Pulsar MSRD 1024 Manual Download Page 2

www.pulsar.pl                                                                        MSRD1024                                                                        

 

 

 

 
 
 

 
 
 
 
 

CONTENTS: 
1. Technical description. 

1.1 General description 
1.2. Block diagram 
1.3. Description of components and connectors 
1.4. Specifications 

2. Installation. 

2.1 Requirements 
2.2 Installation procedure 

3. Operating status indication. 

3.1 LED indication 
3.2. Technical outputs 

4. Operation and use 

4.1. Overload or short circuit of the PSU module output 
4.2. Battery-assisted operation 

 

4.3. Maintenance 

 
 
 
 
1. Technical description 

 
1.1 General description 

 

A buffer PSU module is intended for an uninterrupted supply to alarm systems devices requiring stabilised 

voltage of 24V/DC (+/-15%). The PSU module provides voltage of 27,6 V DC with current capacity: 
 

    

1. Output current 1A (without a battery) 

 

2. Output current 0,8A + 0,2A battery charge 
3. Output current 0,5A + 0,5A battery charge  
Total current of the rec battery: 1A max. 

 
In case of power failure, a battery back-up is activated immediately. The battery charging current is preset to 0,2A.  

 

 

 

 

Features:

 

 

Uninterrupted supply of 27,6VDC/1A 

 

supply voltage: external transformer required 

27-30VAC (AWT5172430, AWT049) 

 

high efficiency 85% 

 

battery charging and maintenance control 

 

deep discharge battery protection (UVP) 

 

battery output protection against short-circuit and 

reverse polarity connection 

 

jumper selectable battery charging current 

0,2A/0,5A  

 

battery fuse status control 

 

LED indication  

 

 

START facility for manual battery connection

 

 

STOP button for battery disconnection during 

battery-assisted operation 

 

FAC technical output indicating AC power 

collapse 

 

FPS technical output indicating PSU failure 

  protections: 

 

SCP short-circuit protection 

 

OLP overload protection 

 

surge protection 

Summary of Contents for MSRD 1024

Page 1: ...MSRD 1024 v 1 0 MSRD 27 6V 1A Buffer switch mode power supply module EN Edition 1st 14th Mar 2012 Supercedes ...

Page 2: ...t 0 8A 0 2A battery charge 3 Output current 0 5A 0 5A battery charge Total current of the receivers battery 1A max In case of power failure a battery back up is activated immediately The battery charging current is preset to 0 2A Features Uninterrupted supply of 27 6VDC 1A supply voltage external transformer required 27 30VAC AWT5172430 AWT049 high efficiency 85 battery charging and maintenance co...

Page 3: ...n collector type FAC AC absence technical output normal status L level 0V failure status hi Z level indication time lag approx 10 sec GND joint terminal FPS technical output of the PSU failure OC type normal status L level 0V failure status hi Z level 4 IBAT pin battery charging current adjustment IBAT Ibat 0 2A IBAT Ibat 0 5A Caption jumper on jumper off 5 VADJ potentiometer DC voltage adjustment...

Page 4: ...ng time 20ms 40ms 12ms Izn Uac min Voltage adjustment range 24 0 V 28 V Ripple voltage 40mV p p max Current drawn by the PSU module systems 25 mA max Battery charging current 0 2A 0 5A IBAT jumper selectable Short circuit protection SCP 200 250 of PSU module power current limitation and or fuse damage in the battery circuit fuse element replacement required Overload protection OLP 110 150 25ºC 55º...

Page 5: ...unacceptable Direct insolation unacceptable Vibrations and impulse waves during transport PN 83 T 42106 2 Installation 2 1 Requirements The buffer PSUmodule is to be mounted by a qualified installer holding relevant permits and licenses applicable and required for a given country for 230V AC interference and low voltage installations The unit should be mounted in confined spaces in accordance with...

Page 6: ...n a DIN rail 3 Operating status indication 3 1 LED indication The PSU module is equipped with four diodes indicating operating status AC LB AUX FBAT AC red diode under normal status AC supply the diode is permanently illuminated The absence of AC supply is indicated by the AC diode going out AUX green diode indicates the DC supply status in the output of the PSU module Under normal status the diod...

Page 7: ...output requires the replacement of the fuse 4 2 Battery assisted operation In case of the main power outage the device is immediately switched into a battery assisted operation In order to run the PSU module from the battery only connect the BAT connectors in accordance with the signs BAT red to plus and BAT black to minus then press the START button on the main board and hold it for 5 seconds The...

Page 8: ...eriod mentioned in item 6 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 8 All the services rendered by force of the warranty are carried out at the service centre of the manufacturer exclusively 9 The warranty does not cover the defects of the equipment resulti...