PSBEN5012C   

 

 

 

 
 

11 

 

Fig. 9. Example of a connection with the fuse module: AWZ535 or AWZ536. 

 

4. Battery-assisted operation. 

 

4.1. Running the PSU from the battery. 

 

The PSU has been equipped with two buttons on the pcb board which enable running or disconnecting the 

PSU during battery-assisted operation. 

 

Running the PSU from the battery: press the START button on the main board and hold for 1s. 

 

Disconnecting the PSU from the battery: press the STOP button on the main board and hold for 5s. 

 

 
4.2. Deep discharge battery protection UVP. 

The PSU is equipped with the  disconnection system and the discharged  battery indication. If the voltage at 

the battery terminals drops below10V±0.2V during battery-assisted operation, the PSU will  be disconnected within 
approx. 15s. The protection mode is off when the P

BAT 

jumper is removed. 

 
Caution. 
Deactivating of the UVP function is not recommended since a deep discharge of the battery limits its 
capability of storing energy, lowers its capacity and shortens its durability. 
 

 
 

4.3 Dynamic battery test. 

The PSU runs a battery test every 10 minutes. It is done by a  momentary switching into a  battery-assisted 

operation. A failure is indicated when voltage drops below 12V. The battery test facility can be switched off. 

 

Deactivating/activating  the  test:  during  mains-powered  PSU  operation  press  the  STOP  button  on  the 

main  board  and  hold  it  for  3  seconds.  The  device  will  confirm  the  activation/deactivation  in  the  following  ways: 
(Tab.4, [6], [7]).  

 

testing off – the tOF sign appears on the display 

 

testing on –  the tON sign appears on the display 

 

 
Deactivating/activating  the  test  is  stored  in  the  memory  even  after  unplugging  the  device  from 
mains.  The  battery  failure  indication  at  the  APS  FLT  output  is  automatically  switched  off.  The 
battery protection system against deep discharged remains on, though. 
 

 

Summary of Contents for PSBEN 5012C

Page 1: ...PSBEN 5012C v 1 0 PSBEN 13 8V 5A 17Ah EN Buffer switched mode power supply unit EN Edition 3 from 20 11 2012 Supersedes the 2 from 14 09 2012 edition...

Page 2: ...11 4 4 STANDBY TIME 12 4 5 BATTERY CHARGING TIME 12 4 6 OPERATION WITHOUT A BATTERY 12 5 REMOTE MONITORING OPTION WI FI ETHERNET RS485 USB 13 5 1 COMMUNICATION IN WI FI WIRELESS NETWORK 13 5 2 COMMUNI...

Page 3: ...OVL acoustic indication of failure adjustable times indicating AC power failure technical inputs outputs with galvanic isolation collective failure input EXT IN EPS technical output indicating AC powe...

Page 4: ...to the Alarm Receiving Centre ARC in accordance with 9 2 PN EN 50131 1 Output voltage 0 28A 3A battery charge General use if the PSU is not mounted within an installation which is PN EN 50131 complia...

Page 5: ...ing battery assisted operation 5 pin activation of the acoustic indication indication on indication off Caption jumper on jumper off 6 VADJ potentiometer DC voltage adjustment 7 BUZER acoustic indicat...

Page 6: ...ent no Description 1 Insolation transformer 2 PSU board tab 1 fig 2 3 TAMPER micro switch contacts of tamper resistance NC 4 FMAIN fuse in the supply circuit 230 V AC 5 L N 230V AC power connector PE...

Page 7: ...status indication 3 1 Control panel The PSU is equipped with a panel with buttons and an LED display which enables reading the basic parameters of the device The buttons are for selecting and approvin...

Page 8: ...LED indicates battery failure green LED indicates power at the AUX output of the PSU three yellow LEDs indicate battery charging level Fig 5 Menu of the display FLt PSU fault memo 30 last events Io A...

Page 9: ...10s mains operation Battery fault undercharged battery 3 2 signals per 10s battery assisted operation Low level of battery charge 4 Fast signals battery assisted operation The PSU will be disconnected...

Page 10: ...he failure signal If voltage appears at the EXT IN input it will cause generating a PSU failure storing the information about the event in the internal memo and sending the signal about the failure to...

Page 11: ...is removed Caution Deactivating of the UVP function is not recommended since a deep discharge of the battery limits its capability of storing energy lowers its capacity and shortens its durability 4...

Page 12: ...attery charge 4 5 Battery charging time The PSU has a battery circuit charged with direct current The current selection is done via IBAT jumpers The table below shows how long it takes to charge a ful...

Page 13: ...ge of wireless communication is lack of additional cords and fast development or modification of the network s structure Fig 10 WI FI communication with the use of the WI FI INTW interface 5 2 Communi...

Page 14: ...B TTL INTU needs to be used This interface allows direct connection between the computer and the PSU and it is recognisable by the operating system as a virtual COM port Fig 13 KUSB TTL communication...

Page 15: ...0A without battery Io 4 4A 0 6A battery charge Io 3 5A 1 5A battery charge Io 2 8A 2 2A battery charge Io 2 0A 3A battery charge Output voltage setting escalation and keeping time 5ms 40ms 18ms Outpu...

Page 16: ...s can be led Convectional cooling Table 8 Operation safety Protection class PN EN 60950 1 2007 I first Protection grade PN EN 60529 2002 U IP20 Electrical strength of insulation between input network...

Page 17: ...ntees indication in case of any attempts of detaching the device from the mounting surface Proper installation is one of the requirements of the PN EN 50131 6 standard Fig 15 Fixing a tamper grip 2 Co...

Page 18: ...uts to protect the battery and the receivers from damage The outputs will be battery powered The protection system is indicated by illuminating of the OVP red LED on the pcb board PSU FLT output statu...

Page 19: ...voltage 14 7V F07 ON 2 flashes ON PSU FLT Too high battery voltage Battery voltage 14V F08 ON 3 flashes ON PSU FLT Battery charging circuit failure Too low output voltage of the PSU set 13V Fault in...

Page 20: ...ibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carri...

Reviews: