5
1.4 Technical parameters:
- electrical parameters (tab.3)
- mechanical parameters (tab.4)
- operation safety (tab.5)
- operation parameters (tab.6)
Electrical parameters
(tab. 3)
Supply voltage
85÷264V AC; 50÷60Hz, 120÷370V DC
Power frequency
50÷60Hz lub DC
Supply power P
55W max.
Current consumption
0.5A@230VAC max.
Output voltage
13.8V DC – buffer operation
9.5V÷13.4V DC – battery operation
Ripple voltage
100mV p-p max.
Output current t
AMB
<30°C
4.0 A const.*
Output current t
AMB
=40°C
2.8 A const.*
Current consumption by power-supply circuits
20mA@ Io=0A (max.)
Battery charging current
0.23A max. @ 17Ah (± 5%)
Short-circuit protection SCP
electronic
Overload protection OLP
PTC fuse
Overvoltage protection OVP
U>115% ÷ 150% - of the output voltage (set), isolation
of the output voltage
Excessive discharge protection UVP
U < 9.5 V (± 5%) – disconnection of +BAT terminal
Technical outputs:
- TAMPER output indicating opening of the power-
supply casing
- microswitch, NC contacts (closed casing),
0.5A@50V DC (max.)
* - refer to chart 1.
Mechanical parameters (tab. 4)
Casing dimensions
285 x 296 x 90 (280 x 291 x 82) (WxHxD)
Fixation
See figure 2
Battery
17Ah/12V (SLA) max.
Net/gross weight
2.05kg / 2.25kg
Casing color
RAL 9003
Closing
Cheese screw x 4 (lock assembly possible)
Connectors
Power-supply: Φ0,63-2,50 (AWG 22-10)
Outputs : Φ0,63-2,50 (AWG 22-10)
Battery output BAT: 6,3F-2,5
TAMPER output: wires
Notes
The casing is distant from the assembly surface so that cables can be installed
Operation safety (tab.5)
Protection class PN-EN 60950-1:2004
I (first)
Protection grade PN-EN 60529: 2002 (U)
IP20
Electrical strength of insulation:
- between input (network) circuit and output circuits of power-supply (I/P-
O/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit (O/P-FG)
3000 V/AC min.
1500 V/AC min.
500 V/AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500V/DC