background image

www.pulsar.pl                                                      HPSBOC2512B            

 

 

2

 

Features: 

 

 

DC 13,8V/3A  uninterruptible power supply  

 

fitting battery: 17Ah/12V 

 

wide range of mains supply: 176÷264V  

 

high efficiency 76% 

 

battery charging and maintenance control 

 

excessive discharging (UVP) protection 

 

battery charge current 0,5A 

 

battery output full protection against short-

circuit and reverse polarity connection 

 

LED indication  

 

 

FAC technical output indicating AC power loss 

 

FPS technical output indicating PSU failure 

 

FLB technical output indicating battery low 
voltage 

 

protections: 

 

SCP short-circuit protection 

 

OVP overvoltage protection 

 

overvoltage protection   

 

against sabotage 

 

overload protection (OLP) 

 

warranty – 3 year from the production date

 

 

 

CONTENTS: 
1. Technical description. 

1.1 General description 
1.2 Block diagram 
1.3 Description of elements and connectors of the PSU 
1.4 Specifications 

2. Installation. 

2.1 Requirements 
2.2 Installation procedure 

3. Operating status indication. 

3.1 LED indication of operating status 
3.2 Technical outputs

 

4. Operation and use. 

4.1 Overload or short circuit of the PSU output (SCP on) 
4.2. Battery-assisted operation 
4.3 Maintenance 

 

 
1. Technical description. 
 

1.1 General description. 
A buffer PSU intended for uninterrupted supply to devices that require stabilised voltage of 12 V DC (+/-

15%). The PSU provides voltage of U=13,8 V DC with output current of I=3A + 0,5A  for battery charging. In case 
of power decay, a battery back-up is activated immediately.  The PSU is constructed based on the switch mode 
PSU,  with  high energy efficiency. The PSU is housed in a metal enclosure (colour RAL 9003) which can 
accommodate a 17Ah/12V battery. A micro switch indicates door opening (front cover). 

 
During normal operation, the total current drawn by the equipment may not exceed I = 3A. 

Maximum battery charging current: 0.5 A. Total device c battery: 3.5 A max. 

 

OPTIONAL POWER SUPPLY CONFIGURATIONS:  

(visualisation available at: 

www.pulsar.pl) 

BATTERY 17Ah: 

 

1.  Buffer power supply unit HPSBOC 13,8V/3x1A/17Ah. 

- HPSBO  LB4 3x1,0A (AWZ576 lub AWZ575) + 17Ah 

2.  Buffer power supply unit HPSBOC 13,8V/6x0,5A/17Ah. 

- HPSBO  LB8 6x0,5A (AWZ580 lub AWZ578) + 17Ah 

             3.  Buffer power supply unit HPSBOC 13,8V/12V/3A/17Ah. 

- HPSBO RN250 (13,8V/12V) + 17Ah 

4.  Buffer power supply unit HPSBOC 13,8V/12V/3x1A/17Ah. 

- HPSBO RN500 (13,8V/12V) + LB4 3x1,0A (AWZ576 lub AWZ575) + 17Ah 

5.  Buffer power supply unit HPSB 13,8V/5V÷7,4V/2A/17Ah. 

- HPSBO DCDC20 (5V÷7,4V/2A) + 17Ah 
 

Summary of Contents for HPSBOC 3512C

Page 1: ...HPSBOC 3512C v 1 0 HPSBOC 13 8V 3A 17Ah OC Buffer switch mode power supply unit with automatic operation control EN Edition 1 from 22 01 2013 Supercedes the edition...

Page 2: ...Maintenance 1 Technical description 1 1 General description A buffer PSU intended for uninterrupted supply to devices that require stabilised voltage of 12 V DC 15 The PSU provides voltage of U 13 8 V...

Page 3: ...components and connectors Table 1 Elements of the module s tab 1 fig 2 Element no Description 1 LED indicating presence of AC power 2 LED indicating presence of DC power 3 LED indicating correct batte...

Page 4: ...ation Output current 3 A 0 5A battery charge Output current tAMB 30 C 3 A 0 5A battery charge refer to chart 1 Output current tAMB 40 C 2 1 A 0 5A battery charge refer to chart 1 Voltage adjustment ra...

Page 5: ...kg Enclosure Steel plate DC01 0 7mm colour RAL 9003 Closing Cheese head screw x 1 at the front lock assembly possible Connectors Power supply 0 63 2 50 AWG 22 10 Outputs 0 63 2 50 AWG 22 10 Battery ou...

Page 6: ...he fuse box The electrical system shall follow valid standards and regulations 2 2 Installation procedure 1 Before installation cut off the voltage in the 230V power supply circuit 2 Mount the PSU in...

Page 7: ...approx 10 seconds CAUTION In Fig 2 the contact set in the potential free status corresponds to a state with no AC power AC power failure FPS technical output indicating absence of DC voltage at the P...

Page 8: ...ly filled warranty claim with a description of the defect 5 Should the claim be accepted the manufacturer is obliged to provide warranty repairs at the earliest convenienve however not later that with...