background image

 

LED green AC: 

 

 on 

– PSU is supplied with 230 V  

 

 off 

– no 230 V power 

LED red FPS:  

 

off 

– no failure 

 

on 

– indicates fuse failure 

 

2.2. Installation procedure.

  

 

CAUTION! 
Before  installation,  cut  off  voltage  in  230  V  power-supply  circuit.  To  switch  power  off,  use  an 
external  switch,  in  which  distance  between  contacts  of  all  poles  in  disconnection  state  is  not  less 
than 3mm. 
 

         It is required to install an installation switch with a nominal current of min. 6 A in the power supply circuits 
outside the power supply unit. 

1.  Mount the PSU in a selected location and connect the wires.  

2.  Connect power cables (~230 V AC) to L-N clips of PSU. Connect ground wire to clip marked by earth symbol  

.  

Use a three-core cable (with a yellow and green protection wire

 

). Lead the power cables to the relevant terminals of 

the power supply via an isolation conduit. 

 

 

Shock  protection  circuit  shall  be  done  with  a  particular  care:  yellow  and  green  wire  coat  of  power 
cable  should  be  connected  to  terminal  marked  with  the  grounding  symbol  on  PSU  enclosure. 
Operation  of  PSU  without  the  properly  made  and  fully  operational  shock  protection  circuit  is 
UNACCEPTABLE! It can cause damage to equipment or an electric shock.

  

 

 

3.  Switch on 230 V supply. The LEDs on the PCB and on the lid of PSU should light up (see Section 3.1).  
4.  Check output voltage and adjust if necessary using potentiometer. 
5.  Disconnect  the  PSU  from  the  mains  and  make  the  rest  of  the  connections  -  connect  wires  to  the  AUX1...AUXn 

connectors.  If  necessary,  connect  the  wires  from  devices  (control  panel,  controller,  siren,  etc.)  to  the  PSU  technical 
outputs FPS (fuse failure indication output). 

6. 

Once the tests and control operation have been completed, close the enclosure. 

 

3.  Operating status indication.

 

 

The power supply unit features LED status indication: 

 

3.1 Optical indication. 

 

The power supply unit features LED status indication. Presence of voltage at each output of the PSU is indicated 

by the green LED nearby each outputs fuse. Failure (fuse damage) is indicated by shutting down green LED nearby 
appropriate  outputs  fuse  on  the  PSU  module  and  illuminating  the  red  LED  FPS.  Status  of  the  PSU  (fuse  damage 
AUX1 ÷ AUXn) can be remotely controlled via the FPS technical output. 

 

In addition, there is an additional indication on the lid of the power supply: 
 

 

 
 
 
 
 
   
  
4.   Technical output. 

 

The PSU features a relay type output indicating FPS fuse failure. 

Caution! In Fig. 4 set of contacts shows a potential-free status of relay, which corresponds to power supply failure.  
 

 

 

 

Fig. 4 Technical output diagram 

 
 

        

Reviews: