The connection between the Ethernet interface and the power supply requires checking whether
the serial port communication parameters are the same.
5. PSU configuration
5.1 Configuration of power supplies of PSBEN series with LCD display.
The PSU is fitted with LCD display, which enables setting the communication parameters of the
serial port from the LCD panel. To enter the setup mode, press the „SET” button from the main screen.
- use the „>” or „<” buttons to display the
PSU
menu
- press the „SET” button
- use the „>” or „<” buttons to display the
Transmission
menu
(The
Transmission
menu is at the bottom of the screen)
- press the „SET” button, the prompt will appear at the end of the line
- use the „>” or „<” buttons to set the
19.2k 8E1
- confirm by pressing the "SET" button