background image

www.pulsar.pl                                                      HPSBOC2512B            

 

 

6

 

RED LED: 

 

on – the PSU is supplied with 230V AC  

 

off – no 230V AC supply  

 

GREEN LED: 

 

on – DC voltage in the AUX output of the PSU 

 

off – no DC voltage in the AUX output of the PSU 

 

2. Installation. 

 

2.1 Requirements. 

 

The buffer PSU shall be mounted by a qualified installer with appropriate  permissions and qualifications for 

230V/AC installations and low-voltage installations (required and necessary for a given country). The device shall 
be  mounted  in  confined  spaces,  according  to  the  environment  class  II,  with  normal  air  humidity  (RH=90%  max. 
without  condensation)  and  the  temperature  from  -10°C  to  +40°C.  The  PSU  shall  work  in  a  vertical  positi on  that 
guarantees sufficient convectional air-flow through ventilating holes of the enclosure. 

 
Before  installation,  prepare  a  PSU  load  balance.  During  normal  operation,  the  total  current  drawn 

by  the  device  may  not  exceed  I  =  3A.    Maximum  battery  charge  current:  0.5  A.  Total  device  current  + 
battery: 3.5 A max. 

 
As the PSU is designed for a continuous operation and is not equipped with a power-switch, therefore an 

appropriate  overload  protection  shall  be  guaranteed  in  the  power  supply  circuit.  Moreover,  the  user  shall  be 
informed  about  the  method  of  unplugging  (usually  through  assigning  an  appropriate  fuse  in  the  fuse-box).  The 
electrical system shall follow valid standards and regulations. 

 

 
2.2 Installation procedure. 
 

1. Before installation, cut off the voltage in the 230V power-supply circuit. 
2. Mount the PSU in a selected location and connect the wires. 
3. Connect the power cables (~230Vac) to L-N clips of the PSU. Connect the ground wire to the clip marked by the 
earth symbol PE. Use a three-core cable (with a yellow and green PE protection wire) to make the connection. 
Lead the cables to the appropriate clips through the insulating bushing of the connection board. 
 

 

The shock protection circuit shall be performed with a particular care, i.e. the yellow and 
green wire coat of the power cable shall stick to one side of the terminal - marked with  

 symbol on the PSU enclosure. Operation of the PSU without the properly made and 

fully  operational  shock  protection  circuit  is  UNACCEPTABLE!  It  can  cause  a  device 
failure or an electric shock. 

 
4. Connect the receivers’ cables to the terminals 

V+ (+), V-(-) 

 of the PSU module.  

5. Connect the power (~230V) 
6. Connect the battery (mind the colours):   
- battery output (+V):  BAT+ cable / red, 
- battery output (0V):  BAT – cable / GND / black. 
7. Check the PSU operation indicator: green LED. 
8. Check the PSU output voltage: 
- the PSU voltage without load should amount to U=13.8V DC.   
9. After installing and checking proper working, the enclosure can be closed. 
 
3. Operating status indication. 

 
3.1 LED indication of operating status. 
The  is equipped with two diodes on the front panel: 
 
 
 

 

 
 

 

 

Summary of Contents for HPSBOC 3512C

Page 1: ...HPSBOC 3512C v 1 0 HPSBOC 13 8V 3A 17Ah OC Buffer switch mode power supply unit with automatic operation control EN Edition 1 from 22 01 2013 Supercedes the edition...

Page 2: ...Maintenance 1 Technical description 1 1 General description A buffer PSU intended for uninterrupted supply to devices that require stabilised voltage of 12 V DC 15 The PSU provides voltage of U 13 8 V...

Page 3: ...components and connectors Table 1 Elements of the module s tab 1 fig 2 Element no Description 1 LED indicating presence of AC power 2 LED indicating presence of DC power 3 LED indicating correct batte...

Page 4: ...ation Output current 3 A 0 5A battery charge Output current tAMB 30 C 3 A 0 5A battery charge refer to chart 1 Output current tAMB 40 C 2 1 A 0 5A battery charge refer to chart 1 Voltage adjustment ra...

Page 5: ...kg Enclosure Steel plate DC01 0 7mm colour RAL 9003 Closing Cheese head screw x 1 at the front lock assembly possible Connectors Power supply 0 63 2 50 AWG 22 10 Outputs 0 63 2 50 AWG 22 10 Battery ou...

Page 6: ...he fuse box The electrical system shall follow valid standards and regulations 2 2 Installation procedure 1 Before installation cut off the voltage in the 230V power supply circuit 2 Mount the PSU in...

Page 7: ...approx 10 seconds CAUTION In Fig 2 the contact set in the potential free status corresponds to a state with no AC power AC power failure FPS technical output indicating absence of DC voltage at the P...

Page 8: ...ly filled warranty claim with a description of the defect 5 Should the claim be accepted the manufacturer is obliged to provide warranty repairs at the earliest convenienve however not later that with...