Pulsar MSRD 1024 Manual Download Page 5

www.pulsar.pl                                                                        MSRD1024                                                                        

 

 

 

Technical outputs: 
- FAC; output indicating failure of AC power 
supply 
 
 
 
- FPS; technical output of the PSU operation 
status 
 

-R – relay type, 1A@ 30Vdc/50Vac max. 

CAUTION! In Fig.2. the set of contacts indicates potential-
free status which corresponds to  AC power outage (AC 
power failure) 
- OC type, 50mA max., normal status: L (0V) level, failure: 
hi-Z level, time lag: 10s. 
 
- OC type, 50mA max. normal status: L (0V) level, failure: 
hi-Z level (automatic return after restoration of correct 
operation) 

LED indication  
- AC diode indicating AC power 
- AUX diode indicating DC at the PSU output 
- LB diode indicating battery charging process 
- F

BAT

 diode indicating battery fuse status 

 
- red, normal status: permanently illuminated 
- green, normal status: permanently illuminated 
 
- yellow, the light intensity depends on battery charging 
current  
- blue, normal status: off, fuse failure: permanently 
illuminated 

F

BAT 

fuse 

F 2A 

Mechanical specifications (tab. 3). 

Enclosure dimensions 

70 x 69 x 89 (WxHxD) 

Fixing 

on DIN TH35 rail 

Net/gross weight 

0,19kg/0,25kg 

Enclosure 

plastic, white 

Connectors 

power supply, outputs, battery outputs, technical outputs: 

Φ

0,63÷2,50 (AWG 22-10) 

 

Operating specifications (tab.4). 

Operating temperature 

-10ºC...+40ºC  

Storage temperature 

-20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insolation 

unacceptable 

Vibrations and impulse waves during transport 

PN-83/T-42106 

 

2. Installation. 
 

2.1 Requirements 
 
The  buffer  PSUmodule  is  to  be  mounted  by  a  qualified  installer,  holding  relevant  permits  and  licenses 

(applicable  and  required  for  a  given  country)  for  230V/AC  interference  and  low-voltage  installations.  The  unit 
should  be  mounted  in  confined  spaces,  in  accordance  with  the  2nd  environmental  class,  with  normal  relative 
humidity (RH=90% maximum, without condensation) and temperature from -10°C to +40°C. The PSU module sh all 
work in a vertical position that guarantees sufficient convectional air-flow through ventilating holes of the enclosure. 
The PSU module provides voltage of 27,6 V DC with current capacity: 
 

        1. Output current 1A (without a battery) 

 

2. Output current 0,8A + 0,2A battery charge 
3. Output current 0,5A + 0,5A battery charge 

 

 

Total current of the rec battery: 1A max. 

 

As  the  PSU  module  is  designed  for  a  continuous  operation  and  is  not  equipped  with  a  power-switch, 

therefore  an  appropriate  overload  protection  shall  be  guaranteed  in  the  power  supply  circuit.  Moreover,  the  user 
shall  be  informed  about  the  method  of  unplugging  (most  frequently  through  separating  and  assigning  an 
appropriate fuse in the fuse-box). The electrical system shall follow valid standards and regulations. 
The device should be installed in the metallic enclosure, distribution board (ICT cabinet) equipped with a DIN TH35 
rail (35 mm wide). In order to meet the UE requirements, the rules concerning: supply, development and shielding 

Summary of Contents for MSRD 1024

Page 1: ...MSRD 1024 v 1 0 MSRD 27 6V 1A Buffer switch mode power supply module EN Edition 1st 14th Mar 2012 Supercedes ...

Page 2: ...t 0 8A 0 2A battery charge 3 Output current 0 5A 0 5A battery charge Total current of the receivers battery 1A max In case of power failure a battery back up is activated immediately The battery charging current is preset to 0 2A Features Uninterrupted supply of 27 6VDC 1A supply voltage external transformer required 27 30VAC AWT5172430 AWT049 high efficiency 85 battery charging and maintenance co...

Page 3: ...n collector type FAC AC absence technical output normal status L level 0V failure status hi Z level indication time lag approx 10 sec GND joint terminal FPS technical output of the PSU failure OC type normal status L level 0V failure status hi Z level 4 IBAT pin battery charging current adjustment IBAT Ibat 0 2A IBAT Ibat 0 5A Caption jumper on jumper off 5 VADJ potentiometer DC voltage adjustment...

Page 4: ...ng time 20ms 40ms 12ms Izn Uac min Voltage adjustment range 24 0 V 28 V Ripple voltage 40mV p p max Current drawn by the PSU module systems 25 mA max Battery charging current 0 2A 0 5A IBAT jumper selectable Short circuit protection SCP 200 250 of PSU module power current limitation and or fuse damage in the battery circuit fuse element replacement required Overload protection OLP 110 150 25ºC 55º...

Page 5: ...unacceptable Direct insolation unacceptable Vibrations and impulse waves during transport PN 83 T 42106 2 Installation 2 1 Requirements The buffer PSUmodule is to be mounted by a qualified installer holding relevant permits and licenses applicable and required for a given country for 230V AC interference and low voltage installations The unit should be mounted in confined spaces in accordance with...

Page 6: ...n a DIN rail 3 Operating status indication 3 1 LED indication The PSU module is equipped with four diodes indicating operating status AC LB AUX FBAT AC red diode under normal status AC supply the diode is permanently illuminated The absence of AC supply is indicated by the AC diode going out AUX green diode indicates the DC supply status in the output of the PSU module Under normal status the diod...

Page 7: ...output requires the replacement of the fuse 4 2 Battery assisted operation In case of the main power outage the device is immediately switched into a battery assisted operation In order to run the PSU module from the battery only connect the BAT connectors in accordance with the signs BAT red to plus and BAT black to minus then press the START button on the main board and hold it for 5 seconds The...

Page 8: ...eriod mentioned in item 6 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 8 All the services rendered by force of the warranty are carried out at the service centre of the manufacturer exclusively 9 The warranty does not cover the defects of the equipment resulti...

Reviews: