www.pulsar.pl MSRD1024
5
Technical outputs:
- FAC; output indicating failure of AC power
supply
- FPS; technical output of the PSU operation
status
-R – relay type, 1A@ 30Vdc/50Vac max.
CAUTION! In Fig.2. the set of contacts indicates potential-
free status which corresponds to AC power outage (AC
power failure)
- OC type, 50mA max., normal status: L (0V) level, failure:
hi-Z level, time lag: 10s.
- OC type, 50mA max. normal status: L (0V) level, failure:
hi-Z level (automatic return after restoration of correct
operation)
LED indication
- AC diode indicating AC power
- AUX diode indicating DC at the PSU output
- LB diode indicating battery charging process
- F
BAT
diode indicating battery fuse status
- red, normal status: permanently illuminated
- green, normal status: permanently illuminated
- yellow, the light intensity depends on battery charging
current
- blue, normal status: off, fuse failure: permanently
illuminated
F
BAT
fuse
F 2A
Mechanical specifications (tab. 3).
Enclosure dimensions
70 x 69 x 89 (WxHxD)
Fixing
on DIN TH35 rail
Net/gross weight
0,19kg/0,25kg
Enclosure
plastic, white
Connectors
power supply, outputs, battery outputs, technical outputs:
Φ
0,63÷2,50 (AWG 22-10)
Operating specifications (tab.4).
Operating temperature
-10ºC...+40ºC
Storage temperature
-20ºC...+60ºC
Relative humidity
20%...90%, without condensation
Vibrations during operation
unacceptable
Impulse waves during operation
unacceptable
Direct insolation
unacceptable
Vibrations and impulse waves during transport
PN-83/T-42106
2. Installation.
2.1 Requirements
The buffer PSUmodule is to be mounted by a qualified installer, holding relevant permits and licenses
(applicable and required for a given country) for 230V/AC interference and low-voltage installations. The unit
should be mounted in confined spaces, in accordance with the 2nd environmental class, with normal relative
humidity (RH=90% maximum, without condensation) and temperature from -10°C to +40°C. The PSU module sh all
work in a vertical position that guarantees sufficient convectional air-flow through ventilating holes of the enclosure.
The PSU module provides voltage of 27,6 V DC with current capacity:
1. Output current 1A (without a battery)
2. Output current 0,8A + 0,2A battery charge
3. Output current 0,5A + 0,5A battery charge
Total current of the rec battery: 1A max.
As the PSU module is designed for a continuous operation and is not equipped with a power-switch,
therefore an appropriate overload protection shall be guaranteed in the power supply circuit. Moreover, the user
shall be informed about the method of unplugging (most frequently through separating and assigning an
appropriate fuse in the fuse-box). The electrical system shall follow valid standards and regulations.
The device should be installed in the metallic enclosure, distribution board (ICT cabinet) equipped with a DIN TH35
rail (35 mm wide). In order to meet the UE requirements, the rules concerning: supply, development and shielding