1.4 Specifications:  
   - electrical parameters (tab.3) 
   - mechanical parameters (tab.4) 
   - operation safety (tab.5) 
   - operating parameters (tab.6) 

 

      

Electrical parameters (tab. 3) 

PSU type 

A (EPS - External Power Source) 

Mains supply 

 

176

÷264V AC 

Current up to 

0,6A@230VAC 

Power frequency 

50÷60Hz  

Supply power 

50W max.  

Efficiency 

76% 

Output voltage 

13,8V DC 

– buffer operation 

9,5V÷13,8V DC – battery-powered operation 

Output current t

AMB

<30°C 

3A + 0,5A battery charge - refer to chart 1 

Output current t

AMB

=40°C 

2,1A + 0,5A battery charge - refer to chart 1 

Voltage adjustment range 

12

÷14VDC 

Ripple 

120mV p-p max. 

Battery charge current 

0,5A max. @ 7Ah (

± 5%) 

Short-circuit protection SCP 

electronic, automatic return 

Overload protection OLP 

105-150% of the PSU power, automatic return 

Battery circuit protection SCP and reverse  
polarity connection 

PTC polymer fuse 

Surge protection 

varistors 

Overvoltage protection OVP 

>16V (automatic recovery) 

Excessive discharge protection UVP 

U<9,5V (

± 5%) – disconnect of connection battery  

Sabotage protection: 
- TAMPER output indicating enclosure opening 

 
- microswitch, NC contacts (enclosure closed), 
0,5A@50V DC (max.) 

LED indication:  
- AC diode indicating AC power status 
 
- AUX diode indicating DC power status at 
the PSU output 

 
- red, normal status 

– on, failure: off 

 
- green, normal status 

– on, failure: off  

 

Summary of Contents for HPSB 3512B

Page 1: ...HPSB 3512B v 1 0 HPSB 13 8V 3A 7Ah Buffer switch mode power supply unit EN Edition 1 from 19 02 2016 Supercedes the edition...

Page 2: ...status 4 Operation and use 4 1 Overload or short circuit of the PSU output SCP on 4 2 Disconnection of discharged battery 4 3 Maintenance 1 Technical description 1 1 General description A buffer PSU i...

Page 3: ...ab 2 3 green LED indicates AC power 4 P1 potentiometer output voltage adjustment 5 BAT GND battery outputs BAT red GND black 6 TAMPER contact sabotage protection NC 7 Additional connector for LED indi...

Page 4: ...refer to chart 1 Voltage adjustment range 12 14VDC Ripple 120mV p p max Battery charge current 0 5A max 7Ah 5 Short circuit protection SCP electronic automatic return Overload protection OLP 105 150 o...

Page 5: ...in 1500 V AC min 500 V AC min Insulation resistance between input circuit and output or protection circuit 100 M 500V DC Operating parameters tab 6 Operating temperature 10 C 40 C see chart 1 Storage...

Page 6: ...L N clips of the PSU Connect the ground wire to the clip marked by the earth symbol PE Use a three core cable with a yellow and green PE protection wire to make the connection Lead the cables to the a...

Page 7: ...d with the discharged battery disconnection system During the battery assisted operation reducing voltage below 9 5V at the battery terminals will cause battery disconnection 4 3 Maintenance Any and a...

Page 8: ...14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the...