www.pulsar.pl
PSBEN10A12C
BLACK POWER
21
5.3.5
Setting the parity of the transmission
“trP”
applies to cooperation with PowerSecurity.
All the parameters responsible for communication between the PSU and the computer, namely the
address, parity and speed should have the same settings for both the PSU and the PowerSecurity program.
The PSU has preset transmission parameters of 115200 baud 8E1. However, if it is connected to the
network with differently defined parameters, make the appropriate changes to its configuration.
-
simultaneously press the „<,>” rightmost and leftmost buttons
-
the „tSt” parameter will be displayed
-
use the „<” or „>” buttons to display the „trP” parameter
- press
„OK”
- the information about the parity of the transmission will be displayed
on the panel
-
use the „<” or „>” buttons in order to set the required communication mode,
- 8N2
- 8E1
(factory setting)
- 8O1
- confirm by pressing
„OK”
-
in order to return to the main menu, simultaneously press the „<,>” rightmost
and leftmost buttons
5.4 Acoustic indication.
Emergency situations are acoustically indicated. The frequency and the number of signals depend on an
event type (see chapter. 5.2.5). The acoustic indication is off after removing an appropriate jumper (fig. 2, [5]).
Table 11. Acoustic indication
.
No.
Description
Event
1
1 signal per 10s, battery-assisted
operation
No 230V AC supply
2
1 signal per 10s, mains operation
Battery fault, undercharged battery
3
2 signals per 10s, battery-assisted
operation
Low level of battery charge
4
Fast signals, battery-assisted operation
The PSU will be disconnected due to the battery discharge
5
Continuous indication
PSU failure [see chapter. 5.2.5]
6
1 signal
Breaking the battery test
7
2 signals
Activation of the battery test