5
Protection in 230V circuit
Glass fuse T3,15A
Glass fuse T5A
LED operation indication
- LEDs on PCB of power supply unit
-
LED indicators on power supply’s cover (see section 3.1)
Technical output FPS
–
fuse failure
relay: 1 A@ 30 V DC /50 V AC,
Connectors
Power supply: 0,5
– 2,5 mm
2
(AWG 26
– 12)
AUX outputs and technical outputs: 0,5
– 2,5 mm
2
(AWG 26
– 12)
Notes
Convectional cooling
Forced cooling (fan)
Table 5. Mechanical parameters.
HPSDC-12V4x1A
HPSDC-12V8x1A
HPSDC-12V16x1A
Enclosure dimensions
(WxH) [±2mm]
270x200
270x200
300x258
Enclosure dimensions
(W
1
xH
1
xD
1
+D) [±2mm]
2758
2758
3058
Mounting (WxH)
237x170
237x170
267x226
Net/gross weight
1,7 / 1,8 [kg]
1,8 / 1,9 [kg]
2,7 / 2,8 [kg]
Enclosure
Steel sheet DC01 0,7mm
Closing
screwed (at the front), (lock assembly possible)
Notes
Enclosure does not adjoin assembly surface so that cables can be led.
Table 6. Operation safety.
Protection class EN 62368-1
I (first)
Protection grade EN 60529
IP20
Electrical strength of insulation:
- between input and output circuits of PSU
- between input circuit and protection circuit
- between output circuit and protection circuit
2500 V AC min.
1500 V AC min.
500 V AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500 V DC
Table 7. Operating parameters.
Operating temperature
-
10ºC...+40ºC
Storage temperature
-
20ºC...+60ºC
Relative humidity
20%...90%, without condensation
Vibrations during operation
unacceptable
Impulse waves during operation
unacceptable
Direct insolation
unacceptable
Vibrations and impulse waves during transport
According to PN-83/T-42106
2. Installation.
2.1. Requirements.
PSU is to be mounted by a qualified installer, holding relevant permits and licenses (applicable and required for a
given country) for 230 V in and low-voltage installations. Unit should be mounted in confined spaces, in accordance, with
normal relative humidity (RH=90% maximum, without condensing) and temperature from -
10°C to +40°C. The PSU shall
work in a vertical position that guarantees sufficient convectional air-flow through ventilating holes of the enclosure.
As power supply is designed for a continuous operation and is not equipped with a power-switch, therefore, an
appropriate overload protection in power supply circuit should be provided. Moreover, the user shall be informed about
the method of unplugging (most frequently through separating and assigning an appropriate fuse in the fuse-box).
The electrical system shall follow valid standards and regulations.