www.pulsar.pl   

 

 

 

PSBEN101A2D/LCD 

 

 

 

 

 
 

 

Features: 

  

  PN-EN50131-6 compliance, grades 1÷3 and II 

environmental class 

  mains supply of 230VAC 

  uninterrupted voltage of 13,8VDC 

  fitting battery: 40Ah/12V 

  high efficiency 80% 

  PSU current efficiency: 

  3,33A  – for grades 1 , 2 * 

  1,33A – for grades 3 ** 

  10A  – for general use *** 

(see: chapter 2.1) 

  low level of voltage ripple  

  microprocessor-based automation system 

  intelligent management of PSU power’s output stage 

 

SERIAL’ communication port with implemented 

MODBUS RTU protocol 

  remote monitoring (option: WiFi, Ethernet, RS485, USB) 

  free program -  ‘PowerSecurity’ for monitoring the PSU 

operation parameters  

  load current control 

  output voltage control 

  output fuse status control 

  dynamic battery test 

  battery circuit continuity control 

  battery voltages control 

  battery fuse status control 

  battery charge and maintenance control 

  deep discharge battery protection (UVP) 

  battery overcharge protection 

  battery output protection against short circuit and reverse 

polarity connection 

  jumper selectable battery charging current 

0,6A/1,5A/2,2A/3A 

  remote battery test (additional module required) 

  START button for battery activation 

  STOP button for disconnecting during battery-assisted 

operation 

  optical indication – LCD panel 

  electrical parameters reading, e.g.: voltage, 

current 

  failure indication 

  PSU settings adjusted from the panel’s level 

  3 levels of access, password-protected  

  PSU’s operation history 

  failure history 

  real-time clock, battery-backed 

  optical indication of PSU overload OVL 

  acoustic indication of failure 

  adjustable times indicating AC power failure 

  technical inputs/outputs with galvanic isolation 

  collective failure input EXT IN 

  EPS technical output indicating AC power loss  

  PSU technical output indicating PSU failure 

  APS technical output indicating battery failure 

  internal memory of PSU operating status 

  protections: 

 

SCP short circuit protection 

 

OLP overload protection 

 

OHP overheat protection 

 

OVP over voltage protection 

 

surge protection 

 

against tampering: unwanted opening of the 

enclosure or detachment from the mounting surface 

 convectional cooling 

 warranty – 5 year from the production date 

 

 

1. Functional requirements of the PSU compliant with PN-EN 50131-6. 

Requirements of 

PN-EN 50131-6 

Functional requirements 

Grade 1 

Grade 2 

Grade 3 

PSBEN10A12D

/LCD 

EPS network absence 

YES 

YES 

YES 

YES 

Battery low voltage 

YES 

YES 

YES 

YES 

Protection against full battery discharge 

YES 

YES 

Battery fault 

YES 

YES 

No battery charge 

YES 

YES 

Output low voltage 

YES 

YES 

Output high voltage 

YES 

YES 

PSU fault 

YES 

YES 

Surge protection 

YES 

YES 

Short circuit protection 

YES 

YES 

YES 

YES 

Overload protection 

YES 

YES 

YES 

YES 

Output fuse activation 

YES 

Battery fuse fault 

YES 

EPS technical output 

YES 

YES 

YES 

YES 

APS technical output 

YES 

YES 

YES 

YES 

PSU technical output 

YES 

YES 

YES 

YES 

Collective failure input 

YES 

Remote battery test 

YES 

Tamper resistance – enclosure opening 

YES 

YES 

YES 

YES 

Tamper resistance – detachment from the 
mounting surface 

YES 

YES 

Summary of Contents for PSBEN 10A12D/LCD

Page 1: ...PSBEN 10A12D LCD v 1 0 PSBEN 13 8V 10A 40Ah EN LCD Buffer switched mode power supply unit EN Edition 4 from 01 02 2013 Supersedes the 3 from 20 11 2012edition...

Page 2: ...g the EPS output lag 17 Setting the communication address 18 3 4 3 Desktop 18 Setting the language of messages 19 Setting the date 19 Setting the time 20 Setting the highlighting 20 Setting the contra...

Page 3: ...EQUIREMENTS 31 7 2 INSTALLATION PROCEDURE 31 8 OPERATION AND USE 32 8 1 OVER VOLTAGE PROTECTION OVP AT THE PSU OUTPUT 32 8 2 OVERLOAD OF THE PSU 32 8 3 SHORT CIRCUIT AT THE PSU OUTPUT 32 8 4 BATTERY R...

Page 4: ...s operation history failure history real time clock battery backed optical indication of PSU overload OVL acoustic indication of failure adjustable times indicating AC power failure technical inputs o...

Page 5: ...ource are reported to the Alarm Receiving Centre ARC in accordance with 9 2 PN EN 50131 1 Output voltage 0 66A 3A battery charge General use if the PSU is not mounted within an installation which is P...

Page 6: ...ion on indication off Caption jumper on jumper off 6 VADJ potentiometer DC voltage adjustment 7 BUZZER acoustic indicator 8 FBAT fuse in the battery circuit 9 Connectors AC AC power input BAT DC power...

Page 7: ...ement no Description 1 Insolation transformer 2 PSU board tab 1 fig 2 3 TAMPER micro switch contacts of tamper resistance NC 4 FMAIN fuse in the supply circuit 230 V AC 5 L N 230V AC power connector P...

Page 8: ...atus indication 3 1 Control panel The PSU is equipped with a panel with buttons and an LCD display which enables reading all available parameters of the device The buttons are for selecting and approv...

Page 9: ...lay The main screen of the LCD display shows basic electrical parameters and informs about the current PSU state Fig 5 The main screen Table 4 Description of the symbols on the main screen Screen fiel...

Page 10: ...status during operation Highlighting of an element informs about an active state and reflects the status of LEDs on the pcb of the PSU see table 1 12 Fig 7 Screen parameters of the PSU Table 5 Descrip...

Page 11: ...analysis of the values shown on the chart the time range of the chart screen can be adjusted in the bottom axis Here are the available ranges 8h 24h 2days week weekly In order to change the displayed...

Page 12: ...erates 3 levels of access to configuration which limit the possibility of changing the PSU s settings from the level of the LCD desktop They are protected with separate passwords Keypad password locks...

Page 13: ...ear with or choose the right level of the password confirm your choice with the SET button with or enter the first digit confirm your choice with the SET button with or enter the second digit confirm...

Page 14: ...sswords have been lost there is a procedure that will allow reassigning the passwords Please do as follows a unplug the PSU from the AC network and the battery for at least 10 seconds b press the STOP...

Page 15: ...to the PSU NO battery not connected to the PSU see chapter 4 6 Battery test YES battery test on NO battery test off see chapter 4 3 Battery protection YES battery protection function disconnection on...

Page 16: ...onfirm your choice with the SET button Setting the battery test with or choose the Battery test menu press the SET button you will see the prompt at the end of the line with or set YES or NO YES batte...

Page 17: ...nction disconnection on NO battery protection function disconnection off confirm your choice with the SET button Setting the EPS output lag with or choose the EPS output lag menu press the SET button...

Page 18: ...mputer confirm your choice with the SET button 3 4 3 Desktop The facility is only available after entering the correct user s or installer s password The Desktop menu enables setting the current date...

Page 19: ...you will see the prompt at the end of the line with or choose the language of messages confirm your choice with the SET button Setting the date with or choose the Date menu press the SET button the pr...

Page 20: ...section with or set the minutes press the SET button the prompt will move to the second section with or set the seconds approve the settings with the SET button Setting the highlighting Intensity of t...

Page 21: ...xt to the constant option with or change the setting into 60 s press the SET button the prompt will move to the end of the line with or set the demanded screen brightness approve your choice with the...

Page 22: ...y the output is close In case of a power failure the PSU will switch the output into the open state after a period of time determined by the EPS output lag facility see 3 4 2 table 7 APS FLT output in...

Page 23: ...IN technical input has been implemented with galvanic isolation between the PSU s systems and the devices attached Fig 16 Electrical diagram of the EXT IN input The electrical diagram below shows the...

Page 24: ...attery test facility can be switched off Deactivating activating the test enter the PSU settings from the level of the LCD desktop by pressing the SET button Then choose PSU Battery protection YES NO...

Page 25: ...2 J3 16h24m 2 2 J1 J2 J3 24h 1 5 J1 J2 J3 0 6 J1 J2 J3 4 6 Operation without a battery In case of an expected PSU operation without an attached battery make a necessary configuration setting from the...

Page 26: ...aces 5 1 Communication in the wi fi wireless network The Wi Fi wireless communication is to be implemented on the basis of additional interfaces WI Fi INTW and RS485 WiFi operating within 2 4GHz frequ...

Page 27: ...Ethernet communication with the use of the INTE interface The RS485 ETHERNET INTRE interface is a device intended for converting signals between the RS485 bus and the Ethernet network To work correct...

Page 28: ...ation with the use of the interfaces INTR and INTUR 5 4 USB TTL communication If the PSU does not cooperate with any of previously mentioned network and the access to the parameters adjustment and mem...

Page 29: ...battery charge Io 9 1A 1 5A battery charge Io 8 4A 2 2A battery charge Io 7 6A 3A battery charge Output voltage setting escalation and keeping time 8ms 3ms 25ms Output voltage adjustment range 12 V 14...

Page 30: ...x 355 x 170 8 WxHxD mm 2 Fixing 300 x 318 x 6 x4 WxH Fitting battery 40Ah 12V SLA max Net gross weight 8 2 8 7 kg Enclosure Steel plate DC01 1 2mm colour RAL 9005 black Closing Cheese head screw x2 a...

Page 31: ...and assigning an appropriate fuse in the fuse box The electrical system shall follow valid standards and regulations 7 2 Installation procedure CAUTION Before installation cut off the voltage in the 2...

Page 32: ...Operation and use 8 1 Over voltage protection OVP at the PSU output In case of voltage exceeding 15 5V 0 5V at the regulator s output the system cuts off the power at the outputs to protect the batter...

Page 33: ...high output voltage Output voltage 14 7V F07 ON 2 flashes ON PSU FLT Too high battery voltage Battery voltage 14V F08 ON 3 flashes ON PSU FLT Battery charging circuit failure Too low output voltage of...

Page 34: ...ssibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are car...