PSAC04244SEP 

   

 

 

Operating specifications (table 6). 

Operating temperature 

-10ºC...+40ºC  

Storage temperature 

-20ºC...+60ºC 

Relative humidity 

20%...90% without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct exposure to sunlight 

unacceptable 

Vibrations and Impulse waves during transport 

according PN-83/T-42106 

 
2. Installation. 
 

2.1 Requirements. 

The  AC/AC  power  supply  is  to  be  mounted  by  a  qualified  installer,  holding  relevant  permits  and  licenses 

(applicable  and  required  for  a  given  country)  for  230V/AC  interference  and  low-voltage  installations.  The  unit 
should  be  mounted  in  confined  spaces,  in  accordance  with  the  2nd  environmental  class,  with  normal  relative 
humidity (RH=90% maximum, without condensation) and temperature from -10°C to +40°C. The PSU shall wor k in 
a vertical position that guarantees free convectional air flow through the ventilating holes of the enclosure 

Before  installation  is  started,  the  balance  of  the  power-supply  load  shall  be  performed.  During  normal 

operation  total  current  drawn  by  the  receivers  cannot  exceed  I=4.0A@24V  AC.    As  the  PSU  is  designed  for  a 
continuous operation and is not equipped with a power-switch, therefore an appropriate overload protection in the 
power  supply  circuit  shall  be  guaranteed.  Moreover,  the  user  shall  be  informed  about  the  method  of  unplugging 
(usually through assigning  an appropriate fuse in  the  fuse-box). The electrical system shall follow valid standards 
and regulations.  

 

 

 

2.2 Installation procedure. 
 

1. Before installation, make sure that the voltage in the 230V power-supply circuit is cut off. 
2. Mount the power supply in the selected location and connect the wires. 
3. Connect the power cables (~230V AC) with L-N power supply terminals. Connect the ground wire to the terminal 
marked by the earth symbol – “

”. Use a three-core cable (with a  yellow and green PE protection wire) to make 

the connection. Lead the cables to the appropriate terminals of the connection board through the bushing. 

 

 The circuit of the shock protection shall be performed with a particular care, i.e. the yellow 
and  green  wire  coat  of  the  power  cable  shall  stick  to  one  side  of  the terminal  marked  with 
the  '

'  earth  symbol  in  the  PSU  enclosure.  Operation  of  the  power  supply  without  a 

properly  made  and  fully  operational  shock  protection  circuit  is  UNACCEPTABLE!  It  can 
result in device damage or an electric shock. 

. 

 

 
4. . Connect the cables of receivers to the OUT1÷OUT4 terminals on LB4-SEP fuse block. 
5. If necessary, connect devices’ wires (alarm panel, controller, indicator, etc.) to the PSU’s technical outputs:   
     - AW output indicating fuse activation (output of the LB4-SEP fuse block). 
    - TAMPER output indicating unwanted opening of the PSU enclosure 
6.  In  case  of  installation,  where  significant  voltage  drops  occur  in  the  resistance  of  the  cables  leading  to  the 
receivers, there is a possibility of voltage value correction by the U1/U2 jumpers, independently for each output. 
7. Connect 230V AC supply. 
8. Check LED indication for PSU operating status: LED L1÷L4 (green) should be constantly illuminated. 
9. Once the installation and operation control have been completed, the enclosure can be locked. 

 
 
3. Operating status indication. 

 

The PSU is equipped with LED indication the status of operation. The presence of power at the outputs of the PSU 
is indicated by the illumination of green LEDs on the PCB of the LB4-SEP fuse block. A failure is indicated by the 
red LED [!] AW. The PSU status can be remotely controlled by the AW technical output. 

Summary of Contents for PSAC 04244SEP

Page 1: ...PSAC 04244SEP v 1 0 PSAC 24VAC 4A 4x1A SEP AC power supply for CCTV EN Edition 2nd 05 Jul 2012 Supersedes the 1st 1 from 06 Dec 2011 edition...

Page 2: ...of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 LED indication 3 2 Technical output 4 Operation and us...

Page 3: ...g 2 the set of contacts indicates potential free status which corresponds to power supply failure 7 Jumper based fuse selection glass fuse or polymer fuse Fx Fx x Fx jumper on glass fuse selected Fx F...

Page 4: ...www pulsar pl PSAC04244SEP 4 Fig 3 View of the PSU s panel Fig 4 The view of the power supply...

Page 5: ...l free status which corresponds to power supply failure LED indication LED L1 L4 green LED LAW red status of OUT1 OUT4 normal status illuminated failure status not illuminated failure indication of mi...

Page 6: ...cted location and connect the wires 3 Connect the power cables 230V AC with L N power supply terminals Connect the ground wire to the terminal marked by the earth symbol Use a three core cable with a...

Page 7: ...tion and use 4 1 Overload or short circuit at the PSU output The OUT1 OUT4 outputs are protected against a short circuit with glass or polymer fuses In case of fuse damage the replacement of the same...

Page 8: ...ccepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried out at the service centre of the manufacturer exclusively 8 The warranty doe...