PSAC04244
6
- glass fuse damage requires fuse-element replacement
Overload protection OLP
circuit AC 24 V: 4x F 1,0A or PTC 1A
circuit AC 230V: T 1A
Surge protection
varistors
Overheat protection OHP
inside transformer
Sabotage protection:
- TAMPER output indicating enclosure
opening
- microswitch, NC contacts (enclosure closed),
0,5A@50 V DC (max.)
Technical outputs:
- FPS output indicating failure at one of
the AUX outputs (fuse activation)
- type OC, 50mA max.
normal state: level L (0 V)
failure: hi-Z level
LED indication:
LEDs
L1÷L4 (green)
LED L
FPS
(red)
-
AUX1…AUX4 output status
correct operation = on
failure = off
- failure indication, at min. one AUX outputs
correct operation = off
failure = on
F fuse
F1÷F4 fuse
T 1A/ 250V
F 1A/ 250V or PTC 1A
Mechanical specifications (tab. 4).
Enclosure dimensions
210 x 182 x 64+8 (WxHxD) [mm] (+/-2mm)
Fixing
178 x 150
x Φ6 (W
x H)
Net/gross weight
2,09 kg / 2,23 kg
Enclosure
Steel plate DC01 0,7mm thick, colour RAL9003
Closing
Cheese head screw (at the front)
Connectors
Power:
Φ0,63÷2,50 (AWG 22-10)
Outputs : Ф0,41÷1,63 (AWG 26-14),
TAMPER output : cable
s’ length: 30cm
Notes
The enclosure does not adjoin the assembly surface so that cables can be led.
Convectional cooling.
Operation safety (tab.5).
Protection class PN-EN 60950-1:2004
I (first)
Protection grade PN-EN 60529: 2002 (U)
IP20
Electrical strength of insulation:
- between input (network) circuit and output circuits of the PSU (I/P-O/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit (O/P-FG)
3000 V/AC min.
1500 V/AC min.
500 V/AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500V/DC
Operating specifications (tab.6).
Operating temperature
-
10ºC...+40ºC
Storage temperature
-
25ºC...+60ºC
Relative humidity
10%...90% without condensation
Vibrations during operation
unacceptable
Impulse waves during operation
unacceptable
Direct insolation
unacceptable
Vibrations and impulse waves during transport
PN-83/T-42106
2. Installation.
2.1 Requirements
The AC/AC power supply is to be mounted by a qualified installer, holding relevant permits and licenses
(applicable and required for a given country) for 230V/AC interference and low-voltage installations. The unit should be
mounted in confined spaces, in accordance with the 2nd environmental class, with normal relative humidity (RH=90%
maximum, without condensation) and temperature from -
10°C to +40°C (table 6). The PSU shall work in a vertical or
horizontal position.
Before mounting the PSU module, perform a load balance. During normal operation, total current drawn by the
receivers cannot exceed
I=4,0A@24V AC.
As the PSU is designed for a continuous operation and is not equipped with a
power-switch, therefore an appropriate overload protection shall be guaranteed in the power supply circuit. Moreover, the
user shall be informed about the method of unplugging (usually through assigning an appropriate fuse in the fuse-box).
The electrical system shall follow valid standards and regulations.