Pulsar PSBEN 5012C Manual Download Page 19

www.pulsar.pl   

 

 

 

PSBEN5012C   

 

 

 

 
 

19 

9. PSU FAILURE CODES. 

 

LED indication 

Failure 

code 

EXT 

OVL 

AC 

PSU 

APS 

Acoustic 

indication 

Technical 

outpust 

actvation  

Fault description 

Causes 

F01 

1 beep 

per 10s 

EPS FLT 

Battery-assisted 

operation 

 

- No AC mains 

supply 

- Faulty main fuse 

F

MAIN

 

F02 

ON 

twinkles 

ON 

PSU FLT 

PTC polyswitch 

activation at the 

AUX output 

- Overloaded AUX 

output 

F03 

 
 
 

ON 

twinkles 

ON 

APS FLT 

Blown fuse of the 

battery F

BAT

 

- Short circuit in the 

battery circuit 

- Short circuit in the 

AUX output circuit 
- Overloaded AUX 

output 

F04 

ON 

ON 

ON 

ON 

PSU FLT 

- Overloaded AUX 

output 

F05 

 
 

ON 

ON 

1 beep 

per 10s 

 

APS FLT 

Faulty battery* 

- Drained battery 

- Undercharged 

battery 

- Unplugged battery 

F06 

ON 

1 flash 

ON 

PSU FLT 

Too high output voltage 

- Output voltage 

>14.7V 

F07 

ON 

2 flashes 

ON 

PSU FLT 

Too high battery 

voltage* 

- Battery voltage  

> 14V 

F08 

 
 

ON 

3 flashes 

ON 

PSU FLT 

Battery charging circuit 

failure 

- Too low output 

voltage of the PSU, 

set <13V 

- Fault in the battery 

charging circuit 

F09 

 

ON 

4 flashes 

ON 

 

PSU FLT 

Too low output voltage 

- Output voltage 

<11.8V (during buffer 

operation) 

F10 

ON 

2 signals 

per 10s 

 

APS FLT 

Too low battery voltage 

- Battery voltage 

drops below 11.5V 

(during battery-

assisted operation) 

F11 

ON 

Fast 

audible 

signals 

 

APS FLT 

PSU disconnection 

caused by battery 

discharge 

- Battery voltage 

drops below 10V 

(during battery-

assisted operation) 

F12 

ON 

ON 

ON 

PSU FLT 

Activation of the EXT IN 

collective failure input 

F50 

   - 

ON 

ON 

PSU FLT 

Internal damage of the 

PSU 

F51 

ON 

ON 

PSU FLT 

Error in setting memo 

F60 

No communication 

Broken cord between 

the PSU and the 

display 

F61-64 

Desktop fault 

F65 

Password unblocking 

procedure 

 
* failure indication only during a battery test 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for PSBEN 5012C

Page 1: ...PSBEN 5012C v 1 0 PSBEN 13 8V 5A 17Ah EN Buffer switched mode power supply unit EN Edition 3 from 20 11 2012 Supersedes the 2 from 14 09 2012 edition...

Page 2: ...11 4 4 STANDBY TIME 12 4 5 BATTERY CHARGING TIME 12 4 6 OPERATION WITHOUT A BATTERY 12 5 REMOTE MONITORING OPTION WI FI ETHERNET RS485 USB 13 5 1 COMMUNICATION IN WI FI WIRELESS NETWORK 13 5 2 COMMUNI...

Page 3: ...OVL acoustic indication of failure adjustable times indicating AC power failure technical inputs outputs with galvanic isolation collective failure input EXT IN EPS technical output indicating AC powe...

Page 4: ...to the Alarm Receiving Centre ARC in accordance with 9 2 PN EN 50131 1 Output voltage 0 28A 3A battery charge General use if the PSU is not mounted within an installation which is PN EN 50131 complia...

Page 5: ...ing battery assisted operation 5 pin activation of the acoustic indication indication on indication off Caption jumper on jumper off 6 VADJ potentiometer DC voltage adjustment 7 BUZER acoustic indicat...

Page 6: ...ent no Description 1 Insolation transformer 2 PSU board tab 1 fig 2 3 TAMPER micro switch contacts of tamper resistance NC 4 FMAIN fuse in the supply circuit 230 V AC 5 L N 230V AC power connector PE...

Page 7: ...status indication 3 1 Control panel The PSU is equipped with a panel with buttons and an LED display which enables reading the basic parameters of the device The buttons are for selecting and approvin...

Page 8: ...LED indicates battery failure green LED indicates power at the AUX output of the PSU three yellow LEDs indicate battery charging level Fig 5 Menu of the display FLt PSU fault memo 30 last events Io A...

Page 9: ...10s mains operation Battery fault undercharged battery 3 2 signals per 10s battery assisted operation Low level of battery charge 4 Fast signals battery assisted operation The PSU will be disconnected...

Page 10: ...he failure signal If voltage appears at the EXT IN input it will cause generating a PSU failure storing the information about the event in the internal memo and sending the signal about the failure to...

Page 11: ...is removed Caution Deactivating of the UVP function is not recommended since a deep discharge of the battery limits its capability of storing energy lowers its capacity and shortens its durability 4...

Page 12: ...attery charge 4 5 Battery charging time The PSU has a battery circuit charged with direct current The current selection is done via IBAT jumpers The table below shows how long it takes to charge a ful...

Page 13: ...ge of wireless communication is lack of additional cords and fast development or modification of the network s structure Fig 10 WI FI communication with the use of the WI FI INTW interface 5 2 Communi...

Page 14: ...B TTL INTU needs to be used This interface allows direct connection between the computer and the PSU and it is recognisable by the operating system as a virtual COM port Fig 13 KUSB TTL communication...

Page 15: ...0A without battery Io 4 4A 0 6A battery charge Io 3 5A 1 5A battery charge Io 2 8A 2 2A battery charge Io 2 0A 3A battery charge Output voltage setting escalation and keeping time 5ms 40ms 18ms Outpu...

Page 16: ...s can be led Convectional cooling Table 8 Operation safety Protection class PN EN 60950 1 2007 I first Protection grade PN EN 60529 2002 U IP20 Electrical strength of insulation between input network...

Page 17: ...ntees indication in case of any attempts of detaching the device from the mounting surface Proper installation is one of the requirements of the PN EN 50131 6 standard Fig 15 Fixing a tamper grip 2 Co...

Page 18: ...uts to protect the battery and the receivers from damage The outputs will be battery powered The protection system is indicated by illuminating of the OVP red LED on the pcb board PSU FLT output statu...

Page 19: ...voltage 14 7V F07 ON 2 flashes ON PSU FLT Too high battery voltage Battery voltage 14V F08 ON 3 flashes ON PSU FLT Battery charging circuit failure Too low output voltage of the PSU set 13V Fault in...

Page 20: ...ibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carri...