1.4 Technical parameters:  
- electrical parameters (tab.3) 
- mechanical parameters (tab.4) 
- operation safety (tab.5) 
- operation parameters (tab.6) 

      

Electrical parameters

 (tab. 3) 

Supply voltage 

85÷264V AC; 50÷60Hz, 120÷370V DC 

Power frequency 

50÷60Hz lub DC 

Supply power P 

55W max.  

Current consumption 

0.5A@230VAC max. 

Output voltage 

13.8V DC – buffer operation 
9.5V÷13.4V DC – battery operation 

Ripple voltage 

100mV p-p max. 

Output current t

AMB

<30°C 

4.0 A const.* 

Output current t

AMB

=40°C 

2.8 A const.* 

Current consumption by power-supply circuits  

20mA@ Io=0A (max.) 

Battery charging current 

0.23A max. @ 17Ah (± 5%) 

Short-circuit protection SCP 

electronic 

Overload protection OLP 

PTC fuse  

Overvoltage protection OVP 

U>115% ÷ 150% - of the output voltage (set), isolation 
of the output voltage 

Excessive discharge protection UVP 

U < 9.5 V (± 5%) – disconnection of +BAT terminal 

Technical outputs: 
- TAMPER output indicating opening of the power-
supply casing 

- microswitch, NC contacts (closed casing), 
0.5A@50V DC (max.) 

* - refer to chart 1. 

      

Mechanical parameters (tab. 4) 

Casing dimensions 

285 x 296 x 90  (280 x 291 x 82) (WxHxD) 

Fixation 

See figure 2 

Battery 

17Ah/12V (SLA) max. 

Net/gross weight 

2.05kg / 2.25kg 

Casing color 

RAL 9003 

Closing 

Cheese screw x 4 (lock assembly possible) 

Connectors 

Power-supply: Φ0,63-2,50 (AWG 22-10) 
Outputs : Φ0,63-2,50 (AWG 22-10) 
Battery output BAT: 6,3F-2,5  
TAMPER output: wires  

Notes 

The casing is distant from the assembly surface so that cables can be installed 

      

Operation safety (tab.5) 

Protection class PN-EN 60950-1:2004 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between input (network) circuit and output circuits of power-supply (I/P-
O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
 
3000 V/AC min. 
1500 V/AC min. 
500  V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500V/DC  

 

Summary of Contents for HPSBC 0412

Page 1: ...HPSBC 0412 13 8V 4A 17Ah v 1 0 Buffer switching power supply unit EN Edition 1 st from 31th of December 2010 Supercedes edition...

Page 2: ...er supply to devices that require stabilised voltage of 13 8 V DC 15 The power supply provides a voltage of U 13 8 V DC 9 5 V 13 4 V DC battery mode with an output current of I 4 0A In the case of an...

Page 3: ...ly output 4 Potentiometer adjustment of the output voltage 5 BAT GND battery outputs BAT red BAT black 6 TAMPER contact of antisabotage protection NC Tab 1 The elements of the power supply Element no...

Page 4: ...4 Fig 2 The view of the power supply...

Page 5: ...puts TAMPER output indicating opening of the power supply casing microswitch NC contacts closed casing 0 5A 50V DC max refer to chart 1 Mechanical parameters tab 4 Casing dimensions 285 x 296 x 90 280...

Page 6: ...s started the balance of the power supply load shall be performed During the normal operation the sum of currents collected by receivers shall not exceed I 4 0A As the power supply is designed for a c...

Page 7: ...wer supply operation status 3 1 Optical indication of operation status The power supply is equipped with an optical indicator of the output voltage state LED diode green on the PCB panel indicates Lit...

Page 8: ...d the claim be accepted the manufacturer is obliged to render warranty repairs as soon as possible however not later that within 14 days from the delivering of the equipment to the service centre of t...

Reviews: