

section 6.6 

Battery test 

ON 

  section 5.3.1 

section 6.3 

Deep discharge battery protection UVP 

ON 

section 6.2 

Acoustic indication 

ON 

section 5.4 

LED display dimmer 

OFF 

 section 5.3.2 

Communication address 

 section 5.3.3 

Transmission 

115.2k 8E1 

 section 5.3.4 
 section 5.3.5

 

 

Summary of Contents for PSBEN 5012D

Page 1: ...PSBEN 5012D v 1 1 PSBEN 13 8V 5A 40Ah EN Buffer switch mode power supply unit Grade 3 EN Edition 9 from 31 01 2019 Supercedes edition 8 from 31 01 2019 LED Version...

Page 2: ...2 LED Display Dimmer dIS 19 5 3 3 Setting the communication address Adr applies to cooperation with PowerSecurity 19 5 3 4 Setting the transmission speed trS applies to cooperation with PowerSecurity...

Page 3: ...ww pulsar pl PSBEN5012D BLACK POWER 3 8 TECHNICAL PARAMETERS 30 TABLE 13 ELECTRICAL PARAMETERS 30 TABLE 14 MECHANICAL PARAMETERS 31 TABLE 15 SAFETY OF USE 31 9 TECHNICAL INSPECTIONS AND MAINTENANCE 32...

Page 4: ...charge protection battery output protection against short circuit and reverse polarity connection jumper selectable battery charging current 0 6 A 1 5 A 2 2 A 3 A remote battery test additional module...

Page 5: ...ES YES No battery charge YES YES Low output voltage YES YES High output voltage YES YES PSU failure YES YES Surge protection YES YES Short circuit protection YES YES YES YES Overload protection YES YE...

Page 6: ...tandard Output current 0 66 A 3 A battery charge General use if the PSU is not mounted in an installation complaint with the EN 50131 standard the acceptable current efficiency amounts to 1 Output cur...

Page 7: ...ACK POWER 7 3 2 Block diagram The PSU is manufactured based on a high duty system of DC DC converter The microprocessor system is responsible for full diagnostics of the PSU and battery parameters Fig...

Page 8: ...utton disconnection of the PSU during battery assisted operation pin activation of the acoustic indication indication on indication off Caption jumper on jumper off VADJ potentiometer DC voltage adjus...

Page 9: ...nt no Description Insolation transformer PSU board see Tab 1 fig 2 TAMPER micro switch contacts of tamper resistance NC FMAINS fuse in the supply circuit 230 V L N power supply connector 230 V protect...

Page 10: ...the enclosure see fig 3 7 and guarantees indication in case of any attempts of detaching the device from the mounting surface Proper installation is one of the requirements of the EN 50131 6 standard...

Page 11: ...the protection system against complete battery discharge 11 Check the current consumption of the receivers taking into account the battery charging current so as not to exceed the total current effici...

Page 12: ...g 5 Control panel Table 5 The description of the buttons and LEDs of the LED panel Description Additional information moves the pointer on the screen next screen selection selection approval red LED i...

Page 13: ...e voltage indicator displays the measured output voltage at the AUX output If the voltage drops below 13 V during operation with activated battery test or exceeds 14 7 V the PSU will indicate a failur...

Page 14: ...tically displayed if the memory has more failures pressing the OK button will result in displaying subsequent codes the parameter on the display marks the end of the list of failures 5 2 4 Current fai...

Page 15: ...e code will be automatically displayed if the memory has more failures pressing the OK button will result in displaying subsequent codes the parameter on the display marks the end of the list of failu...

Page 16: ...Low battery voltage APS FLT the battery voltage has dropped below 11 5 V during battery assisted operation F11 Low battery volt off APS FLT the battery voltage has dropped below 10 V during battery as...

Page 17: ...bols Symbol Description Additional information Battery test tSt On battery test on OFF battery test off Sections 5 3 1 LED display dimmer On dimmer ON OFF dimmer OFF Sections 5 3 2 Communication addre...

Page 18: ...your choice with the OK button in order to return to the main menu simultaneously press the rightmost and leftmost buttons on the LED panel Deactivating activating the test with the STOP button on the...

Page 19: ...mer on OFF dimmer off confirm by pressing OK in order to return to the main menu simultaneously press the rightmost and leftmost buttons 5 3 3 Setting the communication address Adr applies to cooperat...

Page 20: ...ss parity and speed should have the same settings for both the PSU and the PowerSecurity program The PSU has preset transmission parameters of 115200 baud 8E1 However if it is connected to the network...

Page 21: ...he panel use the or buttons in order to set the required communication mode 8N2 8E1 factory setting 8O1 confirm by pressing OK in order to return to the main menu simultaneously press the rightmost an...

Page 22: ...ndicates the PSU failure Under normal status during correct operation the output is close In case of a failure the PSU will switch the output into the open state Any failures can be triggered by the f...

Page 23: ...ee a correct cooperation between the module and the EXT IN input the VEXT jumper must be on and the connections are to be made accordingly to the diagram below Fig 11 Example of a connection with the...

Page 24: ...ated by the OVP yellow LED on the PCB board and the PSU FLT output 5 9 PSU overload The PSU is fitted with the LED OVL overload on the PCB and indicator on the LED panel informing about output overloa...

Page 25: ...s voltage The protection mode is off when the PBAT jumper is removed Caution Deactivating of the UVP function is not recommended since a deep discharge of the battery limits its capability of storing...

Page 26: ...tery charging time The PSU has a battery circuit charged with direct current The current selection is done with use of the IBAT jumpers The table below shows how long does it take to charge a fully di...

Page 27: ...onsumption used for the calculation of standby time should be taken into account see section 6 4 7 1 ETHERNET network communication Communication in the Ethernet network is possible due to the additio...

Page 28: ...www pulsar pl PSBEN5012D BLACK POWER 28 Fig 13 Ethernet network communication using the RS485 INTRE interface...

Page 29: ...the program into smaller areas depending on the number of monitored power supplies The program is equipped with manager mode which allows the grouping of power supplies for easier analysis and orient...

Page 30: ...circuit protection SCP Electronic current limitation and or FBAT fuse failure in the battery circuit requires fuse replacement Automatic return Overload protection OLP Program equipment Battery circui...

Page 31: ...Terminals Supply 0 63 2 50 AWG 22 10 Outputs 0 51 2 AWG 24 12 BAT battery outputs 6 3F 2 5 30cm Notes The enclosure does not adjoin the assembly surface so that cables can be led Convectional cooling...

Page 32: ...batteries and run the battery test 4 weeks after installation re tighten all screw connections see Fig 2 9 WEEE LABEL According to the European Union WEEE Directive waste electrical and electronic eq...