www.pulsar.pl
PSBEN5012C
11
Fig. 9. Example of a connection with the fuse module: AWZ535 or AWZ536.
4. Battery-assisted operation.
4.1. Running the PSU from the battery.
The PSU has been equipped with two buttons on the pcb board which enable running or disconnecting the
PSU during battery-assisted operation.
•
Running the PSU from the battery: press the START button on the main board and hold for 1s.
•
Disconnecting the PSU from the battery: press the STOP button on the main board and hold for 5s.
4.2. Deep discharge battery protection UVP.
The PSU is equipped with the disconnection system and the discharged battery indication. If the voltage at
the battery terminals drops below10V±0.2V during battery-assisted operation, the PSU will be disconnected within
approx. 15s. The protection mode is off when the P
BAT
jumper is removed.
Caution.
Deactivating of the UVP function is not recommended since a deep discharge of the battery limits its
capability of storing energy, lowers its capacity and shortens its durability.
4.3 Dynamic battery test.
The PSU runs a battery test every 10 minutes. It is done by a momentary switching into a battery-assisted
operation. A failure is indicated when voltage drops below 12V. The battery test facility can be switched off.
Deactivating/activating the test: during mains-powered PSU operation press the STOP button on the
main board and hold it for 3 seconds. The device will confirm the activation/deactivation in the following ways:
(Tab.4, [6], [7]).
•
testing off – the tOF sign appears on the display
•
testing on – the tON sign appears on the display
Deactivating/activating the test is stored in the memory even after unplugging the device from
mains. The battery failure indication at the APS FLT output is automatically switched off. The
battery protection system against deep discharged remains on, though.